6.6 Selftest
(Only when the country selected is “Italy 0-21”)
1. In order to perform selftest, in the main interface press “
◄
” and “ENT” at the
same time; from the new display, please select the test to accomplish and
press “ENT” for two times.
2. At the end of test, display will show test results obtained
Graph
Normal
E-Today 0.00 kWh
30-10-18
15:47
Run-Info
About
Power
0 W
E-Today
0.00 kWh
E-Total
0.00 kWh
T-Today
0.0 h
T-Total
0.0 h
Setting
Ovp (59.S2) test
Ovp10 (59.S1) test
Uvp (27.S1) test
Uvp2 (27.S2) test
Ofp (81>.S1) test
Ofp2 (81>.S2) test
Ufp (81<.S1) test
Ufp2 (81<.S2) test
All items test
Return
Graph
Wait
E-Today 0.00 kWh
30-10-18
15:47
Run-Info
About
Power
0 W
E-Today
0.00 kWh
E-Total
0.00 kWh
T-Today
0.0 h
T-Total
0.0 h
Setting
< Ovp (59.S2) results >
Vt: 264.5 V
Vs: 233.0 V
Vo: 232.5 V
Tt: 200 ms
To: 190 ms
30/10/18 15:47 Pass
Return
Next