Module address in older versions of the PHC software

In older versions of the PHC software the PHC panel is not available as an own type 

of module. The PHC panel can be used nevertheless.

The panel with 

16 inputs

 corresponds to a PHC input module (940/24 EM RÜ) in 

relation to the range of functions. In the PHC software then an input module (e.g. with 

the address 

EM 00

) needs to be created as a substitution. The coding switch of the 

panel is then set to the address of the input module (

EMD 00

).

The panel with 

32 inputs

 corresponds to two input modules (940/24 EM RÜ) in relation 

to the range of functions. In the PHC software then two input modules with consecutive 

addresses have to be used (e.g. 

EM 00

 and 

EM 01

). The coding switch of the panel 

is then set to the address of the first input module (EMD 00).

Caution! 

The following address (

EMD 00

) is then also occupied 

by the panel.

DATA ConnECTIon

The PHC panel requires a port (s. port diagram) on the PHC BUS that 

serves as data connection and as voltage supply. 

The connection from the panel to the control unit and to other modules 

is usually made by a JY(ST)Y line of 2x 2x 0.8 mm Ø

The module can be positioned anywhere in the data line. When connecting the BUS 

line be sure that the lines A and B are not crossed. Power needs to be switched off 

before disconnecting the bus line.

MounTIng

The installation of the PHC modules may be carried out by authorised technicians only. 

During installation, the system‘s electricity has to be switched off. The PHC modules 

may not be employed in connection with devices that may endanger people, animals 

or property when operated.

The following points must be observed:

-  Valid laws, standards and regulations.

-  Technical state of the art during installation.

-  PHC manual and the operating instructions of the PHC modules.

-  Operating instructions can only cite general stipulations. These are to be viewed in  

  the context of a specific system.

The following systems may not be switched by PHC output modules:

-  Safety switches such as EMERGENCY OFF

-  Emergency power supplies

-  Fire alarm systems

-  Emergency lighting systems

The PHC panel is screwed onto a installation housing (940 DO) for in-wall mounting. 

For surface mounting the ornamental frame (940 F) is used. Optionally a decorative 

frame (940.70) can be attached.

note:

 In case the installation housing should be mounted flush, the rubber 

seal on the panel needs to be removed so that the decorative frame lies flat 

against the wall.

Caution!

 Before mounting the panel, the data connection needs to be 

established and the coding switch has to be set.

DESCrIPTIon

This panel is used to display switch statuses in a PHC system and to execute the 

switching procedures. All LEDs can be switched ON and OFF by the PHC system 

without additional wiring (status display).

The front side consists of a solvent-resistant film behind which the respective labelling 

strips (included in delivery) can be inserted.

oPErATIon AnD LAbELLIng

The device is operated by means of the 16 or 32 keys on the membrane keyboard. 

Each of these keys can be used in the PHC system upon appropriate programming 

in the PHC software (as of version 2.50). The LED belonging to the keys can be 

programmed independently from the button.

CoDIng SwITCH AnD MoDuLE ADDrESS

The module address is set by the coding switch built into the PHC panel. 

The setting of the coding switch is presented in the PHC software under 

the menu item „

Components 

 module

“.

Make sure that no identical module addresses are given for PHC panels. The setting 

of the coding switch may be carried out by technicians only. For this the PHC module 

needs to be switched off and it must be ensured that there can be no electrical 

discharge.

Module address in the PHC software as of version 2.50

The panel with 

16 inputs

 is available as an independent type of module (named 

TAb

 

under input modules).

Caution!

 If a panel with 

32 inputs

 is used, then two panels with 16 inputs and 

subsequent module addresses (e.g. 

TAb 00

 and 

TAb 01

) have to be created 

in the PHC software. The coding switch of the 32-input panel is then set to the 

address of the first 16-input panel (

TAb 00

).

Caution! 

The following address (

TAb 01

) is then also occupied by the 32-input 

panel.

IN0

IN1

IN2

IN3

IN4

IN5

IN6

IN7

IN8

IN9

IN10

IN11

IN12

IN13

IN14

IN15

IN24

IN25

IN26

IN27

IN28

IN29

IN30

IN31

IN16

IN17

IN18

IN19

IN20

IN21

IN22

IN23

LED

button

Decorative frame

24V
A +
B -
0V

24V
A +
B -
0V

Labelling sheets for laser printers are supplied as well for labelling the key 

and window surfaces. The foil is suitable only for laser printers. After printing 

on the labelling sheets, they are cut to the appropriate size and then slid in 

behind the membrane keyboard. The sliding of the labelling sheets in behind 

the membrane keyboard is facilitated by trimming the tip of the labelling sheet 

slightly conically. 

For labelling the button surfaces there is an MS-Excel spreadsheet available 

on the Internet at 

www.peha.de

. The cells to be labelled have already been 

set here to the height of the key surfaces.

Installation housing

(940 Do)

ornamental frame

(940.70)

InSTALLATIon AnD oPErATIng InSTruCTIon
PHC Panel 941 TAb

16/32 inputs with status LEDs
941/16 TAb and 941/32 TAb