HUM2ESXX CONFIGURATION
SOFTWARE CONFIGURATION
Software is configured by setting the hidden parameter I1. This parameter allows you to vary the
nominal absorbed current value while the machine is operating. Parameter I1 is the fulcrum upon
which correct reading of amperometric absorption is developed and ensuing software processing.
In order to access this parameter, connect the NANO EasySTEAM display and keep the UP button
pressed on the controller keyboard while the machine is without electrical power.
Power the machine, again pressing the
UP
button until the writing I1 appears on the display (the
operation lasts approximately 10 seconds).
Press the
SET
button to view the set value. Keeping the
SET
button pressed increases or decreases
the value
I1
by using the
UP
or
DOWN
keys. Release the
SET
button. The set value is now
memorised by the software.
To exit programming, press the
UP
and
DOWN
keys simultaneously for about 2 seconds.
Table of software setting correspondence through value
I1.
ES series humidifier model
OEM series humidifier model
Value I1
400ES3MN
400ES3MOEMN / 400ES3MOEMCN
9
400ES6MN
400ES6MOEMN / 400ES6MOEMCN
13,5
400ES6N
400ES6OEMN / 400ES6OEMCN
6,5
400ES12N
400ES12OEMN / 400ES12OEMCN
13
400ES24N
400ES24OEMN / 400ES12OEMCN
25
400ES48N
50
Setting value I1 is fundamental for the correct functioning of the humidifier.
For the respect the values indicated in the table, including decimals.
Setting values different from those indicated and/or not corresponding with the
hardware setting of jumper J2, could cause malfunctioning or damage to the
appliance
.