LIGHTING INSTRUCTIONS

LIGHTING PROCEDURE FOR BOILER WITH 

CONTINUOUS PILOT

For Your Safety, Read Before Lighting!!

Read the warning at the beginning of "

1. 

Lighting Instruc-

tions

."

This appliance has a pilot which must be lighted by hand. 

2. 

When lighting the pilot, follow these instructions exactly.
Before lighting, smell all around the appliance area for 

3. 

gas. Be sure to smell next to the floor because some gas 

is heavier than air and will settle on the floor. See section 

"

What To Do If You Smell Gas

."

Use only your hand to push in or turn gas control knob or 

4. 

reset button. Never use tools. If the knob or reset button 

will not push in or turn by hand, don’t try to repair it, call 

a qualified service technician. Force or attempted repair 

may result in a fire or explosion.

Do not use this appliance if any part has been under wa

-

5. 

ter. Immediately call a qualified service technician to in

-

spect the appliance and to replace any part of the control 

system and any gas control which has been under water.

LIGHTING INSTRUCTIONS FOR CONTINUOUS PILOT

STOP!

1. 

 Read the safety information at the beginning of 

these instructions.
Set the thermostat to the lowest setting.

2. 

Turn off all electric power to the appliance.

3. 

Remove access panel and burner door.

4. 

Turn gas control knob clockwise 

5. 

 to "OFF." 

(Fig-

ures #15 and #16)

INL

ET

Figure #15

GAS CONTROL KNOB

PRESSURE REGULATOR 
ADJUSTMENT BENEATH 
COVER SCREW 

PILOT FLOW ADJ. SCREW
BENEATH COVER SCREW

OUTLET 

PRESSURE 

TAP 

TAP 

PRESSURE 

INLET 

GAS

INLET

GAS

OUTLET

TH/TR

ON

OFF

PILOT

Figure #16

NOTE: Some gas control knobs cannot be turned from "PILOT" 
to "OFF" unless knob is pushed in slightly. DO NOT FORCE.

Wait (5) minutes to clear out any gas. If you then smell 

6. 

gas, STOP! Follow "

What To Do If You Smell Gas

." If 

you don't smell gas, go to the next step.

Find pilot. Follow metal tube from gas control. Depending 

7. 

on the model of the boiler, pilot is either mounted on the 

base or on one of the burner tubes.

Turn gas control knob counterclockwise 

8. 

 to "PI-

LOT."

Push in gas control knob or reset button if so equipped, 

9. 

all the way in and hold. Immediately light the pilot with a 

match. Continue to hold the gas control knob or reset but

-

ton in for about 1 minute after the pilot is lit. Release knob 

or button, and it will pop up back up. Pilot should remain 

lit. If it goes out, repeat steps 5 through 9.

If knob or button does not pop up when released, stop 

• 

and immediately call a qualified service  technician or 

your gas supplier.

If the pilot will not stay lit after several tries, turn the gas 

• 

control knob clockwise 

 to "OFF." Call a qualified 

service technician or your gas supplier.

Replace burner door.

10. 

Turn gas control knob counterclockwise 

11. 

  to "ON."

Replace access panel.

12. 

Turn on all electric power to the appliance.

13. 

Set thermostat to desired setting.

14. 

 TO TURN OFF GAS TO THE APPLIANCE

Set the thermostat to lowest setting.

1. 

2. Turn off all electric power to the appliance if service is 

2. 

to be performed.

3. Push in gas control knob slightly and turn clockwise  

3. 

 to "OFF." DO NOT FORCE.

4. Call a qualified service technician.

4. 

Содержание 15B SERIES

Страница 1: ...kirk NY 14048 www ecrinternational com R An ISO 9001 2000 Certified Company 15B SERIES Cast Iron Gas Fired Boilers For Forced Hot Water INSTALLATION OPERATION MAINTENANCE MANUAL MODEL NUMBERS 15B045 1...

Страница 2: ......

Страница 3: ...or elimination of fac tory equipped supplied or specified components may result in property damage personal injury or the loss of life 4 TO THE OWNER Installation and service of this boiler must be p...

Страница 4: ...rs 3 Tank sized for non ferrous baseboard or radiant panel systems Increase size for cast iron baseboard and radiation Net I B R ratings include 15 allowance for normal piping and pick up load Manufac...

Страница 5: ...lighting and other performance 4 criteria with the gas manifold and control assembly on the boiler per the latest revision of ANSI Z21 13 CGA 4 9 The boiler shall be installed such that the gas ignit...

Страница 6: ...National Fuel Gas Code When a boiler is installed in an unconfined space in a 3 building of tight construction air for combustion and ven tilation must be obtained from outdoors or from spaces freely...

Страница 7: ...nch from the back and 6 inches from the front of the boiler The opening shall directly communicate with the outdoors or shall communicate through a verti cal or horizontal duct to the outdoors or spac...

Страница 8: ...ating boiler During heating cycle open valves A and B close valves C and D During cooling cycle open valves C and D close valves A and B Maintain a minimum clearance of one inch to hot water C pipes W...

Страница 9: ...tion This method of piping however is not typically required for baseboard heat ing systems Typical installations where bypass piping is used are as follows This method is used to protect boilers from...

Страница 10: ...ALVE HOSE BIB FLOW CONTROL VALVE EXPANSION TANK BOILER DHW CIRCULATOR CH CIRCULATOR PRIORITY ZONE CIRCULATOR EXPANSION TANK WATER INLET FLOW CONTROL VAVLE SHUT OFF VALVE PRESSURE REDUCER VALVE CHECK V...

Страница 11: ...RIORITY ZONE BOILER WATER INLET CH DHW SYSTEM CIRCULATOR USE FULL PORT ZONE VALVE FOR OPTIMUM TANK PERFORMANCE CONSIDER USING ZONE CIRCULATOR SEE FIGURE 5 ZONE 4 CIRCULATOR SHUT OFF VALVE PRESSURE RED...

Страница 12: ...urn doors win dows exhaust fans fireplace dampers and any other gas burning appliances to their previous condition of use Any improper operation of the common venting system 7 All installations of boi...

Страница 13: ...tor through bracket 3 hole on Damper Motor frame Tighten locknut onto Damper wire harness connector 4 Plug Damper connector into socket on Damper Motor 5 frame Replace Damper Motor cover and wire Damp...

Страница 14: ...iping system during 4 any pressure testing of the gas piping After reconnecting leak test gas connection and boiler piping before placing boiler back into operation Natural Gas Propane Min Supply Pres...

Страница 15: ...15 Wiring Diagram 24V Standing Pilot...

Страница 16: ...16 Wiring Diagram 24V Intermittent Ignition...

Страница 17: ...17 Wiring Diagram 24V Standing Pilot WITH LWCO...

Страница 18: ...18 Wiring Diagram 24V INTERM IGNITION WITH LWCO...

Страница 19: ...all your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department CAUTION C Use only your hand to push in or turn the...

Страница 20: ...COVER SCREW OUTLET PRESSURE TAP TAP PRESSURE INLET GAS INLET GAS OUTLET TH TR ON OFF PILOT Figure 16 NOTE Somegascontrolknobscannotbeturnedfrom PILOT to OFF unless knob is pushed in slightly DO NOT F...

Страница 21: ...per and dangerous operation CAUTION Verify proper operation after service The service agency or owner should make certain the system is filled with water to minimum pressure and open air vents if used...

Страница 22: ...S BURNERS Figure 20 BURNER DOOR The pilot flame should envelop to inch of the tip of the pilot thermocouple ignition sensing electrode or mercury sen sor Figure 21 IGNITION ELECTRODE 3 8 TO 1 2 IN FLA...

Страница 23: ...should be changed if the final manifold pressure varies more than plus or minus 0 3 inches water column from the specified pressure Primary air adjustment is not necessary therefore air shutters are...

Страница 24: ...ltimeter Gauge 4 Jacket Side Right 16 Right End Section 28 High Limit Control 5 Left End Section 17 Jacket Side Left 29 Pipe Bushing 6 Push Nipple 18 Relief Valve 30 Well 7 Jacket Top 19 Pipe Nipple 3...

Страница 25: ...aight Flange NPT 175 195 245 295 LP ONLY 1 6 VG 006 00 Internal Bushing x ALL LP 1 7 356 2 1 01 Manifold 045 1 356 2 1 02 Manifold 070 096 Item Part No Description Qty 7 356 2 1 03 Manifold 120 145 1...

Страница 26: ...6 1 B Center Section 120 145 2 B Center Section 175 195 3 B Center Section 245 4 B Center Section 295 6 Item Part No Description Qty 7 100 2 2 01 B Left Hand Section 1 8 43300976 Push Nipple 2 Mach 04...

Страница 27: ...702 Flue Collector Restrictor 070 3461703 Flue Collector Restrictor 096 3461704 Flue Collector Restrictor 295 Item Part No Description Qty 8 34620501 Flue Collector 045 1 34620502 Flue Collector 070 0...

Страница 28: ...02 Natural Gas Q345A PILOT 1 240007096 LP Q345A Pilot Included with 3 Pilot Tube Assembly Kit above CONTINUOUS PILOT Item Part No Description Qty 1 109007296 PILOT BRACKET ASSEMBLY 1 2 HW 005 01 BRACK...

Страница 29: ...18 1 5 1190001 Pipe Elbow 90 1 14 37513301 Wire Rollout Spill 28 2 6 1260006 Gauge Theraltimeter 1 15 14662070 Pilot Spark Control 1 7 37519501 Harness Circulator 72 1 16 EF03601 Clamp 3600 White 2 8...

Страница 30: ...ion LP to Natural 15B245 550001277 Kit Conversion LP to Natural 15B295 550001278 Kit Conversion LP to Natural NATURAL GAS TO LP Model Part No Description 15B045 550001279 Kit Conversion Natural to LP...

Страница 31: ...31...

Страница 32: ...85 Middle Rd Dunkirk NY 14048...

Отзывы: