 AVERTISSEMENT

Risque de décharge électrique.

Débrancher l'alimentation avant de réaliser tout

raccordement électrique. Le circuit imprimé et

ses composants présentent une tension CA. Tout

contact avec des composants porteurs de tensions

dangereuses risque d'entraîner une décharge

électrique et de provoquer des blessures graves, voire

mortelles.

Important:

• Use the M4 x 8 crosshead terminal screws

provided. Substitution of other screws voids the

warranty and agency approvals.

• To prevent moisture from entering and

condensate from forming inside the Type 3R/IP43

enclosure, do not block the drain hole provided.

• To prevent moisture from entering and

condensate from forming inside the Type 4/IP67

enclosure, do not remove the case-to-cover O-ring

provided on the flow switch.

• Use copper conductors only. Make all wiring in

accordance with local, national, and regional

regulations.

• Do not exceed the control’s electrical ratings.

Exceeding the control’s electrical ratings can

result in permanent damage to the control and

void any warranty.

The F261 models have three color-coded terminals. Red is

common. See Figure 11 and Table 5 for switch action.

Figure 11: F261 control switch action

Table 5: F261 control switch action

Flow action

Switch closure

Increase

Red to yellow

Decrease

Red to blue

Setup and adjustments

 CAUTION

Risk of property damage

Do not set the switch lower than the factory setting.

The switch is factory set at approximately the

minimum flow rate. A lower setting may result in the

switch failing to return to a no-flow position which may

result in damage to the controlled equipment or other

property.

 ATTENTION

Risque de dégâts matériels.

Ne pas régler le commutateur sur une valeur

inférieure au paramètre d'usine. Le commutateur

est réglé en usine sur une valeur correspondant

environ au débit minimum. Un réglage sur une valeur

inférieure risque d'empêcher le commutateur de

revenir sur une position « aucun-débit », ce qui risque

d'endommager l'équipement contrôlé ou de provoquer

d'autres dégâts matériels.

 CAUTION

Risk of Property Damage.

Do not attempt to change sealed settings. Attempted

adjustment may damage the control or cause loss of

calibration or other property damage.

 ATTENTION

Risque de dégâts matériels.

Ne pas essayer de modifier la position des éléments

de réglage bloqués. Toute tentative de réglage

risque d'endommager le dispositif de contrôle ou

de provoquer la perte des valeurs d'étalonnage ou

d'autres dégâts matériels.

To adjust the setting of the flow switch:

1.  Disconnect the power supply before making any

electrical connections.

2.  Remove the enclosure cover.

F261 Series Flow Switches Installation Guide

6

Содержание F261 Series

Страница 1: ...ystème de contrôle doit intégrer des dispositifs de protection supplémentaires Veiller dans ce cas à intégrer de façon permanente d autres dispositifs tels que des systèmes de supervision ou d alarme ou des dispositifs de sécurité ou de limitation ayant une fonction d avertissement ou de protection en cas de défaillance ou de dysfonctionnement du flow switch WARNING Risk This product is made of a ...

Страница 2: ...Dimensions Figure 1 F261 standard flow switch dimensions in mm Figure 2 F261 low flow switch dimensions in mm F261 Series Flow Switches Installation Guide 2 ...

Страница 3: ...the pipe wall Important Do not install the flow paddle in such a way that it touches the pipe or any restrictions in the pipe If the flow paddle touches the pipe or restrictions in the pipe the switch may not correctly detect changes in fluid flow 2 If necessary trim a larger flow paddle at the arc corresponding to the pipe diameter For trimming information see Figure 3 Table 1 and Figure 6 3 Use ...

Страница 4: ...he enclosure Use a pipe union on each side of the flow switch to allow for easy removal or replacement Do not allow the pipe to extend too far into the flow switch casing Use pipe thread sealer or Teflon tape on the male threads only Do not remove the case to cover O ring on Type 4 IP67 enclosures Figure 6 Trimming diagram for the large flow paddle For standard 1 in x 1 in pipe installation mount ...

Страница 5: ...stance of at least five pipe diameters from the nearest elbow valve or other pipe restriction B Flow C Tee or welded half coupling When you mount the flow switch on a horizontal pipe mount the flow switch within 60 degrees of vertical See Figure 9 Figure 9 Correct flow switch angle Note Do not subject the flow switches to water hammer Use a suitable water hammer arrester if a fast closing valve is...

Страница 6: ...action Switch closure Increase Red to yellow Decrease Red to blue Setup and adjustments CAUTION Risk of property damage Do not set the switch lower than the factory setting The switch is factory set at approximately the minimum flow rate A lower setting may result in the switch failing to return to a no flow position which may result in damage to the controlled equipment or other property ATTENTIO...

Страница 7: ...et minimum value Turn the adjustment screw clockwise to raise the flow rate required to activate the switch See Figure 12 Figure 13 Minimum adjustment Table 6 Minimum adjustment callouts Callout Description A Wiring terminals B Adjustment screw C Main lever Table 7 Flow rates for standard models 1 3 in paddles GPM m3 hr GPM m3 hr required to activate switch for pipe size in 1 1 1 1 4 1 1 1 2 1 2 2...

Страница 8: ...1 1 2 x 1 2 in female NPTF 1 2 3 4 x 3 4 in female NPTF 2 3 3 4 x 3 4 in female NPTF 3 Flow increase R to Y Closes 1 30 4 92 2 00 7 57 10 90 41 26 Minimum adjustment Flow decrease R to B Closes 0 60 2 27 0 60 2 27 7 20 27 25 Flow increase R to Y Closes 2 60 9 84 3 60 13 63 17 00 64 35 Maximum adjustment Flow decrease R to B Closes 1 25 4 73 1 30 4 92 14 20 53 75 1 F261KEH V01C F261MEH V01C 2 F261K...

Страница 9: ... failure Replace the flow switch The switch does not activate due to debris in the switch mechanism Clear any debris from within the switch mechanism Test the operation of the switch several times for correct operation The control switch action is reversed Ensure that the connections follow the wiring diagrams Table 11 Troubleshooting Symptom Solution The control does not switch Check the electric...

Страница 10: ...s Low Flow 1 2 in x 1 2 in Female NPTF 3 4 in x 3 4 in Female NPTF Maximum fluid pressure 290 psi 20 bar Minimum fluid temperature 20 F 29 C Note Ensure that the low liquid temperature combined with the low ambient temperature does not lead to freezing the liquid inside the body or if applicable the bellows Observe the liquid freezing point Maximum fluid temperature 250 F 121 C Note At higher ambi...

Страница 11: ...exigences du Règlement sur le matériel brouilleur du Canada Product warranty This product is covered by a limited warranty details of which can be found at www johnsoncontrols com buildingswarranty Software terms Use of the software that is in or constitutes this product or access to the cloud or hosted services applicable to this product if any is subject to applicable end user license open sourc...

Страница 12: ... 2020 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice www penncontrols com ...

Отзывы: