Operation

The flow switch responds to pressure that the flowing

fluid exerts on the fluid paddle. A range adjustment screw

adjusts the rate of the flow required to activate the switch.

For flow rates, see Table 7 through Table 9. For pressure

drop against flow rate, see Figure 14.
The red terminal is the Common. Red to yellow closes on

flow increase. Red to blue closes on flow decrease.

Table 10: F261 control switch action

Flow action

Switch closure

Increase

Red to yellow

Decrease

Red to blue

Checkout procedure

Ensure that installation, wiring, and control settings are

according to the application requirements. Refer to the

controlled system’s manufacturer specifications for the

correct settings when adjusting these controls.
Apply power to the control and controlled equipment.

Cycle the controlled system at least three times at normal

operating conditions.

Repair information

Do not make field repairs, except for replacement of the

flow paddle. For a replacement control or paddle kit,

contact the nearest Johnson Controls

®

/Penn

®

 distributor.

For more information, contact Johnson Controls/Penn

application engineering at 1-800-275-5676.

Troubleshooting

Table 11: Troubleshooting

Symptom

Solution

Condensate water

appears within the

enclosure.

If the control has a Type 3R/IP43

enclosure, inspect the grommet

in the field-installed cable gland

or conduit fitting, and replace the

grommet if it is defective.
If the control has a Type 4/

IP67 enclosure, inspect the

case-to-cover O-ring provided

on the flow switch. Ensure

that the O-ring is in place and

undamaged. Ensure that the

control uses a correct cable

gland or conduit fitting for Type

4/IP67 applications.

Fluid from the

tank leaks into the

enclosure due to a

rod seal failure.

Replace the flow switch.

The switch does

not activate due to

debris in the switch

mechanism.

Clear any debris from within

the switch mechanism. Test the

operation of the switch several

times for correct operation.

The control switch

action is reversed.

Ensure that the connections

follow the wiring diagrams.

Table 11: Troubleshooting

Symptom

Solution

The control does not

switch.

Check the electrical connections.

The switch fails to

return to the no-flow

position.

The switch may be set lower than

the factory setting. Increase the

setting.
On vertical pipes, ensure that the

direction of flow is up. The arrow

on the switch enclosure must

point in the direction of the flow.

The control does

not switch on flow

increase.

Check for a cracked or broken

paddle. Replace the paddle, if

necessary.

F261 electrical ratings

Table 12: F261xxH Series standard controls electrical

ratings

UL 60730/UL 1059

EN 60730

Volts 50/60 Hz

24

120 208 240 24

230

Horsepower

1

1

1

Full load amperes –

16

10

10

8

Locked rotor

amperes

96

60

60

48

Resistive

amperes

16

16

10

10

16

16

Pilot duty VA

125 720 720 720 77

720

Table 13: F261xxL Series low energy controls electrical

ratings, AC current

UL 60730/UL 1059EN 60730

Volts AC,

50/60 Hz

4 VAC

24 VAC

120 VAC

1

Resistive

amperes

1

10

10

10

2

Pilot duty VA

2

12

72

360

1

Maximum dry circuit rating: Resistive only, 400 mW at 28

VAC/VDC. After you use a relay at the general rating level,

the dry circuit rating is no longer valid.

2

Meets UL 100,000 cycle UL endurance test requirement at

switch with T

min

 greater than or equal to 32°F (0°C).

Table 14: F261xxL Series low energy controls electrical

ratings, DC current

UL 60730/UL 1059/EN 60730

Volts DC

4 VDC

24 VDC

48 VDC

1

Resistive

amperes

1

1

1

1

1

Maximum dry circuit rating: Resistive only, 400 mW at 28

VAC/VDC. After you use a relay at the general rating level,

the dry circuit rating is no longer valid.

F261 Series Flow Switches Installation Guide

9

Содержание F261 Series

Страница 1: ...ystème de contrôle doit intégrer des dispositifs de protection supplémentaires Veiller dans ce cas à intégrer de façon permanente d autres dispositifs tels que des systèmes de supervision ou d alarme ou des dispositifs de sécurité ou de limitation ayant une fonction d avertissement ou de protection en cas de défaillance ou de dysfonctionnement du flow switch WARNING Risk This product is made of a ...

Страница 2: ...Dimensions Figure 1 F261 standard flow switch dimensions in mm Figure 2 F261 low flow switch dimensions in mm F261 Series Flow Switches Installation Guide 2 ...

Страница 3: ...the pipe wall Important Do not install the flow paddle in such a way that it touches the pipe or any restrictions in the pipe If the flow paddle touches the pipe or restrictions in the pipe the switch may not correctly detect changes in fluid flow 2 If necessary trim a larger flow paddle at the arc corresponding to the pipe diameter For trimming information see Figure 3 Table 1 and Figure 6 3 Use ...

Страница 4: ...he enclosure Use a pipe union on each side of the flow switch to allow for easy removal or replacement Do not allow the pipe to extend too far into the flow switch casing Use pipe thread sealer or Teflon tape on the male threads only Do not remove the case to cover O ring on Type 4 IP67 enclosures Figure 6 Trimming diagram for the large flow paddle For standard 1 in x 1 in pipe installation mount ...

Страница 5: ...stance of at least five pipe diameters from the nearest elbow valve or other pipe restriction B Flow C Tee or welded half coupling When you mount the flow switch on a horizontal pipe mount the flow switch within 60 degrees of vertical See Figure 9 Figure 9 Correct flow switch angle Note Do not subject the flow switches to water hammer Use a suitable water hammer arrester if a fast closing valve is...

Страница 6: ...action Switch closure Increase Red to yellow Decrease Red to blue Setup and adjustments CAUTION Risk of property damage Do not set the switch lower than the factory setting The switch is factory set at approximately the minimum flow rate A lower setting may result in the switch failing to return to a no flow position which may result in damage to the controlled equipment or other property ATTENTIO...

Страница 7: ...et minimum value Turn the adjustment screw clockwise to raise the flow rate required to activate the switch See Figure 12 Figure 13 Minimum adjustment Table 6 Minimum adjustment callouts Callout Description A Wiring terminals B Adjustment screw C Main lever Table 7 Flow rates for standard models 1 3 in paddles GPM m3 hr GPM m3 hr required to activate switch for pipe size in 1 1 1 1 4 1 1 1 2 1 2 2...

Страница 8: ...1 1 2 x 1 2 in female NPTF 1 2 3 4 x 3 4 in female NPTF 2 3 3 4 x 3 4 in female NPTF 3 Flow increase R to Y Closes 1 30 4 92 2 00 7 57 10 90 41 26 Minimum adjustment Flow decrease R to B Closes 0 60 2 27 0 60 2 27 7 20 27 25 Flow increase R to Y Closes 2 60 9 84 3 60 13 63 17 00 64 35 Maximum adjustment Flow decrease R to B Closes 1 25 4 73 1 30 4 92 14 20 53 75 1 F261KEH V01C F261MEH V01C 2 F261K...

Страница 9: ... failure Replace the flow switch The switch does not activate due to debris in the switch mechanism Clear any debris from within the switch mechanism Test the operation of the switch several times for correct operation The control switch action is reversed Ensure that the connections follow the wiring diagrams Table 11 Troubleshooting Symptom Solution The control does not switch Check the electric...

Страница 10: ...s Low Flow 1 2 in x 1 2 in Female NPTF 3 4 in x 3 4 in Female NPTF Maximum fluid pressure 290 psi 20 bar Minimum fluid temperature 20 F 29 C Note Ensure that the low liquid temperature combined with the low ambient temperature does not lead to freezing the liquid inside the body or if applicable the bellows Observe the liquid freezing point Maximum fluid temperature 250 F 121 C Note At higher ambi...

Страница 11: ...exigences du Règlement sur le matériel brouilleur du Canada Product warranty This product is covered by a limited warranty details of which can be found at www johnsoncontrols com buildingswarranty Software terms Use of the software that is in or constitutes this product or access to the cloud or hosted services applicable to this product if any is subject to applicable end user license open sourc...

Страница 12: ... 2020 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice www penncontrols com ...

Отзывы: