HUM2ESXX CONFIGURATION 

 

- To exit the menu once the configuration values are set, simultaneously keep keys (

5

) and (

6

pressed for a few seconds until the cell humidity value appears again (displays 0.0 if ON/OFF). 

 
Memorisation of the amendments made to the variables will happen automatically when exiting the 
configuration menu. 
 
Press the ON/OFF - STAND-BY key to enable the electronic control (when you enter 2nd level 
programming, the humidifier automatically switches to STAND-BY mode). 
 

 
 
 

DEFAULT 

VAR. 

MEANING 

VALUES 

ES-3M 
ES-6M 

ES-12 

ES-6 

ES-24

ES-48 

S0 

Pump discharge duration time for deconcentration. 

0.1 ÷ 12.7 s 

S1 

Hours of work 

Tenths of hours

S2 

Discharges for deconcentration interval.  

1 ÷ 250 min 

15 

15 

15 

15 

S3 

Delay time in insertion of electrodes after any pump discharge. 

1 ÷ 12 s 

S4 

Water discharge after inactivity 

0 – 24 h 

S5 

Minimum current differential between one water charge and 
another. 

0.2 ÷ 10 A 

0,7 

S6 

Percentage of discharge pump activation 

1 ÷ 50 % 

25 

25 

20 

15 

S7 

Pump discharge duration time for overcurrent. 

0.1 ÷ 5.0 s 

0.5 

0.5 

0.5 

0.5 

S8 

Minimum current differential for water charge. 

0.0 ÷5.0  A 

0.1 

0.1 

0.3 

0.5 

S9 

Functioning setting 

0 ÷ 8 

S10 

Discharge Test  

0 ÷ 1 

1 1 1 

CA1 

Humidity probe calibration 

-20 % ÷ 20 % 

0 % 

0 % 

0 % 

0 % 

CA2 

Channel humidity probe calibration  

-20 % ÷ 20 % 

0 % 

0 % 

0 % 

0 % 

CA3 

NTC probe value correction   

-10.0÷ 10.0 °C 

0,0 

0,0 0,0 0,0 

t1 

Delay in seconds to humidifier re-start 

0-240 s 

10 s 

10 s 

10 s 

10 s 

t2 

Functioning time ON for essence. 

1-30 s 

2 s 

2 s 

2 s 

2 s 

t3 

Functioning time OFF for essence. 

0-99 min 

5 min 

5min 5min 5 

min 

t4 

Timer for manual insertion outlet fans. 

0-24 hrs 0=Dis.

0 0 0 

In2 

Digital input In2 and activation status setting. 

0 ÷ 9 

1 1 1 

In3 

POWERED input In3 and activation status setting. 

0 ÷ 9 

0 0 0 

dO4 

Digital output dO4 functioning setting. 

-3 ÷ 4 

1 1 1 

dO5 

Digital output dO5 functioning setting. 

-3 ÷ 4 

0 0 0 

HSE 

Maximum value attributable to set point 

0 ÷ 99 

99 

99 99 99 

Ad 

MODBUS-RTU network address or master-slave 
configuration. 

0 ÷ 247 

1 1 1 

MS 

Master-Slave setting (with MS=0 modbus is enabled) 

0 ÷ 6 

0 0 0 

rEL 

release software MASTER 

read only 

11 

11 11 11 

Содержание EasySteam 400HUM2ESXX

Страница 1: ...ELECTRONIC KIT 400HUM2ESXX 400KHUM2ESXX INSTALLATION MANUAL REV 01 11 EN...

Страница 2: ...RODUCTION Page 2 1 1 Generality CONFIGURATION Page 3 2 1 Hardware configuration Page 4 2 2 Software configuration SETTING DEFAULT VALUES Page 5 3 1 1st level values Page 5 3 2 2nd level values TABLE O...

Страница 3: ...uire the presence of the display and can be used independently It is also provided with status LED and switch jumper for the manual discharging of the cylinder The 400KHUM2ESXX electronic kit is suppl...

Страница 4: ...ing to 1 fig 1 Jumper J2 has 2 possible positions the jumper can be connected in position 1 2 or position 2 3 Table 1 hardware setting correspondence through jumper J2 and humidifier size ES series hu...

Страница 5: ...e Keeping the SET button pressed increases or decreases the value I1 by using the UP or DOWN keys Release the SET button The set value is now memorised by the software To exit programming press the UP...

Страница 6: ...AR MEANING VALUES DEFAULT all models Pr Steam output percentage 20 100 100 Bp Proportional band 1 20 Rh 10 StC Max humidity set point in channel 25 99 Rh 99 r0 Max humidity set differential in channel...

Страница 7: ...pump activation 1 50 25 25 20 15 S7 Pump discharge duration time for overcurrent 0 1 5 0 s 0 5 0 5 0 5 0 5 S8 Minimum current differential for water charge 0 0 5 0 A 0 1 0 1 0 3 0 5 S9 Functioning se...

Страница 8: ...a Piacentina 6 b 45030 Occhiobello ROVIGO ITALY Tel 39 0425 762906 Fax 39 0425 762905 e mail info pego it www pego it Dealer Document code 400 HUM2ESXX ELECTRONIC KIT rel 01 11 ITA PEGO s r l reserves...

Отзывы: