Mounting

Important: 

Mount the switch so that the housing is

level horizontally, or plumb vertically. Use a shim, if

necessary.

You can mount the F262AA switch on the top, side, or

bottom of a duct.
• Mount the switch in a horizontal duct whenever

possible. In a horizontal duct, make sure that the switch

housing is level and the paddle is at approximately a

right angle to the air flow.

Figure 3: Mounting the F262 Switch in a horizontal duct

• When you mount the switch in a horizontal duct that

is not horizontally true, check with a level and place a

shim under the switch mounting plate. Do not mount

the switch without a shim. See the following figure.

Figure 4: Mounting the F262 Switch in an angled duct

• When you mount the switch in a vertical duct where

the airflow is upward as shown in the following figure,

see Table 1 for the minimum flow required to actuate

the switch. The maximum air velocity must not exceed

2,000 fpm (10.16 m/s).

Figure 5: Mounting the F262 control in a vertical duct

• When you mount the switch in a vertical duct where the

airflow is downward as shown in the previous figure,

adjust the switch:

a. Turn the adjustment screw clockwise until the

switch closes the circuit between the red and

blue terminals when there is no air flow. See the

following figure.

b. Turn the adjustment screw one additional turn

clockwise.

Figure 6: F262 Switch action

Location considerations

Important: 

Mount the switch so that the housing is

level horizontally or plumb vertically. Use a shim, if

necessary.

Do not use this switch where exposure to outdoor

weather occurs. Use the switch only for indoor situations.
Avoid locations close to elbows, dampers, fans, duct

openings, or other areas where excessive turbulence

occurs.
Mount the switch away from such areas at least five times

the distance of the smallest duct dimension as shown in

the following figure.

Example:

 On a 3 in. × 8 in. duct, mount the F261 at least

15 in. (381 mm) from the nearest bend.

Figure 7: Required duct distance

F262 Series Airflow Switch Installation Guide

3

Содержание F262 Series

Страница 1: ...airflow or the absence of airflow only in response to the velocity of air movement within a duct You can wire the switch to open one circuit and close a second circuit single pole double throw SPDT f...

Страница 2: ...e and mark the hole positions 2 Drill or punch the screw holes 3 Cut the center hole large enough for the paddle to pass through 4 Trim the paddle if necessary See Figure 2 The standard paddle fits in...

Страница 3: ...d 2 000 fpm 10 16 m s Figure 5 Mounting the F262 control in a vertical duct When you mount the switch in a vertical duct where the airflow is downward as shown in the previous figure adjust the switch...

Страница 4: ...ndicator light or signal to the blue terminal the light or signal activates when the airflow decreases or ceases Setup and adjustments Before you begin CAUTION Risk of property damage Do not set the s...

Страница 5: ...switch Figure 9 Flow rate adjustment Note Do not lower the flow rate required to activate the switch unless it is set above the factory set flow rate 4 Replace the enclosure cover and tighten the cove...

Страница 6: ...CFR47 Part 15 Subpart B Class B Plenum rated UL 2043 suitable for use in other environmental spaces plenums in accordance with section 300 22 c of the National Electrical Code Industry Canada IC Comp...

Страница 7: ...ference that may cause undesired operation of the device Le pr sent appareil est conforme aux CNR d Industrie Canada applicables aux appareils radio exempts de licence L exploitation est autoris e aux...

Страница 8: ...2021 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice www penncontrols com...

Отзывы: