Penn F261 Series Скачать руководство пользователя страница 1

F261 Series Fluid Flow Switches Product Bulletin

1

 Refer to the 

QuickLIT website

 for the most up-to-date version of this document.

The F261 Series Flow Switches respond to fluid flow in 
lines carrying water, ethylene glycol, or other 
nonhazardous fluids. These models also work in 
applications with swimming pool water and lubricating 
oils.

F261 Series Standard Flow Switches

 use a variety of 

paddle sizes to respond to fluid flow rates in 
applications with pipe sizes greater than 1 inch trade 
size.

 

Figure 1: F261KAH Flow Switch

Table 1:  Features and Benefits

Features

Benefits

Type 3R (NEMA) or Type 4 (NEMA) 
Polycarbonate Enclosure

Provides dust protection in indoor applications. Suitable for Use in Other 
Environmental Air Space (Plenums) in accordance with Section 300.22(C) 
of the National Electrical Code.

Viton® Diaphragms

Allow use in fluid lines carrying chlorinated water, treated water, or other 
nonhazardous fluids.

Low-Flow Operation on Low-Flow Models

Actuates switch with less than 1.0 GPM (3.8 L/min) flow for water 
applications or 9.0 GPM (34.1 L/min) flow for steam applications.

Gold-Plated Contacts on Selected Models

Reduce intermittent contact problems in low-voltage and low-current 
circuits.

Maximum Fluid Pressure of 290 psig 
(20 bar)

Permits use in a wide range of pressure flow conditions.

F261 Series Fluid Flow Switches

Product Bulletin

Code No. LIT-12011987

Issued March 9, 2015

Содержание F261 Series

Страница 1: ...ype 4 NEMA Polycarbonate Enclosure Provides dust protection in indoor applications Suitable for Use in Other Environmental Air Space Plenums in accordance with Section 300 22 C of the National Electrical Code Viton Diaphragms Allow use in fluid lines carrying chlorinated water treated water or other nonhazardous fluids Low Flow Operation on Low Flow Models Actuates switch with less than 1 0 GPM 3 ...

Страница 2: ... these models with pipes carrying fluids at temperatures in the range of 20 F to 250 F 29 C to 121 C A sealing O ring between the cover and case allows these models to be used in high humidity environments or applications where the fluid temperature is below the ambient dew point temperature Do not use these models in applications or environments where the temperature may cause the fluid to freeze...

Страница 3: ... screw adjusts the rate of the flow required to activate the switch See Table 3 through Table 6 for flow rates Figure 2 Dimensions for F261 Standard Flow Switch in mm 1 2 12 Typical Thread Engagement 3 1 2 89 4 1 2 114 5 11 16 144 8 3 4 222 2 3 4 70 11 16 18 2 1 8 54 1 2 in trade size or PG 16 conduit opening FIG F261_stndrd_dmnsns 4 102 2 51 1 11 1 2 NPT 30 mm Hex 2 9 16 65 ...

Страница 4: ...2 3 43 53 63 83 Minimum Adjustment Flow Increase Close R to Y 4 20 0 95 5 80 1 32 7 50 1 70 13 7 3 11 18 0 4 09 27 5 6 24 65 0 14 8 125 28 4 190 43 2 375 85 2 Flow Decrease Close R to B 2 50 0 57 3 70 0 84 5 00 1 14 9 50 2 16 12 5 2 84 19 0 4 32 50 0 11 4 101 22 9 158 35 9 320 72 7 Maximum Adjustment Flow Increase Close R to Y 8 80 2 0 13 3 3 02 19 2 4 36 29 0 6 59 34 5 7 84 53 0 12 0 128 29 1 245...

Страница 5: ... Flow Decrease Close R to B 76 0 1 93 111 25 2 135 30 7 400 90 8 Table 5 Standard Flow Models Cross Reference F61 Series Model F261 Series Model F61KB 11C F261KAH V01C F61LB 1C F261MAH V01C F61MB 1C F261MAH V01C F61MB 5C F261MAH V01C Table 6 F261 Series Standard Model Flow Switches Product Code Number Description F261KAH V01C Standard model flow switch with Type 3R NEMA enclosure 1 in 2 in 3 in an...

Страница 6: ...ge 4 000 VAC Ball Pressure Temperature Enclosure 266 F 130 C Switch Component 252 F 122 C Control Adjustment Instruction Field Wiring Rating Wire Cord Temperature Ratings 140 F 60 C only permitted when ambient air and media are less than 113 F 45 C 167 F 75 C only permitted when ambient air and media are less than 140 F 60 C 194 F 90 C only permitted when ambient air is less than 140 F 60 C and me...

Страница 7: ... these specifications consult Johnson Controls PENN Refrigeration Application Engineering at 1 800 275 5676 Johnson Controls Inc shall not be liable for damages resulting from misapplication or misuse of its products United States Emissions Compliance This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules These limits ar...

Отзывы: