About this task:

The following table shows airflow velocities in fpm required to activate the switch for any given duct size, with horizontal

or vertical upward flow. The flow rate table is based on a standard air density of 0.075 lb/ft

3

 (1.2 kg/m

3

).

Table 1: Flow rate table, fpm (m/s)

Minimum air velocity required to activate control

Horizontal flow

Vertical flow

Paddle

width

Switch actuation on

flow

50 in.

2

 (323 cm

2

) or

larger duct area

Less than 50 in.

2

(323 cm

2

) duct area

50 in.

2

 (323 cm

2

) or

larger duct area

Less than 50 in.

2

(323 cm

2

) duct area

Increase
R to Y closes

625 (3.2)

575 (2.9)

950 (4.8)

750 (3.8)

2-1/8 in.

Decrease
R to B closes

325 (1.7)

220 (1.1)

850 (4.3)

575 (2.9)

Increase
R to Y closes

500 (2.5)

350 (1.8)

750 (3.8)

500 (2.5)

3-1/8 in.

Decrease
R to B closes

250 (1.3)

100 (0.5)

650 (3.3)

350 (1.8)

To adjust the setting of the flow switch, complete the following steps:

1. Disconnect the power supply before you make any

electrical connections.

2. Remove the enclosure cover.
3. Adjust the switch’s flow rate. For more information,

see the following figure.

- Turn the adjustment screw counterclockwise

to lower the flow rate required to activate the

switch.

- Turn the adjustment screw clockwise to raise

the flow rate required to activate the switch.

Figure 9: Flow rate adjustment

Note: 

Do not lower the flow rate required to

activate the switch unless it is set above the

factory set flow rate.

4. Replace the enclosure cover and tighten the cover

screws with 12 in•lb of torque.

Checkout procedure

The circuit between the red and yellow terminals closes

when air flows through the duct where the switch is

located at the required velocity. When you connect to

the red and blue terminals, the warning light or signal

activates when the air flow decreases or ceases.

Before leaving the installation, observe at least three

complete operating cycles to make sure that all

components function correctly.

Ordering information

Table 2: Replacement paddle kits for F262 Switch

Product code Description

PLT112-1R

2-1/8 in. wide x 6-7/8 in. long (54 mm x

175 mm) paddle

PLT112-2R

3-1/8 in. wide x 6-7/8 in. long (79 mm x

175 mm) paddle

Repair information

Do not make field repairs, except for replacement of the

flow paddle. For a replacement control or paddle kit,

contact the nearest Johnson Controls

®

/Penn distributor.

F262 Airflow Switch technical

specifications

Table 3: F262 Series Airflow Switch electrical ratings

UL 60730/UL 1059

EN 60730

Volts 50/60 Hz

24

120 208 240

24

230

Horsepower

1

1

1

Full load amperes

16

10

10

8

Locked rotor

amperes

96

60

60

48

Resistive

amperes

16

16

10

10

16

16

Pilot duty VA

125 720 720 720

77

720

F262 Series Airflow Switch Installation Guide

5

Содержание F262 Series

Страница 1: ...airflow or the absence of airflow only in response to the velocity of air movement within a duct You can wire the switch to open one circuit and close a second circuit single pole double throw SPDT f...

Страница 2: ...e and mark the hole positions 2 Drill or punch the screw holes 3 Cut the center hole large enough for the paddle to pass through 4 Trim the paddle if necessary See Figure 2 The standard paddle fits in...

Страница 3: ...d 2 000 fpm 10 16 m s Figure 5 Mounting the F262 control in a vertical duct When you mount the switch in a vertical duct where the airflow is downward as shown in the previous figure adjust the switch...

Страница 4: ...ndicator light or signal to the blue terminal the light or signal activates when the airflow decreases or ceases Setup and adjustments Before you begin CAUTION Risk of property damage Do not set the s...

Страница 5: ...switch Figure 9 Flow rate adjustment Note Do not lower the flow rate required to activate the switch unless it is set above the factory set flow rate 4 Replace the enclosure cover and tighten the cove...

Страница 6: ...CFR47 Part 15 Subpart B Class B Plenum rated UL 2043 suitable for use in other environmental spaces plenums in accordance with section 300 22 c of the National Electrical Code Industry Canada IC Comp...

Страница 7: ...ference that may cause undesired operation of the device Le pr sent appareil est conforme aux CNR d Industrie Canada applicables aux appareils radio exempts de licence L exploitation est autoris e aux...

Страница 8: ...2021 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice www penncontrols com...

Отзывы: