Trouble Shooting One-Touch Configuration
If status light 2 turns or flashes
RED
at anytime during or after the
configuration sequence, follow this guide to identify the issue:
Unable to Test
PEARL is unable to communicate with thermostat.
Verify R, C, D terminals are tightly screwed down at
the PEARL and thermostat. Check that the R, C, D
wires match from PEARL to thermostat.
No Communication
PEARL is unable to communicate with thermostat.
Verify R, C, D terminals are tightly screwed down at
the PEARL and thermostat. Check that the R, C, D
wires match from PEARL to thermostat.
Damper Error
Damper feedback (S1) is receiving incorrect position.
Check damper and actuator.
Supply Temperature Error
Unable to read the supply temperature probe. Check
supply probe, wires, and terminal (T1).
Outside Temperature Error
Unable to read the outside temperature probe. Check
outside air probe, wires, and terminal (T3).
Off
Blinking
Solid
Solid
Off
1 Blink
every 2 seconds
Solid
3 Blinks
every 2 seconds
Solid
red light
2
green light
1
Solid
20