HUM2ESXX CONFIGURATION
- To exit the menu once the configuration values are set, simultaneously keep keys (
5
) and (
6
)
pressed for a few seconds until the cell humidity value appears again (displays 0.0 if ON/OFF).
Memorisation of the amendments made to the variables will happen automatically when exiting the
configuration menu.
Press the ON/OFF - STAND-BY key to enable the electronic control (when you enter 2nd level
programming, the humidifier automatically switches to STAND-BY mode).
DEFAULT
VAR.
MEANING
VALUES
ES-3M
ES-6M
ES-12
ES-6
ES-24
ES-48
S0
Pump discharge duration time for deconcentration.
0.1 ÷ 12.7 s
2
2
3
5
S1
Hours of work
Tenths of hours
-
-
-
-
S2
Discharges for deconcentration interval.
1 ÷ 250 min
15
15
15
15
S3
Delay time in insertion of electrodes after any pump discharge.
1 ÷ 12 s
2
2
2
2
S4
Water discharge after inactivity
0 – 24 h
1
1
1
1
S5
Minimum current differential between one water charge and
another.
0.2 ÷ 10 A
1
0,7
1
1
S6
Percentage of discharge pump activation
1 ÷ 50 %
25
25
20
15
S7
Pump discharge duration time for overcurrent.
0.1 ÷ 5.0 s
0.5
0.5
0.5
0.5
S8
Minimum current differential for water charge.
0.0 ÷5.0 A
0.1
0.1
0.3
0.5
S9
Functioning setting
0 ÷ 8
0
0
0
0
S10
Discharge Test
0 ÷ 1
1
1 1 1
CA1
Humidity probe calibration
-20 % ÷ 20 %
0 %
0 %
0 %
0 %
CA2
Channel humidity probe calibration
-20 % ÷ 20 %
0 %
0 %
0 %
0 %
CA3
NTC probe value correction
-10.0÷ 10.0 °C
0,0
0,0 0,0 0,0
t1
Delay in seconds to humidifier re-start
0-240 s
10 s
10 s
10 s
10 s
t2
Functioning time ON for essence.
1-30 s
2 s
2 s
2 s
2 s
t3
Functioning time OFF for essence.
0-99 min
5 min
5min 5min 5
min
t4
Timer for manual insertion outlet fans.
0-24 hrs 0=Dis.
0
0 0 0
In2
Digital input In2 and activation status setting.
0 ÷ 9
1
1 1 1
In3
POWERED input In3 and activation status setting.
0 ÷ 9
0
0 0 0
dO4
Digital output dO4 functioning setting.
-3 ÷ 4
1
1 1 1
dO5
Digital output dO5 functioning setting.
-3 ÷ 4
0
0 0 0
HSE
Maximum value attributable to set point
0 ÷ 99
99
99 99 99
Ad
MODBUS-RTU network address or master-slave
configuration.
0 ÷ 247
1
1 1 1
MS
Master-Slave setting (with MS=0 modbus is enabled)
0 ÷ 6
0
0 0 0
rEL
release software MASTER
read only
11
11 11 11
6