Chapter 5
– Data programming
DIN NANO 3RK
Page 15
Rev. 01-16
In2
Settings of no.2 Digital
input
8 = General low pressure alarm (with DI=1)
7 = General high pressure alarm (with DI=1)
6 = Freon level alarm (with DI=1)
5 = Central alarm in manual mode (with DI=1)
4 = Read-only Alarm (with DI=1)
3 = Output No.3 Alarm (with DI=1)
2 = Output No.2 Alarm (with DI=1)
1 = Output No.1 Alarm (with DI=1)
0 = Disabled
-1 = Output No.1 Alarm (with DI=0)
-2 = Output No.2 Alarm (with DI=0)
-3 = Output No.3 Alarm (with DI=0)
-4 = Read-only Alarm (with DI=0)
-5 = Central alarm in manual mode (with DI=0)
-6 = Freon level alarm (with DI=0)
-7 = General high pressure alarm (with DI=0)
-8 = General low pressure alarm (with DI=0)
2
In3
Settings of no.3 Digital
input
8 = General low pressure alarm (with DI=1)
7 = General high pressure alarm (with DI=1)
6 = Freon level alarm (with DI=1)
5 = Central alarm in manual mode (with DI=1)
4 = Read-only Alarm (with DI=1)
3 = Output No.3 Alarm (with DI=1)
2 = Output No.2 Alarm (with DI=1)
1 = Output No.1 Alarm (with DI=1)
0 = Disabled
-1 = Output No.1 Alarm (with DI=0)
-2 = Output No.2 Alarm (with DI=0)
-3 = Output No.3 Alarm (with DI=0)
-4 = Read-only Alarm (with DI=0)
-5 = Central alarm in manual mode (with DI=0)
-6 = Freon level alarm (with DI=0)
-7 = General high pressure alarm (with DI=0)
-8 = General low pressure alarm (with DI=0)
3
DO5
General alarm output
settings
1 = DO5 relay enabled in presence of
alarm
0 = DO5 relay disabled
-1 = DO5 relay disabled in presence
of alarm
1
EP4
Pressure (bar) equal to
4mA. Referring to the
adjustment sensor.
-
1.0…EP2-0,1
(with mOd=0)
0.0
*
(with mOd=1 or
2)
0.0
EP2
Pressure (bar) equal to
20mA. Referring to the
adjustment sensor.
EP4+0,1
…50.0
(with mOd=0)
12.0
*
(with mOd=1 or
2)
30.0