Enthalpy and Temperature (See Figure 9)

The combination mode of operation will activate the Start
Stop Jog sequence when the Enthalpy meets the control
curve setpoint and the outside air temperature is between
the Low and High temperature setpoint.

2.

Remove control access panel and apply jumper to low
voltage terminal strip at “1” and “3”.

3.

Restore power to unit. Observe MV drive motor for
wheel and both blowers are running.

4.

Verify that the MV blower motors are set to “high”
speed for correct  speed and operation.

A - Blower Speed Ad just ment 

Blower speed selection is accomplished by changing the
speed selection switch on terminal strip in control box.
Both fresh air and exhaust air blowers are direct drive
multi-tap motors. Both blowers are factory set at “high”
speed for maximum airflow. To determine air flow setting,
external static pressure readings will need to be read
across the MV.

B - Air Bal anc ing Ad just ment 

1.

Remove plastic plugs in door panels(4 total).

2.

With a manometer measure pressure drop [inches of
water column] across left half of MV(top and bottom
holes in door panel). Unit CFM is determined then by
referring to 

Table #2

3.

Repeat the same process for the right half of MV.

4.

Place plastic plugs back in to door panels.

XI - Main te nance

1.

All motors use prelubricated sealed bearings; no
further lubrication is necessary.

2.

Make visual inspection of filters, motor assemblies
and MV rotating bearings during routine maintenance. 

3.

Filters should be checked periodically and cleaned
when necessary. Filter is located in front of MV unit
and before blower cabinet.

4.

MV segment is positioned on a shaft extended from
middle support bar. Annual inspection of the self
cleaning wheel is recommended. With power
disconnected, remove MV access panels and unplug
[J150 & P150] 

(Refer to wiring diagram in this

instruction manual). 

Then remove wheel cassette

from cabinet by sliding assembly out of support tracks

Figure 6

LED and Test Switch

There is a +5V LED indicating the module is wired and
powered properly. If the LED is not illuminated check the
wiring and power supply. The SSJ LED indicates when the
SSJ module has entered the start stop jog sequence. The
RELAY LED illuminates when the relay is activated cutting
power to the relay contacts. 

The pushbutton on the module is used to test the relay.
When the pushbutton is activated the LED under the
button illuminates. The LED indicates test mode of the
relay is operating. The SSJ sequence will not operate while 
the module is test mode.

Re cov ery  Wheel  Mode

On a call for operation the MV  media will rotate between
intake air and exhaust air streams. Both the intake air
blower and exhaust air blowers will also be operating to
overcome the air resistance of the MV  media.

X - Sys tem Check

1.

Disconnect MV main power.

C25 / MV250 Cab i net

Ex ter nal  Static  Pres sure

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

CFM

Low

498

479

459

435

411

384

347

307

263

218

175

High

592

565

530

496

463

431

398

 356

311

262

218

C45 / MV450 Cab i net

Ex ter nal  Static  Pres sure

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

CFM

Low

656

640

625

609

590

570

552

538

511

477

440

Me dium

729

708

690

671

649

627

605

582

560

 530

495 

High

783

765

740

721

700

678

650

 622

598

580

560

C75 / MV750 Cab i net

Ex ter nal  Static  Pres sure

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

CFM

Low

823

822

821

819

808

790

778

762

755

738

718

Me dium

997

992

985

975

960

940

928

905

884

872

850

High

1162

1145

1130

1104

1095

1090

1068

1047

1020

998

967

Table #2

Содержание C25

Страница 1: ...n In summer the process is automatically reversed Heat and moisture are absorbed from incoming intake air supply and transferred to the exhaust air stream This process allows outdoor air ventilation rates to be increased by factors of three or more without additional energy penalty or increase in size of heating or air conditioning systems PAGE 1 INSTALLATION INSTRUCTIONS ENERGY RECOVERY WHEEL INS...

Страница 2: ...EXIBLE DUCT COLLAR 5 Attach Flexible Duct Collar to MV fresh air intake and secure with screws See Figure 3 6 Attach fresh air intake duct work to fresh air intake Flexible Duct Collar and secure with screws See Figure 3 7 Attach Flexible Duct Collar to return air intake and secure with screws See Figure 3 8 Attach return air intake duct work to return air intake Flexible Duct Collar and secure wi...

Страница 3: ... its rotating cycle Rotating the wheel provides constant flow of energy from warmer to cooler air stream The large energy transfer surface and laminar flow through the wheel causes this constant flow of recovered energy to represent up to 85 of the difference in total energy contained within the two air streams Sensible and latent heat are the two components of total heat Sensible heat is energy c...

Страница 4: ...er to the desired VDC representing temperature The VDC can be calculated for a desired temperature using the following formula VDC 0 1429 x Temperature 5 7143 FROST THRESHOLD TEMPERATURE OD DB INDOOR RH INDOOR DB TEMPERATURE 70o F 72o F 75o F 80o F 20 14 13 11 8 30 3 2 1 3 40 5 7 9 11 50 13 13 15 18 60 18 19 21 26 Table 2 Rotation Sensor The circuit indicates the absence of pulses within a specifi...

Страница 5: ...rom middle support bar Annual inspection of the self cleaning wheel is recommended With power disconnected remove MV access panels and unplug J150 P150 Refer to wiring diagram in this instruction manual Then remove wheel cassette from cabinet by sliding assembly out of support tracks Figure 6 LED and Test Switch There is a 5V LED indicating the module is wired and powered properly If the LED is no...

Страница 6: ...3 Slide filters outwards PAGE 6 Figure 10 WHEEL FILTER ACCESS PANEL WHEEL ELECTRICAL HARNESS XII Warranty RRS Manufactured Parts In the event that defects in workmanship or materials originate in any part manufactured by RRS FOB point of manufactured we guarantee to repair or replace that part within three 3 months of the shipment date Other Supplied Parts Additionally RRS guarantees to replace st...

Страница 7: ...k Control Box Exhaust Air J148 Jack Fresh Air Motor Harness J150 Jack Wheel Motor Harness J151 Jack Exhaust Air Motor Harness K163 Relay Motors K164 Relay Wheel LA Switch Low Ambient MPD 1 Board Rotation P48 Plug Control Box Fresh Air P50 Plug Control Box Wheel P51 Plug Control Box Exhaust Air WIRE COLOR P148 Plug Fresh Air Motor P150 Plug Wheel Motor P151 Plug Exhaust Air Motor RS 1 Sensor Rotati...

Страница 8: ...PAGE 8 1 0 H x 2 0 5 2 C 1 0 t i n U s n o i t p O d e l l a t s n I y r o t c a F W r o t a l i t n e V i n i M H P 1 V 5 1 1 M A R G A I D G N I R I W T I N U 0 5 2 V M 5 2 C ...

Страница 9: ...1 Jack Control Box Exhaust Air J148 Jack Fresh Air Motor Harness J150 Jack Wheel Motor Harness J151 Jack Exhaust Air Motor Harness K163 Relay Motors K164 Relay Wheel LA Switch Low Ambient MPD 1 Board Rotation P48 Plug Control Box Fresh Air P50 Plug Control Box Wheel P51 Plug Control Box Exhaust Air WIRE COLOR P148 Plug Fresh Air Motor P150 Plug Wheel Motor P151 Plug Exhaust Air Motor RS 1 Sensor R...

Страница 10: ...PAGE 10 1 0 H x 2 0 5 7 C 5 4 C 1 0 t i n U s n o i t p O d e l l a t s n I y r o t c a F W r o t a l i t n e V i n i M H P 1 V 5 1 1 M A R G A I D G N I R I W T I N U 0 5 7 V M 5 7 C 0 5 4 V M 5 4 C ...

Страница 11: ...freight bill q Check model number to insure it matches the job requirements q Install field accessories and unit adapter panels as required Follow accessory and unit installation manuals q Verify field wiring including the wiring to any accessories q Check all multi tap transformers to insure they are set to the proper incoming voltage q Verify blower wheels are centered Realign if needed q Prior ...

Отзывы: