A52x Series Electronic Refrigeration Controller with Adaptive Defrost Technical Bulletin
41
Select the evaporator fan speed when the compressor relay is off.
To save the selection, press
SET.
Note:
Fan speed selections depend on whether you select
FAN
TYPE
1-SPD
or
2-SPD
in the System Setup menus.
For 1-SPD Fan:
ON
or
OFF
OFF
For 2-SPD Fan:
HI, LOW,
or
OFF
OFF
Defrost Setup Screens
The top-level
Defrost Setup
start screen for setting up the
refrigeration system behavior during defrost mode. To scroll
through the top-level start screens, tap the
DOWN
or
UP
keys. To
go to the
DEFROST TERMINATION TEMPERATURE
screen or
the
MAX DEFROST DURATION
screen and setup or adjust the
defrost operation and schedule, press
SET.
No selection
To go to the
DEFROST
DURATION
screen, press
SET
. No
selection
Select the maximum defrost duration in minutes. To save the
value, press
SET.
Note:
Temperature-based defrost durations that do not reach
termination temperature terminate when the maximum
defrost duration time elapses.
0
to
99
minutes
See
Evaporator Fan Drip-Time Delay
.
To go to the
DRIP TIME
screen, press
SET.
No selection
Select the preferred drip time delay in minutes after the defrost
duration terminates. To save the value, press
SET.
0
to
10
minutes
To go to the
DEFROST
TERMINATION
TEMPERATURE
screen,
press
SET
.
No selection
Select the defrost termination temperature, sensed at the Sn2
defrost sensor, at which the defrost duration is terminated. To
save the value, press
SET
.
Note:
The
DEFROST TERMINATION TEMPERATURE
screen
appears only if
TE/MP
is selected in the
DEFROST TYPE
screen in the System Setup menus.
-1C°–30C°
30F°–90F°
10°C
40°F
Table 8: A52x Controller Set Up Screens, Descriptions, Behaviors, Value Ranges a Selection Lists (Part
10 of 19)
Screen Name in
Message Field
Parameter Description, Behavior, User Action
Value Range or
Selection List
Default
Value or
Selection
EVAP FAN SPEED
COMP OFF
OFF
DEFROST SETUP
SET
DEFROST
DURATION
SET
MAX DEFROST
DURATION
30
MIN
DRIP TIME
SET
DRIP TIME
MIN
5
DEFROST
TERMINATION
TEMPERATURE
SET
DEFROST
TERMINATION
TEMPERATURE
90
30
40°