F261 Series Fluid Flow Switches Product Bulletin

5

Ordering Information

F61 to F261 Cross-Reference Tables 

Selection Tables  

Repair Information

Do not make field repairs, except for replacement of 
the flow paddle. For a replacement control or paddle 
kit, contact the nearest Johnson Controls/PENN 
distributor. For more information, contact 
Johnson Controls/PENN application engineering at 
1-800-275-5676 or 1-414-524-5535.

Table 4:  Flow Rates for Standard Models, 6 in. Paddles

GPM (m

3

/hr) Required to Activate Switch for Pipe Size (in.)

4

5

6

8

Minimum 
Adjustment

Flow Increase 
(Close R to Y)

37.0 (8.40)

57.0 (12.9)

74.0 (16.8)

205 (46.6)

Flow Decrease 
(Close R to B)

27.0 (6.13)

41.0 (9.31)

54.0 (12.3)

170 (38.6)

Maximum 
Adjustment

Flow Increase 
(Close R to Y)

81.0 (18.4)

118 (26.8)

144 (32.7)

415 (94.3)

Flow Decrease 
(Close R to B)

76.0 (1.93)

111 (25.2)

135 (30.7)

400 (90.8)

Table 5:  Standard Flow Models Cross Reference

F61 Series Model

F261 Series Model

F61KB-11C

F261KAH-V01C

F61LB-1C

F261MAH-V01C

F61MB-1C

F261MAH-V01C

F61MB-5C

F261MAH-V01C

Table 6:  F261 Series Standard Model Flow Switches

Product Code 
Number

Description

F261KAH-V01C

Standard model flow switch with Type 3R (NEMA) enclosure; 1 in., 2 in., 3 in., and 6 in. stainless steel 
paddles, lock-tooth washer, and stainless steel paddle screw supplied uninstalled

F261MAH-V01C

Standard model flow switch with Type 4 (NEMA) enclosure; 1 in., 2 in., 3 in., and 6 in. stainless steel 
paddles, lock-tooth washer, and stainless steel paddle screw supplied uninstalled 

Table 7:  Replacement Paddle Parts

Product Code 
Number

Description

KIT21A-600

Stainless steel 3-piece paddle (3 in., 2 in., and 1 in. segments) 

KIT21A-601

Stainless steel 6 in. paddle

PLT52A-600R

Stainless steel 3-piece paddle (3 in., 2 in., and 1 in. segments) and Stainless steel 6 in. paddle

Содержание F261 Series

Страница 1: ...ype 4 NEMA Polycarbonate Enclosure Provides dust protection in indoor applications Suitable for Use in Other Environmental Air Space Plenums in accordance with Section 300 22 C of the National Electrical Code Viton Diaphragms Allow use in fluid lines carrying chlorinated water treated water or other nonhazardous fluids Low Flow Operation on Low Flow Models Actuates switch with less than 1 0 GPM 3 ...

Страница 2: ... these models with pipes carrying fluids at temperatures in the range of 20 F to 250 F 29 C to 121 C A sealing O ring between the cover and case allows these models to be used in high humidity environments or applications where the fluid temperature is below the ambient dew point temperature Do not use these models in applications or environments where the temperature may cause the fluid to freeze...

Страница 3: ... screw adjusts the rate of the flow required to activate the switch See Table 3 through Table 6 for flow rates Figure 2 Dimensions for F261 Standard Flow Switch in mm 1 2 12 Typical Thread Engagement 3 1 2 89 4 1 2 114 5 11 16 144 8 3 4 222 2 3 4 70 11 16 18 2 1 8 54 1 2 in trade size or PG 16 conduit opening FIG F261_stndrd_dmnsns 4 102 2 51 1 11 1 2 NPT 30 mm Hex 2 9 16 65 ...

Страница 4: ...2 3 43 53 63 83 Minimum Adjustment Flow Increase Close R to Y 4 20 0 95 5 80 1 32 7 50 1 70 13 7 3 11 18 0 4 09 27 5 6 24 65 0 14 8 125 28 4 190 43 2 375 85 2 Flow Decrease Close R to B 2 50 0 57 3 70 0 84 5 00 1 14 9 50 2 16 12 5 2 84 19 0 4 32 50 0 11 4 101 22 9 158 35 9 320 72 7 Maximum Adjustment Flow Increase Close R to Y 8 80 2 0 13 3 3 02 19 2 4 36 29 0 6 59 34 5 7 84 53 0 12 0 128 29 1 245...

Страница 5: ... Flow Decrease Close R to B 76 0 1 93 111 25 2 135 30 7 400 90 8 Table 5 Standard Flow Models Cross Reference F61 Series Model F261 Series Model F61KB 11C F261KAH V01C F61LB 1C F261MAH V01C F61MB 1C F261MAH V01C F61MB 5C F261MAH V01C Table 6 F261 Series Standard Model Flow Switches Product Code Number Description F261KAH V01C Standard model flow switch with Type 3R NEMA enclosure 1 in 2 in 3 in an...

Страница 6: ...ge 4 000 VAC Ball Pressure Temperature Enclosure 266 F 130 C Switch Component 252 F 122 C Control Adjustment Instruction Field Wiring Rating Wire Cord Temperature Ratings 140 F 60 C only permitted when ambient air and media are less than 113 F 45 C 167 F 75 C only permitted when ambient air and media are less than 140 F 60 C 194 F 90 C only permitted when ambient air is less than 140 F 60 C and me...

Страница 7: ... these specifications consult Johnson Controls PENN Refrigeration Application Engineering at 1 800 275 5676 Johnson Controls Inc shall not be liable for damages resulting from misapplication or misuse of its products United States Emissions Compliance This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules These limits ar...

Отзывы: