background image

9.

If you do not need to change the output’s sensor,

press 

Next

 in the Edit Sensor screen to save the

current sensor selection, complete the output setup,

and return to the Output Setup Start screen.

To change the output’s sensor, press 

Up

 or

Down

 in the Edit Sensor screen to select the

sensor that the output references. After you

select a different sensor, press 

Next

 to go to

the required output selection screen and repeat

the output setup procedure for the new Sensor

Type values.

Note: 

If you change the sensor that an output

references, the default setup parameters and

values for the output change, and you must set

up the output again.

Figure 33: Edit Sensor screen

10. The Standard Relay Output is now set up in the UI.

Press 

M

 to scroll through the remaining Setup Start

screens and continue setting up your control system,

or press 

Up

 and 

Down

 simultaneously to return to

the System 450 Main screens.

Figure 34: Relay Output Setup Start screen

Setting up a Relay Output with Reset

Setpoint

A relay output with reset setpoint provides On/Off control

to your application based on the Reset Setpoint sensor

(rES) that you set up for your control system.

1.

In the 

Relay Output Setup Start

 screen, press

Next

 to go to the Sensor Selection screen. The

output number and output type (relay or analog)

are automatically assigned when you connect power

to the module assembly. See the Relay Output

with Reset Setpoint Setup Screens row in the setup

screens flow chart in 

System 450 menu flow example

.

Note: 

All Setup Start screens are view-only;

selections cannot be made in Setup Start

screens.
The following figure shows the 

Relay Output

Setup Start

 screen for Output 2. The remaining

figures in this procedure show screens with the

parameter values selected for Relay Output 2

to control the temperature of Boiler 1 in Figure

3 based on the RSP set up in 

Setting up the

System 450 Reset Setpoint

.

Figure 35: Relay Output Setup Start screen

2.

In the 

Sensor Selection

 screen, press 

Up

 or 

Down

 to

select the Reset Setpoint Sensor (rES) for the output

to reference. The sensor selected here determines

the output control type (standard or reset control),

and the output’s setup parameters and value ranges.

Press 

Next

 to save your sensor selection and go to

next screen. If a sensor is not selected, the remaining

output setup screens do not appear. If a sensor is

already selected for the output, the Sensor Selection

screen does not appear here, the next screen in the

setup sequence appears instead.

Note: 

To set up a Relay Output with Reset

Setpoint, you must select rES in this screen. rES

cannot be selected until the Reset Setpoint is

set up in the System 450 UI. See 

Setting up the

System 450 Reset Setpoint

 for information and

procedures on setting up the RSP and rES.
The following figure shows the initial 

Relay

Output 2 Sensor Selection

 screen with no

sensor selected, followed by the same screen

with the Reset Setpoint sensor (rES) selected for

Relay Output 2.

Figure 36: Relay Output 2 Sensor Selection screens

3.

In the 

Reset Differential Selection

 screen, press

Up

 or 

Down

 to select the Reset Differential value for

the output. Select a dIFF value to establish the fixed

differential between the floating Relay-OFF setpoint

(RSP) and the floating Relay-ON setpoint (RSP+dIFF).

See Table 3 for the (fixed) minimum differential and

the range of usable dIFF values for outputs with RSP

in your control system.

- A positive differential (dIFF = +

n

) turns the

relay ON when temperature or humidity

increases; typically cooling.

- A negative differential (dIFF = -

n

) turns the

relay ON when temperature or humidity

decreases; typically heating.

Press 

Next

 to save your selection and go to the

next screen.

The following figure shows -5 differential

selected for Output 2.

Figure 37: Reset Differential Selection screen

System 450 Series Reset Control Modules with Real-Time Clock and Relay Output Installation Guide

14

Содержание System 450 C450RBN-1

Страница 1: ...ith reset control and or real time setback control for temperature and humidity only control applications System 450 expansion modules allow you to control up to 10 outputs which can be relay and anal...

Страница 2: ...lies before mak ing electrical connections More than one disconnec tion or isolation may be required to completely de en ergize equipment Contact with components carrying hazardous voltage can cause e...

Страница 3: ...and input sensor terminals low voltage less than 30V Labels 5V 24V Sn 1 Sn 2 Sn 3 Note Common terminals C are internally connected 2 6 pin module connector 3 Second output relay and terminal block La...

Страница 4: ...ion Module 16 Analog Output 4 Table 1 System 450 terminal wiring information Label Terminal function Wire sizes 24V Accepts 24 VAC supply power when a C450YNN power module is not connected and provide...

Страница 5: ...nd Down for 5 seconds to access the Setup Start screens 7 Menu button Press M to move through the sensor and output setup start screens When moving through the status or setup screens press M to retur...

Страница 6: ...s of the assembly outputs which requires setting up the outputs again See Figure 4 for an explanation of the System 450 display screen and the 4 button touch pad features and functions See Table 3 for...

Страница 7: ...s that the Analog Output is set up with SP EP and OSP OEP and Relay Output 2 has 17 hours of total runtime relay ON Figure 7 System Status screens Accessing the System 450 Setup screens 1 Apply power...

Страница 8: ...screens are view only selections cannot be made in Setup Start screens 2 In the Sn 1 Sensor Type Selection screen press Up or Down to select a Sensor Type F C or Press Next to save your selection and...

Страница 9: ...Setup Start screen Setting up the System 450 Reset Setpoint The System 450 Reset Control Modules feature temperature and humidity setpoint reset capability based on a Master temperature sensor Sn 1 an...

Страница 10: ...screen The remaining figures in this procedure show the setup parameter values selected for the RSP high and low temperature shutdown unoccupied setback and load balancing that are used by the output...

Страница 11: ...en The following figure shows an Shutdown High Temperature value of 65 F selected Figure 20 Shutdown High Temperature Selection screen 7 In the Shutdown Low Temperature Selection screen press Up or Do...

Страница 12: ...e the following sections Setting up a Relay Output with Reset Setpoint Setting up an Analog Output with Reset Setpoint Setting up a Standard Relay Output A standard relay output provides On Off contro...

Страница 13: ...mains off after reaching the OFFT value Minimum Relay OFF Time range is 0 to 300 seconds Press Next to save your selection and go to the next screen The following figure shows 10 seconds selected for...

Страница 14: ...et up in Setting up the System 450 Reset Setpoint Figure 35 Relay Output Setup Start screen 2 In the Sensor Selection screen press Up or Down to select the Reset Setpoint Sensor rES for the output to...

Страница 15: ...nge is 0 to 300 seconds Press Next to save your selection and go to the next screen The following figure shows 0 seconds selected for the minimum OFF Time for Output 2 Figure 40 Minimum Relay OFF Time...

Страница 16: ...gth at End Point OEP The LCD displays different Control Ramp icons for the four control actions The following figure shows an example of the analog output setup values and the resulting output signal...

Страница 17: ...e To set up a Standard Analog Output you must select Sn 1 Sn 2 or Sn 3 in this screen and the selected sensor must already be set up in the System 450 UI See Setting up System 450 Sensors for informat...

Страница 18: ...re limits to set point excursion The following figure shows 0 selected for the Unoccupied Setback value for Output 3 Figure 51 Unoccupied Setback Selection screen 8 In the Integration Constant Selecti...

Страница 19: ...sensor is not selected the remaining output setup screens do not appear If a sensor is already selected for the output the Sensor Selection screen does not appear here the next screen in the setup se...

Страница 20: ...tput When properly set up P I control can drive the load closer to Setpoint than proportional only control Press Next to save your selection and go to the next screen Initially you should select the I...

Страница 21: ...wing figure shows 12 hour clock format selected Figure 67 12 or 24 Hour Clock Selection screen 3 In the Time of Day Setup screen press Up or Down to set the current time Set the clock to real time Pre...

Страница 22: ...e unoccupied times The load balancing feature is not effected in its function as a result of Occupied Unoccupied modes See Figure 3 1 In the Occupied Unoccupied Schedule Setup Start screen press Next...

Страница 23: ...eriods for that day and the entire day is occupied and all outputs operate at their occupied setpoint value Occupied and Unoccupied time periods are available at 15 minute intervals only For example 1...

Страница 24: ...nd menu flow example System screens Description 1 Main screens Note The Main menu screens auto scroll during normal operation After two minutes of inactivity in any screen the display returns to the m...

Страница 25: ...eed 8 Standard analog output setup start screens Mixing valve output 9 Time and day clock setup start screens Note You can set Time and day and occupied or unoccupied schedule for any control system T...