Figure 6. Standard Plumbing Layout
Anchor Clamp(s) Installation, continued
6. Use a masonry drill bit and drill a hole in the cement
with a diameter as determined by the concrete anchor,
at each of the marks on the equipment pad. The hole
should be approximately 1½ in. deep.
7. Insert a bolt anchor into each of the holes. Be sure the
anchors are set completely into the holes
8. Position the anchor clamps so that the holes in the clamps
are over the bolt anchors. Be sure that the clamp hooks
are over the lip of the heat pump base, see
Figure 5
.
9. Insert an anchor bolt through each clamp into the anchor
and tighten to secure the clamp and heat pump to the
equipment pad.
Water Connections
Plumbing layout
Figure 6
illustrates the standard plumbing layout with a single heat pump unit. Follow the diagram from
right to left, the plumbing sequence is as follows:
Note: For normal installations, do not install a shut-off valve or any kind of variable restriction
in the water piping between the heat pump outlet and the pool/spa.
The heat pump must be protected from back-siphoning of water. Be sure to provide an optional manual
bypass valve between the pool and the heat pump outlet to protect from back-siphoning.
Arrangement of pool system components (other than
Figure 6
and following diagrams) can affect the
operation of the heat pump’s water pressure switch. Location of the heat pump above or below the pool
water surface can also affect operation of the switch.
In general, the pressure switch can be adjusted to accommodate this effect if the heat pump water
connections are no more than six (6) feet below the pool water surface or no more than fi fteen (15) feet
above it. See instructions for pressure switch adjustment (
page 16
) in the heat pump start-up section
of this manual for more information. If the heat pump is installed outside of this range, an external
pressure switch may need to be installed in the plumbing upstream of the heat pump. Call the Pentair
Heat Pump Technical Service department at (800) 831-7133 for details.
Be advised that when pool equipment is located below the pool surface a leak can result in large-scale
water loss or fl ooding. Pentair cannot be responsible for such water loss or fl ooding or the damage
caused by either occurrence.
Pool > Skimmer and Main Drain > Pool Pump > Filter > Heat Pump > Chlorinator > Pool
HEAT PUMP
ANCHOR CLAMP
AIR COIL GUARD
AIR
COIL
BOLT ANCHOR
(installer provided)
HEAT PUMP
BASE
1-3/8" HEX BOLT
(installer provided)
CONCRETE
EQUIPMENT PAD