Penn F261 Series Скачать руководство пользователя страница 2

F261 Series Fluid Flow Switches Product Bulletin

2

Application  

 

Standard Flow Switches

Use F261 Series Standard Flow Switches in 
applications with fluid pressures up to 290 psig 
(20 bar). A typical application for a standard F261 flow 
switch is to shut down the refrigeration compressor on 
a fluid chiller system if flow stops, reducing chances of 
chiller freeze-ups.

Type 3R (NEMA) / IP43 Enclosures 

Use models with Type 3R (NEMA) / IP43 enclosures 
for indoor or outdoor applications where they are 
protected from weather and splashing water. Use these 
models with pipes carrying fluids at temperatures in the 
range of -20°F to 250°F (-29°C to 121°C). A drain hole 
allows Type 3R (NEMA) models to be used in 
applications where the fluid temperature is below the 
ambient dew point temperature. The drain hole 
knockout is plugged on IP43 models to prevent the 
intrusion of objects 1 mm Ø and greater. Removing the 
plug reduces the enclosure rating to IP23, allowing 
these models to be used in applications where the fluid 
temperature is below the ambient dew point 
temperature. Do not use these models in applications 
or environments where the temperature may cause the 
fluid to freeze.

Type 4 (NEMA) / IP67 Enclosures 

Use models with Type 4 (NEMA) enclosures for indoor 
or outdoor applications in high humidity environments. 
Use these models with pipes carrying fluids at 
temperatures in the range of -20°F to 250°F (-29°C to 
121°C). A sealing O-ring between the cover and case 
allows these models to be used in high-humidity 
environments, or applications where the fluid 
temperature is below the ambient dew point 
temperature. Do not use these models in applications 
or environments where the temperature may cause the 
fluid to freeze.

Media Compatibility

F261 Series Flow Switches are compatible with several 
common media:

water

ethylene glycol

brine

sea  water

swimming pool water

lubricating oils

IMPORTANT:

All F261 Series Flow Switches are 

intended to control equipment under normal 
operating conditions. Where failure or malfunction of 
an F261 Flow Switch could lead to an abnormal 
operating condition that could cause personal injury 
or damage to the equipment or other property, other 
devices (limit or safety controls) or systems (alarm 
or supervisory) intended to warn of, or protect 
against, failure or malfunction of the F261 Flow 
Switch must be incorporated into and maintained as 
part of the control system.

IMPORTANT:

Do not install or use this F261 Series 

Flow Switch in or near environments where 
corrosive substances or vapors could be present. 
Exposure of the F261 Series Flow Switch to 
corrosive environments may damage the device’s 
internal components and will void the warranty.

IMPORTANT:

Do not use F261 Series Flow 

Switches where the fluid in the pipes drops below 
the fluid’s freezing point, causing an internal
freeze-up.

Содержание F261 Series

Страница 1: ...ype 4 NEMA Polycarbonate Enclosure Provides dust protection in indoor applications Suitable for Use in Other Environmental Air Space Plenums in accordance with Section 300 22 C of the National Electrical Code Viton Diaphragms Allow use in fluid lines carrying chlorinated water treated water or other nonhazardous fluids Low Flow Operation on Low Flow Models Actuates switch with less than 1 0 GPM 3 ...

Страница 2: ... these models with pipes carrying fluids at temperatures in the range of 20 F to 250 F 29 C to 121 C A sealing O ring between the cover and case allows these models to be used in high humidity environments or applications where the fluid temperature is below the ambient dew point temperature Do not use these models in applications or environments where the temperature may cause the fluid to freeze...

Страница 3: ... screw adjusts the rate of the flow required to activate the switch See Table 3 through Table 6 for flow rates Figure 2 Dimensions for F261 Standard Flow Switch in mm 1 2 12 Typical Thread Engagement 3 1 2 89 4 1 2 114 5 11 16 144 8 3 4 222 2 3 4 70 11 16 18 2 1 8 54 1 2 in trade size or PG 16 conduit opening FIG F261_stndrd_dmnsns 4 102 2 51 1 11 1 2 NPT 30 mm Hex 2 9 16 65 ...

Страница 4: ...2 3 43 53 63 83 Minimum Adjustment Flow Increase Close R to Y 4 20 0 95 5 80 1 32 7 50 1 70 13 7 3 11 18 0 4 09 27 5 6 24 65 0 14 8 125 28 4 190 43 2 375 85 2 Flow Decrease Close R to B 2 50 0 57 3 70 0 84 5 00 1 14 9 50 2 16 12 5 2 84 19 0 4 32 50 0 11 4 101 22 9 158 35 9 320 72 7 Maximum Adjustment Flow Increase Close R to Y 8 80 2 0 13 3 3 02 19 2 4 36 29 0 6 59 34 5 7 84 53 0 12 0 128 29 1 245...

Страница 5: ... Flow Decrease Close R to B 76 0 1 93 111 25 2 135 30 7 400 90 8 Table 5 Standard Flow Models Cross Reference F61 Series Model F261 Series Model F61KB 11C F261KAH V01C F61LB 1C F261MAH V01C F61MB 1C F261MAH V01C F61MB 5C F261MAH V01C Table 6 F261 Series Standard Model Flow Switches Product Code Number Description F261KAH V01C Standard model flow switch with Type 3R NEMA enclosure 1 in 2 in 3 in an...

Страница 6: ...ge 4 000 VAC Ball Pressure Temperature Enclosure 266 F 130 C Switch Component 252 F 122 C Control Adjustment Instruction Field Wiring Rating Wire Cord Temperature Ratings 140 F 60 C only permitted when ambient air and media are less than 113 F 45 C 167 F 75 C only permitted when ambient air and media are less than 140 F 60 C 194 F 90 C only permitted when ambient air is less than 140 F 60 C and me...

Страница 7: ... these specifications consult Johnson Controls PENN Refrigeration Application Engineering at 1 800 275 5676 Johnson Controls Inc shall not be liable for damages resulting from misapplication or misuse of its products United States Emissions Compliance This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules These limits ar...

Отзывы: