F262 Series Airflow Switch Installation Guide

Applications

Important: 

Use this F262 Series Airflow Switch only

as an operating control. Where failure or malfunction

of the F262 switch could lead to personal injury

or property damage to the controlled equipment

or other property, additional precautions must be

designed into the control system. Incorporate and

maintain other devices, such as supervisory or alarm

systems or safety or limit controls, intended to warn

of or protect against failure or malfunction of the

F262 switch.

Important: 

Utiliser ce F262 Series Airflow Switch

uniquement en tant que dispositif de régulation.

Lorsqu'une défaillance ou un dysfonctionnement

du F262 switch risque de provoquer des blessures

ou d'endommager l'équipement contrôlé ou un

autre équipement, la conception du système de

contrôle doit intégrer des dispositifs de protection

supplémentaires. Veiller dans ce cas à intégrer de

façon permanente d'autres dispositifs, tels que

des systèmes de supervision ou d'alarme, ou des

dispositifs de sécurité ou de limitation, ayant une

fonction d'avertissement ou de protection en cas de

défaillance ou de dysfonctionnement du F262 switch.

The F262 Series Airflow Switch detects airflow or the

absence of airflow only in response to the velocity of air

movement within a duct. You can wire the switch to open

one circuit and close a second circuit, single-pole, double-

throw (SPDT), for either signaling or interlock purposes.
Airflow failure during the normal operation of air handling

systems may cause overheating, coil icing, or other

conditions that may be detrimental to the equipment.
Typical applications include:
• Make-up air systems

• Air cooling or heating processes

• Exhaust systems

The switch has a Type 3R/IP43 enclosure with an integral

mounting plate. A mounting plate gasket is supplied with

each control.
The enclosed SPDT Penn switch has color-coded

terminals for ease of wiring. The control is factory set

at approximately the minimum flow rate. See Table 1.

You must not set the control any lower than the factory

setting because the control may fail to return to a no-flow

condition. If you require a higher flow rate setting, turn

the range adjusting screw clockwise.
Mount the F262 switch on the top, side, or bottom of a

duct in a horizontal position whenever possible. If vertical

duct mounting is required and the flow is downward, you

must readjust the control. If the flow is upward, refer to

Table 1 for minimum flow required to actuate the control.
The switch is not designed for use where it is exposed to

outside weather.

Part No. 24-7664-2977 Rev. E

2021-0

4

-

20

F262AA

Содержание F262 Series

Страница 1: ...airflow or the absence of airflow only in response to the velocity of air movement within a duct You can wire the switch to open one circuit and close a second circuit single pole double throw SPDT f...

Страница 2: ...e and mark the hole positions 2 Drill or punch the screw holes 3 Cut the center hole large enough for the paddle to pass through 4 Trim the paddle if necessary See Figure 2 The standard paddle fits in...

Страница 3: ...d 2 000 fpm 10 16 m s Figure 5 Mounting the F262 control in a vertical duct When you mount the switch in a vertical duct where the airflow is downward as shown in the previous figure adjust the switch...

Страница 4: ...ndicator light or signal to the blue terminal the light or signal activates when the airflow decreases or ceases Setup and adjustments Before you begin CAUTION Risk of property damage Do not set the s...

Страница 5: ...switch Figure 9 Flow rate adjustment Note Do not lower the flow rate required to activate the switch unless it is set above the factory set flow rate 4 Replace the enclosure cover and tighten the cove...

Страница 6: ...CFR47 Part 15 Subpart B Class B Plenum rated UL 2043 suitable for use in other environmental spaces plenums in accordance with section 300 22 c of the National Electrical Code Industry Canada IC Comp...

Страница 7: ...ference that may cause undesired operation of the device Le pr sent appareil est conforme aux CNR d Industrie Canada applicables aux appareils radio exempts de licence L exploitation est autoris e aux...

Страница 8: ...2021 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice www penncontrols com...

Отзывы: