Menu #

16

17

18

19

20

21

22

feature

Hi fan or aux Heat

dual fuel operation

Heat Pump economy/ 

Comfort

%rH user adjust

front Panel

setback Control

dehum. normally 

open/Closed

oa economizer 

offset

range

FAN HI,

AUX HEAT

OFF,

0º - 55ºF,

-9.5º – 13.5ºC

OFF, 

0 – 55 Minutes

Enable / Disable

Enable / Disable

Normally Open (NO) / 

Normally Closed (NC)

0º to 15ºF,

0º to 7.5ºC

factory default*

AUX HEAT

OFF

15

Enabled

Disabled (Off)

NC

10°F

increment

-

1ºF, .5ºC

1 minute

-

-

-

1ºF, .5ºC

Comments

Selects either Fan High (2 Fan Speeds) or Aux Heat operation.  

If Fan High is selected, AUX HEAT mode is disabled.  

Available modes:  OFF, HEAT, COOL, AUTO  

If Aux Heat is selected, Fan High is disabled.  

Available modes: OFF, HEAT, COOL, AUTO, Aux HEAT   

Disables Heat Pump operation if Outside Air Temperature is below 

the selected value and a Heating demand exists. 

If OFF is selected, and/or AUX HEAT is not enabled in Service 

Menu 16, and/or no OA Temperature Sensor is connected, Dual 

Fuel Operation is disabled.  The Heat Pump operation is then 

allowed at all temperatures. 

If 0-55°F is selected for the OA Temperature and the OA Tempera

-

ture sensor drops below the selected value, the Heat Pump opera

-

tion will be disabled only for a Heating demand.  When the OA 

Temperature increases equal to or greater than the selected OA 

value, Heat Pump operation is enabled and Aux Heat operation is 

disabled.  The Aux Heat output may still be enabled if a valid Aux 

Heat demand exists.  Heat Pump operation must meet minimum 

On and Off time to prevent short cycling.

Enables a delay to On for Aux Heat output; default is 15 minutes.  

The delay is only enabled during AUTO or HEAT modes.

Allows occupant to adjust or not adjust RH levels.

This menu item enables SETBACK as a system mode selection.  If 

SETBACK mode is selected, the thermostat will control to the cur

-

rent Setback Heat and Setback Cool Set Points.  The thermostat 

will not respond to any changes in the Setback input if SETBACK 

mode is selected.  

During Setback operation, the thermostat will override the default 

display to display the Zone Temperature and SETBACK icon.  Any 

key presses will have no effect on the Setback operation except for 

the System Switch Selection button.  Pressing the System Switch 

button will allow the user to exit the SETBACK mode.

If disabled, Setback is not an available mode and feature. The 

thermostat will respond to changes in the Setback input if SET

-

BACK mode is not selected.  

Normally Closed:  If RH Demand = Output Disabled

                             No RH Demand = Output Enabled

Normally Open:    If RH Demand = Output Enabled

 

                            No RH Demand = Output Disabled

The adjustable value that is subtracted from the room temperature 

and then compared to the OA temperature.  If OA ≤ Temp minus 

Offset, then OA damper is enabled.  

Содержание TH170

Страница 1: ...ly to 24VAC oper ated humidifiers No other connection or interlock is required Several installer selectable operating modes are available as described in the Humidity Control Operation Section Dehumid...

Страница 2: ...3 When installed the TH170 Heating and cooling setback limits are used as temperature control points Fan operation in setback is cycled with demand Pressing any button will override setback for 1 hour...

Страница 3: ...on or Outside Air operation A humidity sensor module must be connected to the PCBA for the humidity control to function If you are installing a TH70 001 only the Outside Air Economizer feature is avai...

Страница 4: ...tion of Humidify or Dehumidify must be made in Service Menu 12 to allow the adjustment of RH Set Point If Outside Air operation is selected from Service Menu 12 instead of Humidifi cation or Dehumidif...

Страница 5: ...elay is extended to 10 minutes The time delay can only be extended once If the thermostat is powered up in the Occupied State and the door is open after 10 minutes the thermostat will disable its outp...

Страница 6: ...of 58 90 F A user selection of OFF will disable the Cooling Setback Zone Temperature offset adjusts the sensed Zone Temperature reading Allows you to choose what the occupant can adjust on the TH170...

Страница 7: ...increases equal to or greater than the selected OA value Heat Pump operation is enabled and Aux Heat operation is disabled The Aux Heat output may still be enabled if a valid Aux Heat demand exists H...

Страница 8: ...COPYRIGHT 2008 PECO INC ALL RIGHTS RESERVED P N 69290 3220 2088 REV 0 PAGE 8...

Отзывы: