Pego ECP202 EXPERT Скачать руководство пользователя страница 19

                                                                                                  

ECP

202

 EXPERT D7.5

 

                                                                                                                                                                                                                                                                                                           

                                                                                                                                     

Page  19

 

USE AND MAINTENANCE MANUAL 

Rev. 01-21

 

5.12 

5.13 

VARIABLES 

MEANING 

VALUES 

DEF. 

mOd 

Thermostat functioning mode 

0 = Cold function 
1  =  Hot  function  (in  this  mode  defrosting 
and fan disable Fst are excluded) 

P1 

Password type of protection 

(active when PA is not equal 0) 

0 = only display set point 
1 = display set point, AUX,  light access 
2 = access in programming not permitted 
3  =  access  in  second  level  programming 

not permitted 

PA 

Password 

(see P1 for the type of protection) 

0...999 

0 = not active 

reL 

release software 

indicates software version 

26 

(read only)

 

 
 
 

SWITCHING ON THE ECP202 EXPERT D7.5 ELECTRONIC CONTROLLER 

 

After wiring the electronic controller correctly, power up at 230 V AC; the display panel will 
immediately emit a beep and all the LEDs will come on simultaneously for a few seconds.

 

 
 

 

COMPRESSOR ACTIVATION/DEACTIVATION CONDITIONS

 

 

 

In  cold  mode  (mOd=0),

  the 

ECP202  EXPERT  D7.5 

controller  activates  the  compressor 

when  cold  room  temperature  exceeds  setting  +  differential  (r0);  it  deactivates  the 
compressor when cold room temperature is lower than the setting. 
If  Pump-Down  function  is  selected  (Parameter  AU1/AU2  =  4/-4),  see  chapter  5.16  for 
compressor activation/deactivation conditions. 

In  hot  mode  (mOd=1),

  the 

ECP202  EXPERT  D7.5 

controller  activates  the  heat  output 

(COMPR  output)  when  cold  room  temperature  drops  below  setting-differential  (r0);  it 
deactivates the heat  output  (COMPR output) when cold  room temperature is higher than 
the setting. 

 
 

 

MANUAL DEFROSTING 

 
To  defrost  just  press  the  dedicated  key  (see  section  5.2)  to  activate  the  elements  relay. 
Defrosting  will  not  take  place  if  the  end-of-defrost  temperature  setting  (d2)  is  lower  than 
the  temperature  detected  by  the  evaporator  sensor.  Defrosting  ends  when  the  end-of-
defrost temperature (d2) or maximum defrost time (d3) is reached, or due to forced manual 
defrost termination (end of defrost button or digital input). 

CAP. 5 - Parameter programming 

5.11 

Содержание ECP202 EXPERT

Страница 1: ...Rel Software 26 READ AND KEEP Use and maintenance manual ELECTRICAL BOARDS FOR REFRIGERATING INSTALLATIONS REV 01 21 ENG ECP202 EXPERT D7 5...

Страница 2: ...ECP202 EXPERT D7 5...

Страница 3: ...ting and displaying set points Page 15 5 7 Level 1 programming Page 15 5 8 List of Level 1 variables Page 16 5 9 Level 2 programming Page 16 5 10 List of Level 2 variables Page 19 5 11 Switching on th...

Страница 4: ...ator fans room light with outputs directly connectable to the various units Three phase N electrical defrost up to 7500W 2500W x 3 Innovative smartly designed ABS cover with transparent cover for acce...

Страница 5: ...SIONS Dimensions in mm IDENTIFICATION DATA The unit described in this manual has an ID plate on the side showing all the relevant identification data Name of Manufacturer Code of the unit Serial numbe...

Страница 6: ...5 Fit a general protection fuse upstream from the electronic controller 6 All wiring must be of a cross section suitable for relevant power levels 7 When it is necessary to make a probe sensor extensi...

Страница 7: ...and remove the cover for the screws on the right side Fig 2 Remove the 4 fastening screws from the front panel of the b Fig 3 Close the transparent door Fig 4 Open the front panel of the box by lifti...

Страница 8: ...possible In particular keep the power cables away from the signal cables Use any sealing strips Fig 8 Close the front panel again paying attention that the cables are inside the box and that the gask...

Страница 9: ...through heaters with temperature control through cycle reversal Direct or pump down management and control of condensing unit up to 2HP Cold room light activation through key on the panel or through d...

Страница 10: ...ype of sensors that can be connected NTC 10K 1 Resolution 0 1 C Sensor read precision 0 5 C Read range 45 45 C ECP202 EXPERT D7 5 Output characteristics max applicable load 230VAC Compressor 1500W AC3...

Страница 11: ...the equipment is modified or transformed Under no circumstances Pego S r l will be liable for any loss of data and information costs of goods or substitute services damage to property people or animal...

Страница 12: ...NT KEYPAD AUXILIARY RELAY CONTROL controls the relays manual if parameter AU1 AU2 2 2 UP MUTE BUZZER ALARM STAND BY if the system shuts down the LED flashes room temperature SETTING DOWN MANUAL DEFROS...

Страница 13: ...flashes on stand by Outputs are deactivated Room light flashes if door switch activated Cold indicates activation of compressor Fans Defrosting Auxiliary indicates AUX relay calling if AU1 AU2 2 or 3...

Страница 14: ...s the Level 2 programming directly from Level 1 you must exit the programming mode first KEY TO SYMBOLS For purposes of practicality the following symbols are used the UP key is used to increase value...

Страница 15: ...efrost is not executed if the temperature read by the defrost sensor is greater than d2 If the sensor is faulty defrosting is timed 35 45 C 15 C d3 Max defrost duration minutes 1 240 min 25 min d7 Dri...

Страница 16: ...uring defrost 0 Fans run during defrost 1 Fans do not run during defrost 1 F6 Evaporator fans activation for air recirculation The fans activate for a time defined by F7 if they have not started worki...

Страница 17: ...sor remains off and defrosting is prevented in order to conserve the remaining cold 0 240 min 0 disabled 0 min CE2 Duration of compressor OFF time in the case of faulty ambient probe emergency mode 5...

Страница 18: ...tion factor for the SET button during night operation energy saving with In1 or In2 8 or 8 During night operation the control set is Set Control Set nSC In night mode decimal point flashes 20 0 20 0 C...

Страница 19: ...In cold mode mOd 0 the ECP202 EXPERT D7 5 controller activates the compressor when cold room temperature exceeds setting differential r0 it deactivates the compressor when cold room temperature is lo...

Страница 20: ...d solenoid valve For capillary systems without thermostat valve it is only necessary to control the cycle inversion solenoid valve via the defrost relay control PUMP DOWN FUNCTION Pump down function i...

Страница 21: ...of this manual WARNING During configuration at entry Module to select the entry Instrument ECP Base Series ECP Expert Series rel 25 or higher NET CONFIGURATION WITH MODBUS RTU PROTOCOL For RS485 conne...

Страница 22: ...ut inside the cold room Ec Compressor protection tripped e g thermal protection or max pressure switch All outputs except the alarm one where applicable are deactivated Check that compressor is workin...

Страница 23: ...C 2014 30 UE Electromagnetic compatibility EMC 2014 30 EU LA CONFORMITA PRESCRITTA DALLA DIRETTIVA E GARANTITA DALL ADEMPIMENTO A TUTTI GLI EFFETTI DELLE SEGUENTI NORME THE CONFORMITY REQUIRED BY THE...

Страница 24: ...ECP202 EXPERT D7 5 Page 24 USE AND MAINTENANCE MANUAL Rev 01 21 ECP202 EXPERT D7 5 WIRING DIAGRAM A 2 Appendices...

Страница 25: ...X REAR IN ABS 2 BOX FRONT IN ABS 3 FRONT COVER IN TRANSPARENT POLYCARBONATE 4 BOX FRONT OPENING HINGE 5 BOX CLOSURE SCREWS 6 BOARD FIXING SCREWS 7 DEFROST CONTACTOR 8 CPU BOARD 9 POLYCARBONATE SCREW C...

Страница 26: ...ECP202 EXPERT D7 5 Page 26 USE AND MAINTENANCE MANUAL Rev 01 21 NOTES...

Страница 27: ...ECP202 EXPERT D7 5 Page 27 USE AND MAINTENANCE MANUAL Rev 01 21...

Страница 28: ...l Via Piacentina 6 b 45030 Occhiobello ROVIGO ITALY Tel 39 0425 762906 e mail info pego it www pego it AFTER SALES ASSISTANCE SERVICE Tel 39 0425 762906 e mail tecnico pego it Distributor PEGO s r l...

Отзывы: