HUM2ESXX CONFIGURATION 

 

SOFTWARE CONFIGURATION 

 
Software is configured by setting the hidden parameter I1. This parameter allows you to vary the 
nominal absorbed current value while the machine is operating. Parameter I1 is the fulcrum upon 
which correct reading of amperometric absorption is developed and ensuing software processing. 
In order to access this parameter, connect the NANO EasySTEAM display and keep the UP button 
pressed on the controller keyboard while the machine is without electrical power. 
 
Power the machine, again pressing the 

UP

 button until the writing I1 appears on the display (the 

operation lasts approximately 10 seconds). 
 
Press the 

SET

 button to view the set value. Keeping the 

SET

 button pressed increases or decreases 

the value 

I1

 by using the 

UP

 or 

DOWN

 keys. Release the 

SET

 button. The set value is now 

memorised by the software. 
 
To exit programming, press the 

UP

 and 

DOWN

 keys simultaneously for about 2 seconds. 

 
 
Table of software setting correspondence through value 

I1.

 

 

 
 
 
 
 
 
 

 
 
 
 
 
 
 
 

ES series humidifier model 

OEM series humidifier model 

Value I1 

 

 

 

400ES3MN   

400ES3MOEMN / 400ES3MOEMCN 

400ES6MN 

400ES6MOEMN / 400ES6MOEMCN 

13,5 

400ES6N 

400ES6OEMN    / 400ES6OEMCN 

6,5 

400ES12N 

400ES12OEMN  / 400ES12OEMCN 

13 

400ES24N 

400ES24OEMN  / 400ES12OEMCN 

25 

400ES48N  

50 

 

Setting value I1 is fundamental for the correct functioning of the humidifier.  
For the respect the values indicated in the table, including decimals. 
Setting values different from those indicated and/or not corresponding with the 
hardware setting of jumper J2, could cause malfunctioning or damage to the 
appliance

2.2

3

 

Содержание EasySteam 400HUM2ESXX

Страница 1: ...ELECTRONIC KIT 400HUM2ESXX 400KHUM2ESXX INSTALLATION MANUAL REV 01 11 EN...

Страница 2: ...RODUCTION Page 2 1 1 Generality CONFIGURATION Page 3 2 1 Hardware configuration Page 4 2 2 Software configuration SETTING DEFAULT VALUES Page 5 3 1 1st level values Page 5 3 2 2nd level values TABLE O...

Страница 3: ...uire the presence of the display and can be used independently It is also provided with status LED and switch jumper for the manual discharging of the cylinder The 400KHUM2ESXX electronic kit is suppl...

Страница 4: ...ing to 1 fig 1 Jumper J2 has 2 possible positions the jumper can be connected in position 1 2 or position 2 3 Table 1 hardware setting correspondence through jumper J2 and humidifier size ES series hu...

Страница 5: ...e Keeping the SET button pressed increases or decreases the value I1 by using the UP or DOWN keys Release the SET button The set value is now memorised by the software To exit programming press the UP...

Страница 6: ...AR MEANING VALUES DEFAULT all models Pr Steam output percentage 20 100 100 Bp Proportional band 1 20 Rh 10 StC Max humidity set point in channel 25 99 Rh 99 r0 Max humidity set differential in channel...

Страница 7: ...pump activation 1 50 25 25 20 15 S7 Pump discharge duration time for overcurrent 0 1 5 0 s 0 5 0 5 0 5 0 5 S8 Minimum current differential for water charge 0 0 5 0 A 0 1 0 1 0 3 0 5 S9 Functioning se...

Страница 8: ...a Piacentina 6 b 45030 Occhiobello ROVIGO ITALY Tel 39 0425 762906 Fax 39 0425 762905 e mail info pego it www pego it Dealer Document code 400 HUM2ESXX ELECTRONIC KIT rel 01 11 ITA PEGO s r l reserves...

Отзывы: