background image

P/N 472089

Rev. B  4-5-02

16

INDOOR INSTALLATION (USA ONLY)
OUTDOOR SHELTER INSTALLATION (CANADA)

See page 17 for (Indoor) Vent Adaptors

All products of combustion and vent gases must be
completely removed to the outside atmosphere through
a vent pipe which is connected to the stack adaptor. A
vent pipe extension of the same size must be connected
to the indoor stack adaptor and extended at least 2 feet
higher than highest point of the roof within a 10 foot
horizontal radius, and at least 3 ft. higher than the point
at which it passes through the roof, or as permitted by
local code; see Figures 12 and 13. The vent should
terminate with an approved vent cap (weather cap) for
protection against rain or blockage by snow.  Double-
wall vent pipe and an approved roof jack shall be
employed through the roof penetration.

The heater must be located as close as practical to a
chimney or gas vent.

CAUTION

The heater should be installed at least 5 feet away
from the pool or spa.

The heater must be placed in a suitable room on a non-
combustible floor or on a non-combustible base and in
an area where leakage from heat exchanger or water
connections will not result in damage to the area
adjacent to the heater or the structure.  When such
locations cannot be avoided, it is recommended that a
suitable drain pan with adequate drainage, be installed
under the heater.  The pan must not restrict air flow.

Installations in basements, garages, or underground
structures where flammable liquids may be stored must
have the heater elevated 18 inches from the floor using
a non-combustible base. The following minimum
clearances from combustible materials must be
provided.

Side

Front

Back

Top

Water Connection

18 in.

24 in.

-

-

Remaining

6 in.

-

6 in.

-

Ceiling Clearance

-

-

-

18 in.*

*To ceiling or roof.

;;;

;;;

;;;

Vent
Cap

Ridge

Chimney

3 ft. min.

2 ft. min.

10 ft.

Roof
Jack

AIR SUPPLY
VENTILATION

AIR SUPPLY
GAS COMBUSTION

OPTIONAL SIDE WALL VENT NT

VENT CAP AND
RISER FURNISHED
BY INSTALLER

Installation (Indoor)

The heater should not be installed closer than 6 inches to
any fences, walls or shrubs at any side or back, nor
closer than 18 inches at the plumbing side. A minimum
clearance of 24 inches must be maintained at the front of
the heater.

DOOR

6"

6"

24"

18"

Figure 14.

Figure 12.

Figure 13.

Содержание MiniMax NT Low NOx 200

Страница 1: ...ation and service must be performed by a licensed qualified installer service agency or the gas supplier MiniMax NT Low NOx Series POOL SPA HEATERS OPERATION INSTALLATION MANUAL WARNING WHAT TO DO IF...

Страница 2: ...stallation Water Connections 13 Installation Plumbing 13 Installation Gas Line 14 Pipe Sizing Chart Gas Pressure Requirements 14 Regulated Manifold Pressure Test 14 Venting Indoor Installations 15 18...

Страница 3: ...the MiniMax NT Low NOx pool and spa heater The manufacturer s warranty may be void if for any reason the heater is improperly installed and or operated Be sure to follow the instructions set forth in...

Страница 4: ...e with an accurate thermometer Spa or hot tub thermostats may err in regulating water temperatures by as much as 4 F 5 Persons with a medical history of heart disease circulatory problems diabetes or...

Страница 5: ...G OPERATION NATURAL GAS 1 STOP Read the safety information above 2 Set the thermostat to the lowest setting 3 Turn off electric power to the heater 4 This heater is equipped with an ignition device wh...

Страница 6: ...state be sure your contractor bears the appropriate license SPECIFICATIONS 24 05 2 in SOCKET A DIM 8 84 6 64 30 63 LEG LEG 14 50 3 50 4 875 MODEL 200 250 24 63 21 63 A DIM 15 50 300 400 34 13 27 63 7...

Страница 7: ...supplied with this heater must be replaced installer must supply No 18 AWG 600V 105 C U L approved AWM low energy stranded copper wire or it s equivalent Thermal fuse wiring must be replaced with 18...

Страница 8: ...NITION MOD EXT SWITCH THERMOSTAT CIRCUIT BOARD JUMPER REQUIRED IF NO 2 WIRE REMOTE SWITCH POOL OFF SPA FRONT PANEL THERMOSTAT SELECT SWITCH TFUSE VALVE REMOTE POOL OFF SPA THERMOSTAT SELECT SWITCH PRE...

Страница 9: ...ture 3 Spa position This allows separate control of spa water temperature INDICATOR LIGHT DESCRIPTION The MiniMax NT Heater provides nine status indicator lights six can be seen from the front of the...

Страница 10: ...CUIT BLOCK CURRENT SWITCH OR DEVICE CLOSED CIRCUIT PASS CURRENT THERM AUX PRESS HEAT POWER SERVICE FRONT PANEL LEDS FRONT PANEL LEDS HEAT PRESS AUX THERM SERVICE POWER OR POOL OFF SPA THERMOSTAT SELEC...

Страница 11: ...ERM INCOMING LINE VOLTAGE THERMOSTAT PWR BREAKER CIRCUIT TSTAT RELAY RMT REMOTE THERMOSTAT CIRCUIT BOARD NO MV CLOSE IF IGNITION MODULE SRVE HI TEMP LIMIT SWITCHES HI TEMP TFUSE MV IND TFUSE GND THERM...

Страница 12: ...WHT LOW GAS F1 F2 24 VAC WHT POOL JUMPER REQUIRED J6 PROBE TEMP VLV TPROBE J5 J8 24V J4 J7 IGN MODULE J10 J11 IND PRESSURE SW IF ORIGINAL FACTORY WIRING MUST BE REPLACED INSTALLER MUST SUPPLY UL CSA...

Страница 13: ...perature sensing bulb from the inlet outlet header Note If needed you may cut the wire ties holding them together 5 Remove the 16 bolts holding the main inlet outlet head and return head in place exch...

Страница 14: ...n must be leak tested before placing the heater in operation Do not use flame to test the gas line Use soapy water or another nonflammable method A manual main shut off valve must be installed externa...

Страница 15: ...ombustible materials must be maintained in accordance with type of vent pipe employed in the absence of a clearance recommendation by the vent pipe manufacturer the requirements of the Uniform Mechani...

Страница 16: ...on combustible floor or on a non combustible base and in an area where leakage from heat exchanger or water connections will not result in damage to the area adjacent to the heater or the structure Wh...

Страница 17: ...be contaminated by corrosive chemical fumes which can void the warranty NOTE The openings listed in Table 2 are free open vent area if the vents incorporate restrictive louvers the vent openings must...

Страница 18: ...walkways must be at least 3 ft above any outside air intake located within a 10 ft radius must NOT be within 3 ft of an inside corner of the structure must be at least 1 ft above grade must be located...

Страница 19: ...drainage Maintain minimum clearances as indicated below Install a minimum of 4 feet below and 4 feet horizontally from any opening to a building see Figure 18 IMPORTANT When locating the heater consid...

Страница 20: ...is running and is primed to close water pressure switch and supply power to heater 2 Set thermostat to lowest setting 3 Set the thermostat rocker switch to the center OFF position 4 Open the access do...

Страница 21: ...re than a 3 ft elevation difference between the heater heat exchanger and the pool water line if this is the case the water pressure switch must be reset to maintain open switch contacts with no water...

Страница 22: ...r is activated for a heat up period followed by energization of the gas valve for the trial for ignition period When flame is detected during the trial for ignition the ignitor is deactivated and the...

Страница 23: ...thermostat knob stopper 5 Set time clock to start circulation system no earlier than daybreak The swimming pool loses less heat at this time 6 For pools that are only used on the weekends it is not ne...

Страница 24: ...Then test only once every month or so to be sure it is being maintained See your local pool dealer for help in properly balancing the water chemistry 7 2 6 8 7 0 7 4 7 6 7 8 8 0 8 2 8 4 Add Soda Ash...

Страница 25: ...ter operating after pump has shut off Shut off gas supply and call serviceperson Heater exchanger scaled Shut off gas supply and call serviceperson Troubleshooting General SERVICE CHECKS IGNITION MODU...

Страница 26: ...X NT LOW NOx HEATER Dual Voltage 1 4 3 5 7 8 9 11 28 30 35 36 38 51 50 48 46 44 45 40 39 17 16 15 14 23 13 34 41 26 27 2 6 10 24 25 22 18 31 33 32 37 47 43 42 12 29 19 20 21 MiniMAX NT Low NOx Heater...

Страница 27: ...old Assy 1 472004 472003 472002 472001 32 Burner 4 5 6 8 200 250 300 400 33 Face Plate 1 472069 472068 472067 472052 34 Jacket Upper Panel Left 1 35 Jacket Corner 4 36 Jacket Divider 1 471827 471651 4...

Страница 28: ...dent negligence alteration abuse misapplication or misuse The above warranty applies only if the heater is installed and operated in complete compliance with the installation and operation manual prov...

Отзывы: