Peco TH170 Скачать руководство пользователя страница 5

The thermostat has an economizer feature that allows the use of outside 

air to cool the controlled space when outside air is at an appropriate 

temperature with respect to Room Temperature and Temperature Set 

Point (SP).  This section also outlines logic to be used with RH sensor 

enabled units (-002 Models) to address potential increases to indoor 

humidity caused by humid outside air during Economizer operation.

The OA output is disabled anytime the thermostat is operating in the 

OFF or SETBACK modes, or when the Setback input is closed.   If you 

are installing a TH170-001 (no onboard RH sensor), selections 4 and 5 

are disabled.  An OA Sensor is required for OA3-5.

The Outside Air Economizer user selection configurations are:

outside air damper (Default):  Any time the thermostat is out 

of OFF mode or not operating in Setback, the Outside Air output 

is enabled (damper open). This feature can be used to provide 

minimum ventilation.

outside air damper Cycle: This feature enables OA output with 

an active heating or cooling demand.

outside air economizer:  In this setting, the OA damper 

operates only during active Cooling demand and is based on 

OA temperature.  If the sensed OA Temperature is ≤ the room 

temperature minus the OA Economizer Offset, then the OA output 

is enabled. The OA output is disabled when the OA Temperature 

> the Room Temperature minus the OA Economizer Offset.  OA 

Economizer Offset range is user selectable from 0 - 15°F in the 

Service Menu, with a default of 10°F.  The Outside Air Econo

-

mizer conditions are continuously checked.     

oa and relative Humidity economizer:  Like option 3, the 

OA damper operates only during active Cooling demand, but its 

operation is based on both OA temperature and %RH values.   

The OA economizer follows the logic of option 3, unless excess 

humidity is created and/or the conditions in configuration 3 are no 

longer met.  

oa and relative Humidity economizer with Humidity abate-

ment:  Like option 3 and 4, the OA damper operates only during 

active Cooling demand.  Like option 4, operating logic is based 

on both OA and % RH values.  The OA economizer uses OA 

to provide economizer operation and will OVERCOOL to abate 

excess humidity.

1.

2.

3.

4.

5.

oCCuPanCy oPeration

If the TH170 is installed with occupancy sensors, operation is as follows:

In an 

occupied state the thermostat operates normally and looks for an 

open door.  

On a Door Open signal the thermostat begins to control the 

ambient temperature to the programmed Set Point and waits for a 

door close.  If door is open for more than 2-minutes the thermo

-

stat outputs are disabled.  If a button is pressed on the keypad 

before the two minute timer expires, the time delay is extended 

to 10 minutes.  The time delay can only be extended once.  If the 

thermostat is powered up in the Occupied State and the door is 

open, after 10 minutes the thermostat will disable its outputs.  The 

Reversing value may remain enabled depending on the demand 

and configuration.  Once the thermostat outputs are disabled, a 

door closure is required to re-enable the outputs. 

On a Door Closed signal the thermostat starts a 2-minute timer in 

which to look for occupancy.  If the occupancy sensor transitions 

to unoccupied and the timer expires, the thermostat enters into 

the Unoccupied State.  If the occupancy sensor transitions from 

unoccupied to occupied while the timer is running the thermostat 

will remain in Occupied State.  If the occupancy sensor transitions 

from unoccupied to occupied after the 2-minute timer expires, the 

thermostat will remain in the Occupied State.  

In an 

unoccupied state the thermostat sets Heating and Cooling Set 

Points to Setback values, as determined by factory or user settings.  In 

this mode the fan is automatically set to cycle with demand. The ther-

mostat will continue to monitor the occupancy sensor and will go to the 

Occupied State if it sees occupancy.

If the only a Door / Window Switch is installed, the thermostat will dis

-

able the thermostat outputs when the input is open for longer than 2 

minutes.

© COPYRIGHT 2008 PECO, INC.  ALL RIGHTS RESERVED. 

 

 

 

 

 

P/N 69290 3220-2088  REV 0  PAGE 4

© COPYRIGHT 2008 PECO, INC.  ALL RIGHTS RESERVED. 

 

 

 

 

 

P/N 69290 3220-2088  REV 0  PAGE 5

operation  (i.e. example)

OA damper is always enabled (damper open).  OA closed in OFF or Setback modes.

76 > 72 = Active Cooling demand and OA Damper is enabled. OA damper is enabled (damper open) whenever there is active 

heating or cooling demand.  

60 ≤ 72 – 10  =   OA Economizer Enabled (Open) if an active cooling demand exists.

OA Economizer offset is user adjustable in the service menu.

60 ≤ 72 – 10  =  OA Economizer Enabled and Timer Set 

RH also checked :  72%RH (value is stored)

5 minutes pass with Damper enabled

Thermostat checks for 2 conditions.  If either is TRUE, the OA is disabled.

New RH - Stored RH > 10%                  80  - 72 > 8%       FALSE

New RH > RH SP                                  80 > 77                 TRUE

                                                                                                      OA is disabled

1 hour timer begins.  After 1 hour, OA & RH are checked again.

60 ≤ 72 – 10  =  OA Economizer Enabled and Timer Set 

RH also checked :  72%RH (value is stored)

5 minutes pass with Damper enabled

If New RH >  RH SP, the OA is disabled             80 > 77       OA is disabled 

Overcooling operation begins, allowing the Temp. to drop up to 3°F below the Temp SP to satisfy the dehumidification demand.

1 hour timer begins

After 1 hour OA & RH are checked again

1.

2.

Conditions

Any Temperature

Room Temp = 76

Temp SP = 72

Cool or Auto Mode

OA = 60

Temp = 72

Offset = 10

Cool or Auto Mode

OA = 60

Temp = 72

Offset = 10

Current RH = 72%

New RH = 80% 

RH SP = 77%

Cool or Auto Mode

OA = 60

Temp = 72

Offset = 10

Current RH = 72%

New RH = 80% 

RH SP = 77%

Cool or Auto Mode

requirements

None

None

OA Sensor

TH170-002 Model 

     + OA Sensor

TH170-002 Model 

     + OA Sensor

Mode

1

2

3

4

5

Содержание TH170

Страница 1: ...ly to 24VAC oper ated humidifiers No other connection or interlock is required Several installer selectable operating modes are available as described in the Humidity Control Operation Section Dehumid...

Страница 2: ...3 When installed the TH170 Heating and cooling setback limits are used as temperature control points Fan operation in setback is cycled with demand Pressing any button will override setback for 1 hour...

Страница 3: ...on or Outside Air operation A humidity sensor module must be connected to the PCBA for the humidity control to function If you are installing a TH70 001 only the Outside Air Economizer feature is avai...

Страница 4: ...tion of Humidify or Dehumidify must be made in Service Menu 12 to allow the adjustment of RH Set Point If Outside Air operation is selected from Service Menu 12 instead of Humidifi cation or Dehumidif...

Страница 5: ...elay is extended to 10 minutes The time delay can only be extended once If the thermostat is powered up in the Occupied State and the door is open after 10 minutes the thermostat will disable its outp...

Страница 6: ...of 58 90 F A user selection of OFF will disable the Cooling Setback Zone Temperature offset adjusts the sensed Zone Temperature reading Allows you to choose what the occupant can adjust on the TH170...

Страница 7: ...increases equal to or greater than the selected OA value Heat Pump operation is enabled and Aux Heat operation is disabled The Aux Heat output may still be enabled if a valid Aux Heat demand exists H...

Страница 8: ...COPYRIGHT 2008 PECO INC ALL RIGHTS RESERVED P N 69290 3220 2088 REV 0 PAGE 8...

Отзывы: