PT495 Series Detector
(Ultra1000)
Rev 5.11
31
Resetting Alarms
If the alarm relays are configured as Non-Latching then the relays will be deactivated
once the alarm level falls below the pre-set level. Else the relay must be deactivated
manually by using the magnetic wand as shown in figure 10 below
Hold the magnet to its place for few seconds until the transmitter displays
“RESET”
on the LCD. Move the magnet away. The relays will be de-energized,
however, if the gas concentration continues to be above the alarm level the
relays will be activated again.
Figure 10. Magnetic switch position 4 o'clock to RESET alarms and to adjust alarm set points
Alarm 1
15
Magnet
ic W
and
RESET