background image

Rev. B  4-5-02

             P/N 472089

11

PRESS

PRESS

HEATER FIRING - NORMAL OPERATION

NOTE: SERVICE LED LIT FLAGS PROBLEM, TFUSE LED OFF SHOWS PROBLEM 

PRESS

PRESS

THERMOSTAT CALLING FOR HEAT - BLOWN THERMAL FUSE BLOCKS FIRING

FRONT PANEL LEDS

HEAT

PRESS

AUX

SERVICE

TRANSFORMER

THERM

POWER

INCOMING

LINE VOLTAGE

FRONT PANEL LEDS

PRESS

HEAT

AUX

THERMOSTAT

PWR

CIRCUIT
BREAKER

TSTAT

RELAY

RMT

REMOTE

TRANSFORMER

THERM

INCOMING

LINE VOLTAGE

THERMOSTAT

PWR

BREAKER

CIRCUIT

TSTAT

RELAY

RMT

REMOTE

THERMOSTAT CIRCUIT BOARD

NO MV

CLOSE IF

IGNITION MODULE

SRVE

HI TEMP

LIMIT SWITCHES

HI TEMP

TFUSE

MV

IND

TFUSE

GND

THERMOSTAT CIRCUIT BOARD

GAS VALVE

HEAT

VAL

MV

MV

IGNITION MODULE

SRVE

CLOSE IF

NO MV

HI TEMP

LIMIT SWITCHES

HI TEMP

TFUSE

MV

IND

TFUSE

GND

GAS VALVE

HEAT

VAL

MV

MV

POWER

SERVICE

IS IN THERMAL FUSE CIRCUIT

SYMBOL TABLE

LED LIT

LED OFF

SWITCH OR DEVICE
OPEN CIRCUIT
(BLOCK CURRENT)

SWITCH OR DEVICE
CLOSED CIRCUIT
(PASS CURRENT)

TROUBLESHOOTING (CONTROLS) - Continued

Installation (Operating Controls, cont’d.)

Содержание MiniMax NT Low NOx 200

Страница 1: ...ation and service must be performed by a licensed qualified installer service agency or the gas supplier MiniMax NT Low NOx Series POOL SPA HEATERS OPERATION INSTALLATION MANUAL WARNING WHAT TO DO IF...

Страница 2: ...stallation Water Connections 13 Installation Plumbing 13 Installation Gas Line 14 Pipe Sizing Chart Gas Pressure Requirements 14 Regulated Manifold Pressure Test 14 Venting Indoor Installations 15 18...

Страница 3: ...the MiniMax NT Low NOx pool and spa heater The manufacturer s warranty may be void if for any reason the heater is improperly installed and or operated Be sure to follow the instructions set forth in...

Страница 4: ...e with an accurate thermometer Spa or hot tub thermostats may err in regulating water temperatures by as much as 4 F 5 Persons with a medical history of heart disease circulatory problems diabetes or...

Страница 5: ...G OPERATION NATURAL GAS 1 STOP Read the safety information above 2 Set the thermostat to the lowest setting 3 Turn off electric power to the heater 4 This heater is equipped with an ignition device wh...

Страница 6: ...state be sure your contractor bears the appropriate license SPECIFICATIONS 24 05 2 in SOCKET A DIM 8 84 6 64 30 63 LEG LEG 14 50 3 50 4 875 MODEL 200 250 24 63 21 63 A DIM 15 50 300 400 34 13 27 63 7...

Страница 7: ...supplied with this heater must be replaced installer must supply No 18 AWG 600V 105 C U L approved AWM low energy stranded copper wire or it s equivalent Thermal fuse wiring must be replaced with 18...

Страница 8: ...NITION MOD EXT SWITCH THERMOSTAT CIRCUIT BOARD JUMPER REQUIRED IF NO 2 WIRE REMOTE SWITCH POOL OFF SPA FRONT PANEL THERMOSTAT SELECT SWITCH TFUSE VALVE REMOTE POOL OFF SPA THERMOSTAT SELECT SWITCH PRE...

Страница 9: ...ture 3 Spa position This allows separate control of spa water temperature INDICATOR LIGHT DESCRIPTION The MiniMax NT Heater provides nine status indicator lights six can be seen from the front of the...

Страница 10: ...CUIT BLOCK CURRENT SWITCH OR DEVICE CLOSED CIRCUIT PASS CURRENT THERM AUX PRESS HEAT POWER SERVICE FRONT PANEL LEDS FRONT PANEL LEDS HEAT PRESS AUX THERM SERVICE POWER OR POOL OFF SPA THERMOSTAT SELEC...

Страница 11: ...ERM INCOMING LINE VOLTAGE THERMOSTAT PWR BREAKER CIRCUIT TSTAT RELAY RMT REMOTE THERMOSTAT CIRCUIT BOARD NO MV CLOSE IF IGNITION MODULE SRVE HI TEMP LIMIT SWITCHES HI TEMP TFUSE MV IND TFUSE GND THERM...

Страница 12: ...WHT LOW GAS F1 F2 24 VAC WHT POOL JUMPER REQUIRED J6 PROBE TEMP VLV TPROBE J5 J8 24V J4 J7 IGN MODULE J10 J11 IND PRESSURE SW IF ORIGINAL FACTORY WIRING MUST BE REPLACED INSTALLER MUST SUPPLY UL CSA...

Страница 13: ...perature sensing bulb from the inlet outlet header Note If needed you may cut the wire ties holding them together 5 Remove the 16 bolts holding the main inlet outlet head and return head in place exch...

Страница 14: ...n must be leak tested before placing the heater in operation Do not use flame to test the gas line Use soapy water or another nonflammable method A manual main shut off valve must be installed externa...

Страница 15: ...ombustible materials must be maintained in accordance with type of vent pipe employed in the absence of a clearance recommendation by the vent pipe manufacturer the requirements of the Uniform Mechani...

Страница 16: ...on combustible floor or on a non combustible base and in an area where leakage from heat exchanger or water connections will not result in damage to the area adjacent to the heater or the structure Wh...

Страница 17: ...be contaminated by corrosive chemical fumes which can void the warranty NOTE The openings listed in Table 2 are free open vent area if the vents incorporate restrictive louvers the vent openings must...

Страница 18: ...walkways must be at least 3 ft above any outside air intake located within a 10 ft radius must NOT be within 3 ft of an inside corner of the structure must be at least 1 ft above grade must be located...

Страница 19: ...drainage Maintain minimum clearances as indicated below Install a minimum of 4 feet below and 4 feet horizontally from any opening to a building see Figure 18 IMPORTANT When locating the heater consid...

Страница 20: ...is running and is primed to close water pressure switch and supply power to heater 2 Set thermostat to lowest setting 3 Set the thermostat rocker switch to the center OFF position 4 Open the access do...

Страница 21: ...re than a 3 ft elevation difference between the heater heat exchanger and the pool water line if this is the case the water pressure switch must be reset to maintain open switch contacts with no water...

Страница 22: ...r is activated for a heat up period followed by energization of the gas valve for the trial for ignition period When flame is detected during the trial for ignition the ignitor is deactivated and the...

Страница 23: ...thermostat knob stopper 5 Set time clock to start circulation system no earlier than daybreak The swimming pool loses less heat at this time 6 For pools that are only used on the weekends it is not ne...

Страница 24: ...Then test only once every month or so to be sure it is being maintained See your local pool dealer for help in properly balancing the water chemistry 7 2 6 8 7 0 7 4 7 6 7 8 8 0 8 2 8 4 Add Soda Ash...

Страница 25: ...ter operating after pump has shut off Shut off gas supply and call serviceperson Heater exchanger scaled Shut off gas supply and call serviceperson Troubleshooting General SERVICE CHECKS IGNITION MODU...

Страница 26: ...X NT LOW NOx HEATER Dual Voltage 1 4 3 5 7 8 9 11 28 30 35 36 38 51 50 48 46 44 45 40 39 17 16 15 14 23 13 34 41 26 27 2 6 10 24 25 22 18 31 33 32 37 47 43 42 12 29 19 20 21 MiniMAX NT Low NOx Heater...

Страница 27: ...old Assy 1 472004 472003 472002 472001 32 Burner 4 5 6 8 200 250 300 400 33 Face Plate 1 472069 472068 472067 472052 34 Jacket Upper Panel Left 1 35 Jacket Corner 4 36 Jacket Divider 1 471827 471651 4...

Страница 28: ...dent negligence alteration abuse misapplication or misuse The above warranty applies only if the heater is installed and operated in complete compliance with the installation and operation manual prov...

Отзывы: