DESCRIPTION 

The DIN NANO 4CK is an electronic regulator DIN rail designed to 

control  refrigerated  counters,  display  windows  and  static  or 

ventilated refrigeration units with off-cycle, electrical or  hot gas 

defrosting  also  in  real  time  clock  (RTC).  It  is  fitted  with  three 

analogue  inputs  for  NTC  temperature  probes  one  of  which 

configurable as digital input, another digital input, four relays for 

the  control  of  the  compressor,  fans,  light  and  defrosting 

evaporator  and  buzzer.  Two  relays  can  be  set  as:  alarm  relay, 

simultaneously  to  the  compressor  output,    room  light,  cold 

function  for  pump  down  operation,    second  defrosting  relay, 

night relay or hot relay. The regulator can be also configured for 

heat applications. Internal buzzer for acoustic signals. 

 

 

PRINCIPAL CHARACTERISTICS 

 

Can be configured for cold, hot or neutral zone applications. 

 

Relay  for  compressor  and  evaporator  fan  management  (2  non 

configurable  relays)  and  defrosting  resistances  1  and  2,  alarm, 

pump  down  start,  room  light  and  compressor  output  (2 

configurable relays). 

 

Clock for programmed defrosts (RTC), up to 6 starts in 24h. 

 

Defrosting can be configured for off-cycle, heating element, cycle 

inversion,  cycle  inversion  with  basin  or  heating  element  with 

temperature control; frequency and duration can be set. End-of- 

defrosting can be based on time or temperature. 

 

Key operated manual START/STOP defrosting. 

 

Key operated ON/OFF. 

 

Night / day management (energy saving) 

 

Smart defrost functionality (energy saving)

 

 

 

Cold  room  light  ON/OFF  switch  with  key  or  by  means  of  door 

switch (if defrost output is configured like cold room light). 

 

Display/adjustment of temperature with decimal point. 

 

Flat front surface for easy cleaning and keys of ample dimensions 

which can be customised with various colours (on request). 

 

3-Digit LED display with sign, decimal point and system status icon.  

Internal buzzer for acoustic signals. 

 

PEGO programming philosophy guaranteeing immediate start-up. 

 

RS485 serial connection with Modbus-RTU  or Telenet protocol. 

 

IP65 front protection. Two-fold fastening option: clips / screws. 

 

Voltage and terminal type depending on model. 

 

HACCP  function  for  memorization  and  visualization  of  the  last 

temperature alarm 

 

 

 

COMBINED ACTIVATION OF KEYS AND THEIR FUNCTIONS 

FUNCTION / KEY COMBINATION 

SETTINGS PROGRAMMING   /

  (Set + 

 o 

 

Press  the  SET  key  to  view  the  current  SETPOINT  value 

(temperature). 
Keeping the SET key down and pressing either the (

) or (

key, the SETPOINT value can be changed. 

Release the SET key to return to view the room temperature; 

the changes made will be automatically saved. 

LEVEL 1 PROGRAMMING /

  (

 + 

 

Press the UP and DOWN keys simultaneously for over 3 sec. to 

access  the  Level  1  programming  menu.  When  the  menu  is 

accessed, a BIP is generated to confirm. The system leaves the 

menu after 30 seconds. 

LEVEL 2 PROGRAMMING

/ (

+

+Stand-by) 

 

Press  the  UP,  DOWN  and  STAND-BY  keys  simultaneously  for 

over 3 sec. to access the Level 1 programming menu. When the 

menu is accessed, a BIP is generated to confirm and the system 

is placed in Stand-By mode. 

HACCP  MENU  FOR  VISUALIZATION  OF  THE  LAST 
TEMPERATURE ALARM RECORDING /

 (

+ Stand-by) 

 
Push UP and STAND-BY keys simultaneously for over 3 sec. To 
access the HACCP menu. 
A BIP is generated to confirm. 

EXIT PROGRAMMING MENUS  /

  (

 + 

 

Pressing  the  UP  and  DOWN  buttons  simultaneously  in  any 

programming menu for over 3 sec. causes the system to save 

the settings entered and leave that menu. A BIP is generated to 

confirm. 

 

 

NANO4CKD SERIES MODELS 

PEGO CODE 

EXPERT NANO DESCRIPTION 

200NDIN4CK01

 

Power 

supply 

230Vac, 

relays 

(16A+16A+16A+8A), digital input, hot/cold funct., 

RTC,  RS485,  pump    down,    buzzer,  extractable 

terminals. 

KC-TTLB-L2.5

 

Connection cable  for temperature repeater ECHO 

Length=2.5m 

200NANOTTL02

 

Temperature repeater Display (ECHO)

 

 

 

 
 

E N G L I S H

 

Power voltage 

Model 200NDIN4CK01 

230V  +10/-15%  50-60Hz  

Absorbed power  

5 VA  Max 

Environment conditions 

Operating temperature 

-5T50°C  - humidity < 90% Rel. Hum. Not condensing 

Storage temperature 

-10T70°C - humidity < 90% Rel. Hum.  Not condensing 

Unsuitable operating 

environments 

Environments with strong vibrations or impacts; aggressive, 

polluted or corrosive atmospheres, exposure to direct solar 

radiation, explosive atmospheres or flammable gas. 

General characteristics 

Display 

3-Digit with sign, decimal point and 9 LED status 

indicators 

Resolution 

0.1 °C 

Probe precision (electronic) 

± 0.5 °C 

Reading range 

-45T99 °C 

Model 200NDIN4CK01 

 

Power clamps: extractable, screw for cables with c/section 

0.2 to  2.5mm

2

 

Software class: A  /  Parameters saved on non-volatile memory (EEPROM) 
Input characteristics 
Analogue inputs 

3 Inputs for NTC probes (10K Ώ 1%  at 25°C)  

 

Digital inputs 

1 Input (clean contact) 

Output characteristics (free voltage contact) 
Compressor relay (DO1) 

N.O.  16(6)A  / 250V  

Fan relay  (DO2) 

N.O.  16(6)A  / 250V  

Relay  (DO3) 

N.O.  16(6)A  / 250V  

Relay (DO4) 

N.O.  8(3)A   /  250V  

Buzzer 

Present 

Dimensional, insulation and mechanical characteristics 

Dimensions 

200NDIN4CK01 : 105x121.5x71mm  

Echo: 93x37x23.1mm 

Drill hole template (display Echo)  71x29mm (+0.2/-0.1mm) 
Protection rating (display Echo) 

IP65 with front board installation 

Installation (display Echo) 

In front of board by side tabs fixing or by two front 

screws 

Installation 200NDIN4CK01 

Din rail 35mm 

Casing 

Plastic PC+ABS UL94 V-0 body, PC transparent front, Key 

panel PC or PC+ABS 

Insulation type 

Class II 

Conformity with EEC low voltage directives, electromagnetic compatibility and EC mark 
Conforms to following EEC Directives : Directives 2014/30/EU, 2014/35/EU 

Conforms to following harmonised standards:  

EN60730-1:2016, EN60730-2-9:2010, EN61000-6-1:2007,  EN61000-6-3:2007 

 

DIMENSIONS (mm)

 

STATUS ICON 

ICON 

MEANING 

 

COLD FUNCTION ICON 

(icon activated with mOd=0)   

Led OFF = Cold function OFF 

Led ON =  Cold function ON 

Flashing Led = Cold function ON  waiting for C1 delay 

 

HOT FUNCTION ICON

  

Led OFF = Hot function OFF 

Led ON =  Hot function ON   

 

FAN ICON

   

Led OFF = Fans OFF 

Led ON =  Fans ON   

Flashing  Led  =    Fans  paused  after  defrosting  (see 

parameter F5) 

 

DEFROSTING ICON  

(icon activated with mOd=0)   

Led OFF = Defrosting OFF 

Led ON =  Defrosting ON   

Led  Flashing  =  Dripping  in  progress  after  defrosting 

(see parameter d7) 

 

DOOR SWITCH / ROOM LIGHT ICON

 

Led OFF = Door switch not activated or not used and 

room light off 

Led  ON  =    Room  light  ON    (function  active  only  if 

variable dO3=4 or dO4=4) 

Flashing Led = Door switch activated or room light ON 

with alarm E8. 

 

ALARM ICON

 

Led OFF = No alarm present 

Led  ON  =  Indicates  temperature  alarm  intervention 

with remedy (HACCP alarm). 

Flashing Led =  Alarm present 

 

TECHNICAL DATA

 

KEY FUNCTIONS 

Key 

FUNCTION 

 

UP KEY 

Increases  values  /  Scrolls  parameters  in  ascending 

order  /  Deactivates  acoustic  alarm  if  present  / 

Acknowledges  an  alarm.  With  variable  dO3=4  or 

dO4=4 if pressed for over 3 sec, activates/deactivates 

room  light  (DO3  or  DO4  output).  With  manual 

activation/ deactivation of the light a BIP is generated 

to confirm. 

 

DOWN KEY 

Decreases values  / Scrolls  parameters in  descending 

order  /  If  pressed  for  over  3  sec.  activates  manual 

defrosting (if suitable conditions are present). 

Terminates defrosting if pressed for over 3 sec. during 

the  defrosting  process.  With  manual  activation/ 

deactivation  of  defrosting  a  BIP  is  generated  to 

confirm. 

Stand 

by

 

STAND-BY KEY 

If pressed for over 1 sec. alternates the Stand-By with 

normal  mode  and  vice  versa.  When  mode  is 

alternated a BIP is generated to confirm. In Stand-By 

mode  the  system  stops  and  the  display  signals  OFF 

and the temperature alternating. 

 

SET KEY

 

Displays the set point. 

Allows  the set  point to  be entered  when  pressed  in 

combination with the DOWN or UP keys. Resets the 

acoustic alarm if present. 

 

FASTENING TO PANEL ECHO DISPLAY BY MEANS OF TWO 
FRONT SCREW 

DRILL HOLE TEMPLATE (mm)

 

Screw 2,9x9,5mm

 

Screw 2,9x9,5mm

 

Distance between hole 
centres : 77mm

 

Содержание Expert DIN NANO 4CK

Страница 1: ...VOTTLXDISPLAY ECHONANO Lunghezza 2 5m 200NANOTTL02 DISPLAYRIPETITOREDITEMPERATURAECHO ITALIANO Tensione di alimentazione Modello 200NDIN4CK01 230V 10 15 50 60Hz Potenza assorbita 5VA Max Condizioni cl...

Страница 2: ...ementato solo se il compressore acceso e la temperatura dell evaporatore pi freddo inferiore a dSt 1 C1 Tempo minimo tra lo spegnimento e la successiva Accensione del compressore Range 0 15 min 0 CE1...

Страница 3: ...ore rimane e viene riattivato con la pressione del tasto SET FORZATURA MANUALE DI FINE SBRINAMENTO IN CORSO Durante uno sbrinamento la pressione del tasto DOWN per 3 secondi forza la fine dello sbrina...

Страница 4: ...lepossibiliinesattezzecontenutenelpresentemanuale sedovuteaderroridistampaoditrascrizionee si riservaildirittodiapportareaipropriprodottiquellemodifichecheriterr necessarieoutili senzapregiudicarnelec...

Страница 5: ...B L2 5 Connection cable for temperature repeater ECHO Length 2 5m 200NANOTTL02 TemperaturerepeaterDisplay ECHO ENGLISH Power voltage Model 200NDIN4CK01 230V 10 15 50 60Hz Absorbed power 5VA Max Enviro...

Страница 6: ...han dSt 1 C1 Minimum time between each turning off and on of the compressor Range 0 15 min 0 CE1 Duration of compressor ON time in the case of faulty ambient probe emergency mode Range 0 240min 0 Disa...

Страница 7: ...messages is displayed ALARM CODE TABLE Var MEANING E0 Functionalfaultofambientprobe Eu1 Functional fault of defrosting probe in this case any defrosting processeswillhaveadurationequaltotimed31 Eu2 F...

Страница 8: ...s of the device PEGO S r l does notaccept responsibility for any inaccuracies which may be present in this manual inthe case that these are due to printing or transcription errors and reservestheright...