VFD68 Variable Frequency Drive (575 VAC) Installation Instructions

25

Adjusting the Default Parameters

Enter the Parameter Adjustment Mode

1.

Remove the jumper that connects terminal SD to terminal STF. 

2.

Turn the power on. The monitor display appears.

3.

Open the operation panel cover to reveal more keys.

4.

Press 

MODE

 until 

OP.nd EXT

 appears on the display, then press the up arrow until 

PU PU

 appears.

Select and Change Most Parameters

5.

Press 

MODE

 until 

Pr.. PU

 appears.

6.

To change Parameter 32, press the up arrow multiple times until 

P.032

 appears.

7.

Press 

SET

 to show 

12.5

 (Default value of P. 32).

8.

Press and hold the down arrow until 

9999

 appears (9999 indicates that the motor is set to run at minimum 

speed and not turn off during a low pressure condition).

9.

Press 

SET

 and hold for two seconds to set the new value.

10. Press 

SET

 again to advance to the next parameter.

11. To change additional parameters, press the up or down arrows.

Select and Change P.90x Parameters

12. To change parameter 902 (screen a) or 902 (screen b), press 

MODE

 until 

Pr.. PU 

appears on the display.

13. Press 

SET

P.000

 appears. (The underline indicates a blinking character.)

14. Press the down arrow once to show 

P.900

.

15. Press 

SET

 twice until 

P.900

 appears.

16. Press the up arrow twice to display 

P.902

.

17. Press 

SET

 to show 

P.90x

a. (The default value of 

P.902

a is 12.5 Hz.) Press the up or down arrow to change the 

value.

18. Press and hold 

SET

 for two seconds to set the 

P.90x

a value and show the actual input % for 

P.90x

b.

19. Press the up arrow once to view the default setting (38% for 

P.902

b). Press the up or down to change the 

value.

20. Press and hold 

SET

 for two seconds to set the new value.

21. Press 

SET

 again to advance to the next parameter.

22. Press the up or down arrow to display the next P.90x parameter that needs to be changed. Repeat Steps 17-

21.

!

CAUTION: Risk of Property Damage.

Do not apply power to the system before checking all wiring connections. Short circuited or improperly 
connected wires may result in permanent damage to the equipment.

MISE EN GARDE : Risque de dégâts matériels.

Ne pas mettre le système sous tension avant d'avoir vérifié tous les raccords de câblage. Des fils 
formant un court-circuit ou connectés de façon incorrecte risquent d'endommager irrémédiablement 
l'équipement.

IMPORTANT:

Remove the jumper to stop the motor before you change the parameter values.

Содержание VFD68D Series

Страница 1: ...5 Dimensions 7 Mounting 8 Wiring 10 Precautions 11 Terminal Screw Torque Specifications 12 Branch Circuit Protection 12 Short Circuit Ratings 12 High Voltage Wire Size and Maximum Wire Length 12 Selec...

Страница 2: ...Adjusting the Default Parameters 25 Enter the Parameter Adjustment Mode 25 Select and Change Most Parameters 25 Select and Change P 90x Parameters 25 Exit the Parameter Adjustment Mode 26 Manual Moto...

Страница 3: ...controlled equipment or other property additional precautions must be designed into the control system Incorporate and maintain other devices such as supervisory or alarm systems or safety or limit c...

Страница 4: ...Information Voltage kW Horsepower Dimensions H x W x D mm in D 575 VAC 50 60 Hz F 0 75 1 G 1 5 2 H 2 2 3 J 3 7 5 K 5 5 7 1 2 L 7 5 10 M 150 x 140 x 136 5 15 16 x 5 1 2 x 5 5 16 N 150 x 220 x 148 5 15...

Страница 5: ...re radio frequency or electromagnetic emissions may cause interference IMPORTANT When selecting the motor do not exceed the maximum output current rating of the VFD68 Drive IMPORTANT Do not control bo...

Страница 6: ...position in an enclosure Ambient air temperature is a temperature outside an enclosure The VFD68 is designed to operate above 50 C by following the maximum output current derating limits show in Table...

Страница 7: ...for VFD68Dxx Drives mm in VFD Model H H1 W W1 D VFD68DFM 150 5 15 16 138 5 7 16 140 5 1 2 128 5 1 16 136 5 3 8 VFD68DGM VFD68DHM VFD68DJN 220 8 11 16 208 8 3 16 148 5 13 16 VFD68DKN VFD68DLN Figure 2...

Страница 8: ...gure 4 2 Remove the high voltage wiring cover at the bottom of the VFD68 Drive by pulling in the direction of Arrow A Figure 5 Mount the VFD vertically in an acceptable NEMA rated enclosure on a non f...

Страница 9: ...ension 3 7 kW 5 HP or Less 5 5 to 7 5 kW 7 1 2 to 10 HP A 100 mm 4 in or more 100 mm 4 in or more B 10 mm 7 16 in or more 50 mm 2 in or more C Figure 6 Required Clearance for Mounting Inside an Enclos...

Страница 10: ...charge lectrique Afin d viter tout risque de d charge lectrique attendre au moins 10 minutes apr s la d connexion de l alimentation CA du VFD68 Drive pour intervenir sur l appareil Le VFD68 Drive rest...

Страница 11: ...ion and phase to phase insulation of the VFD output side before applying power Carefully check the motor insulation resistance especially when the VFD is used with an old motor or a motor located in u...

Страница 12: ...age drive output U V W to the motor Selecting the Correct VFD68 Drive for a Fan Motor 1 Determine the maximum current consumption from the motor ratings label 2 Use Table 9 to find the maximum output...

Страница 13: ...recommended cable wire size is that of the cable PVC cable with a continuous maximum permissible temperature of 70 C Assumes that the surrounding air temperature is 40 C or less Selection example for...

Страница 14: ...ate Figure 1 on page 4 for that model indicates that the VFD68DGM Drive has a voltage rating of 575 VAC and a maximum output rating of 7 amperes c Table 9 on page 13 gives the recommended wire size as...

Страница 15: ...10 Note Use UL Listed copper stranded wire with insulation rated at 75 C 167 F for wiring the high voltage supply to the drive R L1 S L2 T L3 and wiring the high voltage drive output U V W to the moto...

Страница 16: ...relay and regenerative brake circuits SD Common Common for contact inputs using Sink logic default setting and 24 VDC supply AM Analog Output 0 10 VDC analog output corresponding to output frequency P...

Страница 17: ...g STF Contact Input Forward rotation Must connect STF to SD terminal common using the factory supplied jumper to allow the VFD to rotate in a forward direction STR Contact Input Reverse rotation not u...

Страница 18: ...the P 90x parameters For medium and low pressure refrigerants you must determine the proper P499R Transducer and then calculate and change the P 90x parameters For more information see Setup and Adju...

Страница 19: ...ot the drive and motor operation using controlled input signal values EXT Mode In the External EXT mode the drive and motor respond to a signal or signals from one or two external analog input signal...

Страница 20: ...d to change the parameter setting consecutively when in the setting mode Press the key to change the parameter setting Used to give a forward rotation command Used to give a reverse rotation command U...

Страница 21: ...9 Motor Rated Current Set parameter to the rated FLA on motor rating plate 0 500 A Rated VFD68 Output P 19 VFD Output Voltage Defines the maximum output voltage relative to the drive supply voltage 2...

Страница 22: ...t 1 Minimum speed defined as frequency 0 60 Hz 12 5 Hz P 902b screen b Analog Input 1 of input voltage to start minimum speed ramp 0 100 38 1 90 V P 903 screen a Analog Input 1 Maximum speed defined a...

Страница 23: ...quency and Motor Speed Frequency Hz is an expression of motor speed RPM on the VFD Figure 14 and Figure 15 show how the drive operating frequency is related to the speed RPM of the motor Figure 14 Fre...

Страница 24: ...y Audible Motor Noise and EMI Using the default setting P 72 1 frequency 1 kHz electromagnetic interference EMI radiation and leakage current from the wiring between the VFD68 Drive and the motor is l...

Страница 25: ...SET P 000 appears The underline indicates a blinking character 14 Press the down arrow once to show P 900 15 Press SET twice until P 900 appears 16 Press the up arrow twice to display P 902 17 Press...

Страница 26: ...motor EXT Mode Using Analog Inputs After the motor FLA and speed have proven to be acceptable follow the procedure in Restarting the Motor After It Has Stopped on page 29 The VFD68 Drive is now commis...

Страница 27: ...1 of 2 Operation Panel Indication Name Error message E Faults history HOLD Operation panel lock Er1 to 4 Parameter write error LOCD Password locked Err VFD reset Warning OL Stall protection over curre...

Страница 28: ...BE Brake transistor alarm detection E GF Output side earth ground fault over current at start not used E LF Output phase loss E OHT External thermal relay operation not used E PTC PTC thermistor opera...

Страница 29: ...ect the jumper between the SD and STF terminals on the low voltage terminal blocks 2 Verify that the SINK SOURCE jumper to the left of the low voltage terminal blocks Figure 11 is set to SINK 3 Press...

Страница 30: ...phase NEMA Design B motors required Inverter rated motors recommended Overload Capacity 150 of ampere rating for 1 minute Start Stop Use STF input to start or stop the motor Ambient Conditions Storage...

Отзывы: