2
2
2
3.
Press the
button to start the Automated One-Touch
Configuration. Status light 1 (green light) and Status light 2 (blue
light) will begin slowly blinking.
Test started
4.
After approximately 60 seconds Status light 2 (blue light) will
begin flashing to indicate the PEARL is moving the damper to the
FULLY CLOSED
position.
Closing economizer damper
If the economizer damper begins OPENING during Step 5 then
press the
button to switch to closing the damper.
Switching damper direction
Status light 2 (blue light) will begin flashing to indicate the PEARL
is now correctly moving the damper to the FULLY CLOSED
position.
Closing economizer damper
5.
30 seconds after reaching FULLY CLOSED: Status light 1 (green
light) will begin flashing to indicate the PEARL is moving the damper
to the
FULLY OPEN
position.
Opening economizer damper
6.
If test is successful settings will be stored. Status light 1 will be
solid green.
Normal operation
If any other light pattern is present, refer to the following section to
determine the reason for the error. Correct the problem and then
re-run the One-Touch Configuration.