10
Table 5.1
Beckett NX Burner Specifications
Boiler Model No.
Burner Model
Nozzle Manufacturer, Size
Pump Pressure (psig)
Head/Air Setting
Low Fire Baffle
WV-DV-03-075
NX70LB
Delavan 0.60 60° W¹
175
2.25
Yes
WV-DV-03-085
NX70LB
Delavan 0.65 60° W
175
3.00
Yes
WV-DV-03-110
NX70LB
Hago 0.85 60° B¹
175
3.75
No
WV-DV-04-115
NX70HB
Hago 0.85 60° B
170
1.50
Yes
WV-DV-04-130
NX70HB
Hago 1.00 60° B¹
170
1.50
No
Table 5.2
Table 5.3
Carlin EZ1-HP Burner Specifications
Boiler Model No.
Delavan Nozzle Size
Pump Pressure (psig)
Air Boot Setting
Head Bar
WV-DV-03-075
.60 70° A¹
150
0.5
0.75
WV-DV-03-085
.65 70° A¹
150
0.6
0.75
WV-DV-03-110
.85 70° A
150
0.85
1.10 - 1.25
WV-DV-04-115
Hago 1.00 60° B¹
140
1.00
1.10 - 1.25
WV-DV-04-130
Hago 1.10 60° B
140
1.25
1.10 - 1.25
Riello BF5 Burner Specifications
Boiler Model No.
Nozzle Size
Pump Pressure (psig)
Turbulator Setting
Air Damper Setting
WV-DV-03-075
Delavan .60 80° B¹
165
1
3.3
WV-DV-03-085
Delavan .65 80° B¹
165
1
3.8
WV-DV-03-110
Delavan .90 80° B
165
2
5.0
WV-DV-04-115
Hago .85 60° B¹
180
2
5.0
WV-DV-04-130
Hago 1.10 60° B
140
4
5.0
Start-up and adjustment recommendations: Above Turbulator, Pin, Air Damper, and Air Dial settings are start-up settings only. Adjust burner for highest
CO² (no more than 13%) while maintaining a 0 smoke spot. Pressure or draft over fire and in flue cannot be adjusted. However, draft and/or pressure
measurements must be taken in these two locations and recorded for reference. All adjustments and measurements must be made using suitable
instruments such as those found in a Bacharach Combustion Test Kit.
Factory Installed Nozzles are indicated in
Boldface.
1. Shipped Loose