background image

1 Phase Simplex
Control Panel for Grinder 
and Vortex Pumps

Owner and Operational Manual

293 S. Wright St, Delavan, WI 53115 Phone: 1-866-973-6835 Fax: 800-426-9446

P10063VSM

Page 4 of 10

B

la

ck

 -

 P

ro

b

e

Y

e

llo

w

 P

ro

b

e

Seal Probe from pump

Seal Fail may not be an option on your pump.

Pump 1 Seal Fail Probe: 

(Seal Fail may not be an option on your pump) 

Testing Seal Fail Probes:

 

 

0

#1. 

#2. 

 

0

Sensor is good:

 

Sensor is good:

 

#1. Put one ohm meter probe on the Black 
wire of the sensor. 

#2. Place the other ohm meter probe on the 
“Hex” Nut portion of the sensor.  The ohm 
meter should read “continuity” or close to 
zero ohms, If it reads “open” or “High” ohms 
then the sensor is defective. 

#3. Put one ohm meter probe on the seal 
probe. 

#4. Place the other ohm meter probe on the 
yellow wire. The ohm meter should read 
“continuity” or close to zero ohms, If it reads 
“open” or “High” ohms then the sensor is 
defective.  

The Seal Probe wires are connected to terminals 9 and 10 which are 
labeled Pump 1 Seal Sensor. The Black wire from the Seal Probe is 
connected to terminal 9 which is labeled BK for Black. The Yellow wire 
from the Seal Probe is connected to terminal 10 which is labeled YW 

Содержание PENTEK G2D-01

Страница 1: ... 21 V2D 01 V3D 01 V3D 21 Safety Guidelines 1 DO NOT USE WITH FLAMMABLE OR EXPLOSIVE FLUIDS SUCH AS GASOLINE FUEL OIL KERO SENE ETC DO NOT USE IN EXPLOSIVE ATMOSPHERES CONTROL PANEL SHOULD ONLY BE USED IN WATER AND WASTEWATER APPLICATIONS THAT ARE NOT RATED AS A HAZARDOUS LOCATION 2 DO NOT WORK ON THE CONTROL PANEL WITH LIVE VOLTAGE APPLIED TO THE CONTROL PANEL WITH WET HANDS OR WHEN STANDING ON A ...

Страница 2: ... then slide the bracket down so the screws are in the narrow part of the mounting holes Fig 5 then tighten the screws Fig 1 1 The Starter Pack Fig A comes pre assembled with the start capacitor 1 run capacitor 2 and start relay 3 mounted on a plug and play bracket Fig 6 Fig 3 Fig 2 3 After securing the Starter Pack inside of the control panel Fig 6 you will connect the wires from the Starter Pack ...

Страница 3: ...mp 1 Thermal Sensor The remaining two wires will be Blue and Orange They are connected to the terminal block labeled Pump 1 Thermal Sensor BL Blue OR Orange Connecting the Pump and Thermal Wires Blu e T h er m a l O r an g e T h erma l W hit e P ump B la ck P ump R ed P u mp Pump P10063VSM Page 3 of 10 Testing the Thermal Sensor 1 Put one ohm meter probe on the Blue wire and one on the Orange wire...

Страница 4: ...2 Place the other ohm meter probe on the Hex Nut portion of the sensor The ohm meter should read continuity or close to zero ohms If it reads open or High ohms then the sensor is defective 3 Put one ohm meter probe on the seal probe 4 Place the other ohm meter probe on the yellow wire The ohm meter should read continuity or close to zero ohms If it reads open or High ohms then the sensor is defect...

Страница 5: ... Place one of the ohm meter probes on terminal 97 of the overload and place the other probe of the ohm meter on 98 of the overload If your reading is high the overload is not tripped If your reading shows continuity or 0 ohms the unit is tripped and should be reset To verify the Overload has tripped Stop Off Float Start Float Alarm Float Float switches are most commonly used but 1 Phase Simplex Gr...

Страница 6: ...Panel for Grinder and Vortex Pumps Owner and Operational Manual 293 S Wright St Delavan WI 53115 Phone 1 866 973 6835 Fax 800 426 9446 B Alarm Control Power Configurations Alarm Float Normal Float switch function as tank fills Normal Float switch function as tank empty s Start Float Start Off Pump Starts Pump continues to run Pump continues to run Pump turns off Alarm Float Start Float Start Off P...

Страница 7: ...lso used as the System Test switch for diagnosing the control panel The Stop float Start float and Alarm float indicator lights are red 8 position terminal block Auxiliary contact terminal block Circuit Board Terminal Blocks 1 Phase Simplex Grinder Vortex control panels use two terminal blocks for alarm mode configura tions An 8 position main terminal block is for power and level switch connection...

Страница 8: ...Fuse needs to be replaced Control Fuse needs to be 2 View the current status of your system The indicator lights illuminate as each float rises with the liquid level in the tank 1 Alarm Float Start Float Stop Float Alarm Float Start Float Stop Float All three floats are not activated Only the Control Power and Alarm Power indicator lights should be illuminated If the Stop float is activated the St...

Страница 9: ...Operating the pump manually with the HOA Hand Off Auto Place the HOA Hand Off Auto switch in the Off position to turn the pump off from operation completely Place the HOA Hand Off Auto switch in the Auto position to turn the pump with float control When the water level raises the stop and start float the pump turns on and stays on until the stop float drops down If the liquid raises the high level...

Страница 10: ...use the HOA switch is in the hand mode Illustration Fig 3A shows the Stop float is activated but the indicator light on the command center in Fig 2A is not illuminated The Stop float is not working properly and should be replaced Example Fig 3B shown below is demonstrating that the same float is not working but for a different reason In this example the float is hung up in the tank EXAMPLE Fig 2A ...

Отзывы: