PENNCO 15B SERIES Скачать руководство пользователя страница 14

14

CONNECTING GAS SERVICE

ELECTRICAL SECTION

Connect gas service from meter to control assembly in 

1. 

accordance with ANSI Z223.1 and local codes or utility. 

A ground joint union should be installed for easy removal 

of gas control for servicing. A drip leg or trap must be 

installed at the bottom of a vertical section of piping at the 

inlet to the boiler. A pipe compound resistant to the action 

of liquified petroleum gases must be used on all threaded 

pipe connections. Check with the local utility for location 
of manual shutoff valve if required. (

Figure #13

)

Figure #13

The gas line should be of adequate size to prevent undue 

2. 

pressure drop and  never smaller than the pipe size of the 
main gas control valve. (See Chart)

MAXIMUM CAPACITY OF PIPE IN CUBIC FEET OF GAS/HOUR

(Gas Pressure = 0.5 psig or less, Pressure Drop = 5 in. w/c)

Length of 

Pipe (Feet)

Nominal Iron Pipe Size

½”

¾”

1”

1¼”

10

175

360

680

1400

20

120

250

465

950

30

97

200

375

770

40

82

170

320

660

60

66

138

260

530

80

57

118

220

460

100

50

103

195

400

For additional information refer to the National Fuel Gas Code 

Handbook.

To check for leaks in gas piping, use a soap and water 

3. 

solution or other approved method.

Do not use an open flame!!

WARNING

!

  

Disconnect boiler from gas supply piping system during 

4. 

any pressure testing of the gas piping. After reconnecting, 

leak test gas connection and boiler piping before placing 

boiler back into operation.

Natural Gas

Propane

Min. Supply Pressure

5" w.c.

11" w.c.

Max. Supply Pressure

14" w.c.

14" w.c.

Manifold Pressure

3.5" w.c.

10.5" w.c.

ELECTRICAL WIRING

See wiring diagrams on the following  

four pages for details.

Electrical wiring must conform with the National Electrical 
Code, ANSI/NFPA No 70 latest edition when installed in the 
United states, the CSA C22.1 Canadian Electrical Code, Part 
1, when installed in Canada, and/or the local authority having 
jurisdiction. 

When an external electrical source is utilized, 

the boiler, when installed, must be electrically 
grounded  in  accordance  with  these  require-
ments.

WARNING

!

  

IMPORTANT:  Install  a  fused  disconnect 

switch  between  boiler  and  electrical  panel  at 

a convenient location.

THERMOSTAT INSTALLATION

Thermostat should be installed on an inside wall about 

1. 

four feet above the floor.

NEVER install a thermostat on an outside wall. 

2. 

Do not install a thermostat where it will be affected by 

3. 

drafts, hot or cold pipes, sunlight, lighting fixtures, televi

-

sions, a fireplace, or a chimney.

Check thermostat operation by raising and lowering ther

-

4. 

mostat setting as required to start and stop the burners.

Instructions for the final adjustment of the thermostat are 

5. 

packaged with the thermostat (adjusting heating anticipa-

tor, calibration, etc.)

Содержание 15B SERIES

Страница 1: ...kirk NY 14048 www ecrinternational com R An ISO 9001 2000 Certified Company 15B SERIES Cast Iron Gas Fired Boilers For Forced Hot Water INSTALLATION OPERATION MAINTENANCE MANUAL MODEL NUMBERS 15B045 1...

Страница 2: ......

Страница 3: ...or elimination of fac tory equipped supplied or specified components may result in property damage personal injury or the loss of life 4 TO THE OWNER Installation and service of this boiler must be p...

Страница 4: ...rs 3 Tank sized for non ferrous baseboard or radiant panel systems Increase size for cast iron baseboard and radiation Net I B R ratings include 15 allowance for normal piping and pick up load Manufac...

Страница 5: ...lighting and other performance 4 criteria with the gas manifold and control assembly on the boiler per the latest revision of ANSI Z21 13 CGA 4 9 The boiler shall be installed such that the gas ignit...

Страница 6: ...National Fuel Gas Code When a boiler is installed in an unconfined space in a 3 building of tight construction air for combustion and ven tilation must be obtained from outdoors or from spaces freely...

Страница 7: ...nch from the back and 6 inches from the front of the boiler The opening shall directly communicate with the outdoors or shall communicate through a verti cal or horizontal duct to the outdoors or spac...

Страница 8: ...ating boiler During heating cycle open valves A and B close valves C and D During cooling cycle open valves C and D close valves A and B Maintain a minimum clearance of one inch to hot water C pipes W...

Страница 9: ...tion This method of piping however is not typically required for baseboard heat ing systems Typical installations where bypass piping is used are as follows This method is used to protect boilers from...

Страница 10: ...ALVE HOSE BIB FLOW CONTROL VALVE EXPANSION TANK BOILER DHW CIRCULATOR CH CIRCULATOR PRIORITY ZONE CIRCULATOR EXPANSION TANK WATER INLET FLOW CONTROL VAVLE SHUT OFF VALVE PRESSURE REDUCER VALVE CHECK V...

Страница 11: ...RIORITY ZONE BOILER WATER INLET CH DHW SYSTEM CIRCULATOR USE FULL PORT ZONE VALVE FOR OPTIMUM TANK PERFORMANCE CONSIDER USING ZONE CIRCULATOR SEE FIGURE 5 ZONE 4 CIRCULATOR SHUT OFF VALVE PRESSURE RED...

Страница 12: ...urn doors win dows exhaust fans fireplace dampers and any other gas burning appliances to their previous condition of use Any improper operation of the common venting system 7 All installations of boi...

Страница 13: ...tor through bracket 3 hole on Damper Motor frame Tighten locknut onto Damper wire harness connector 4 Plug Damper connector into socket on Damper Motor 5 frame Replace Damper Motor cover and wire Damp...

Страница 14: ...iping system during 4 any pressure testing of the gas piping After reconnecting leak test gas connection and boiler piping before placing boiler back into operation Natural Gas Propane Min Supply Pres...

Страница 15: ...15 Wiring Diagram 24V Standing Pilot...

Страница 16: ...16 Wiring Diagram 24V Intermittent Ignition...

Страница 17: ...17 Wiring Diagram 24V Standing Pilot WITH LWCO...

Страница 18: ...18 Wiring Diagram 24V INTERM IGNITION WITH LWCO...

Страница 19: ...all your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department CAUTION C Use only your hand to push in or turn the...

Страница 20: ...COVER SCREW OUTLET PRESSURE TAP TAP PRESSURE INLET GAS INLET GAS OUTLET TH TR ON OFF PILOT Figure 16 NOTE Somegascontrolknobscannotbeturnedfrom PILOT to OFF unless knob is pushed in slightly DO NOT F...

Страница 21: ...per and dangerous operation CAUTION Verify proper operation after service The service agency or owner should make certain the system is filled with water to minimum pressure and open air vents if used...

Страница 22: ...S BURNERS Figure 20 BURNER DOOR The pilot flame should envelop to inch of the tip of the pilot thermocouple ignition sensing electrode or mercury sen sor Figure 21 IGNITION ELECTRODE 3 8 TO 1 2 IN FLA...

Страница 23: ...should be changed if the final manifold pressure varies more than plus or minus 0 3 inches water column from the specified pressure Primary air adjustment is not necessary therefore air shutters are...

Страница 24: ...ltimeter Gauge 4 Jacket Side Right 16 Right End Section 28 High Limit Control 5 Left End Section 17 Jacket Side Left 29 Pipe Bushing 6 Push Nipple 18 Relief Valve 30 Well 7 Jacket Top 19 Pipe Nipple 3...

Страница 25: ...aight Flange NPT 175 195 245 295 LP ONLY 1 6 VG 006 00 Internal Bushing x ALL LP 1 7 356 2 1 01 Manifold 045 1 356 2 1 02 Manifold 070 096 Item Part No Description Qty 7 356 2 1 03 Manifold 120 145 1...

Страница 26: ...6 1 B Center Section 120 145 2 B Center Section 175 195 3 B Center Section 245 4 B Center Section 295 6 Item Part No Description Qty 7 100 2 2 01 B Left Hand Section 1 8 43300976 Push Nipple 2 Mach 04...

Страница 27: ...702 Flue Collector Restrictor 070 3461703 Flue Collector Restrictor 096 3461704 Flue Collector Restrictor 295 Item Part No Description Qty 8 34620501 Flue Collector 045 1 34620502 Flue Collector 070 0...

Страница 28: ...02 Natural Gas Q345A PILOT 1 240007096 LP Q345A Pilot Included with 3 Pilot Tube Assembly Kit above CONTINUOUS PILOT Item Part No Description Qty 1 109007296 PILOT BRACKET ASSEMBLY 1 2 HW 005 01 BRACK...

Страница 29: ...18 1 5 1190001 Pipe Elbow 90 1 14 37513301 Wire Rollout Spill 28 2 6 1260006 Gauge Theraltimeter 1 15 14662070 Pilot Spark Control 1 7 37519501 Harness Circulator 72 1 16 EF03601 Clamp 3600 White 2 8...

Страница 30: ...ion LP to Natural 15B245 550001277 Kit Conversion LP to Natural 15B295 550001278 Kit Conversion LP to Natural NATURAL GAS TO LP Model Part No Description 15B045 550001279 Kit Conversion Natural to LP...

Страница 31: ...31...

Страница 32: ...85 Middle Rd Dunkirk NY 14048...

Отзывы: