ECP
202
EXPERT D7.5
Page 14
USE AND MAINTENANCE MANUAL
Rev. 01-21
GENERAL
To enhance safety and simplify the operator’s work, the
ECP202 EXPERT D7.5
has two
programming levels; the first level (Level 1) is used to configure the frequently-modified
SETPOINT
parameters. The second programming level (Level 2) is for general parameter
programming of the various controller work modes.
It is not possible to access the Level 2 programming directly from Level 1: you must exit
the programming mode first.
KEY TO SYMBOLS
For purposes of practicality the following symbols are used:
•
(
)
the UP key
is used to increase values and mute the alarm.
•
(
)
the DOWN key
is used to decrease values and force defrosting.
SETTING AND DISPLAYING THE SET POINTS
1. Press the
SET key
to display the current
SETPOINT
(temperature).
2. Hold down the
SET key
and press the
(
)
or
(
)
keys to modify the
SETPOINT
.
Release the
SET key
to return to cold room temperature display: the new setting will be
saved automatically.