TH170 HEAT PUMP THERMOSTAT

READ THESE INSTRUCTIONS CAREFULLY BE-

FORE ATTEMPTING TO INSTALL, OPERATE OR 

SERVICE THIS THERMOSTAT.

Failure to observe safety information and comply 

with instructions could result in PERSONAL INJURY, 

DEATH AND/OR PROPERTY DAMAGE.

To avoid electrical shock or damage to equipment, 

disconnect power before installing or servicing and 

use only wiring with insulation rated for full thermo-

stat operating voltage.

Before installing this control, the Voltage Selection 

Switch must be placed in the correct position.  See 

instructions.

To avoid potential fire and/or explosion do not use in 

potentially flammable or explosive atmospheres.

Retain these instructions for future reference.  This 

product, when installed, will be part of an engi-

neered system whose specifications and perfor

-

mance characteristics are not designed or controlled 

by PECO.  You must review your application and 

national and local codes to assure that your installa-

tion will be functional and safe. 

WARNING

Use copper wire only, insulate or wire nut all unused 

leads.

Care should be used to avoid electrostatic discharge 

to the T170 thermostat.

This unit has configuration jumpers.  You may need 

to reconfigure this thermostat for your application.

CAUTION

Preinstallation Considerations

Thermostat Location – The thermostat should be used indoors only.  It 

should be mounted on an inner wall 48” from the floor, in a location with 

freely circulating air, and where it will be responsive to changes in room 

temperature.  Avoid mounting near heat generating appliances (i.e. TV, 

heater, refrigerator), or in direct sunlight.

Humidifiers – The humidify output connects directly to 24VAC oper

-

ated humidifiers.  No other connection or interlock is required.  Several 

installer-selectable operating modes are available as described in the 

Humidity Control Operation Section.

Dehumidifiers – The dehumidify output connects to the dehumidify input 

on variable–speed furnaces and fan coils.  Additional dehumidification is 

done by controlling the compressor.  Several installer-selectable operat

-

ing modes are available as described in the Humidity Control Operation 

Section.

Outdoor Temperature Sensor – The use of an outdoor temperature in 

conjunction with the TH170 will improve the performance and increase 

the number of humidity control modes available to the installer.  Run two 

wires from the TH170 to an outdoor location. The outdoor sensor can be 

mounted to the outdoor unit and existing control wires may be used for 

its connection.

aPPliCations and features

Heat Pump Thermostat for 24 VAC Applications

Up to 3 Heat and 2 Cool Stages

System Selection:  Off-Heat-Cool-Auto-Setback-Aux Heat

Up to 2 Fan Stages:  On-Auto (1 fan), Hi-Low-Auto (2 fans)

Dehumidification/Humidity Control*

Setback and Off-Override Capable

Also Configurable With

Outdoor Air Sensors

Remote Probes

Occupancy Control Systems

Outside Air Ecomomizer (Damper Control)

*Available on the TH170-002 model only.

!

!

sPeCifiCations

Temperature Set Point Range 

50 to 90°F / 10 to 32°C 

RH Set Point Range 

 

Humidity: 20-45% RH,  Dehumidification: 50-90% RH

Electrical Rating   

 

24 VAC Input, 24 VAC Output,  Hardwired

Memory – Back-Up  

 

EEPROM, No batteries required, Stores settings for unlimited time.

Mounting  

 

 

Installs on standard 4” x 4” device box with a 2” x 4” horizontal mud ring

Humidity Accuracy   

 

+/- 3% RH

Storage Temperature Range   

-20 to 130°F

Physical Dimensions 

 

4.4”H x 5.8”W x 1.1”D

Agency Approvals   

 

UL, UL Canada

© COPYRIGHT 2008 PECO, INC.  ALL RIGHTS RESERVED. 

 

 

 

 

 

P/N 69290 3220-2088  REV 0  PAGE 1

Содержание TH170

Страница 1: ...ly to 24VAC oper ated humidifiers No other connection or interlock is required Several installer selectable operating modes are available as described in the Humidity Control Operation Section Dehumid...

Страница 2: ...3 When installed the TH170 Heating and cooling setback limits are used as temperature control points Fan operation in setback is cycled with demand Pressing any button will override setback for 1 hour...

Страница 3: ...on or Outside Air operation A humidity sensor module must be connected to the PCBA for the humidity control to function If you are installing a TH70 001 only the Outside Air Economizer feature is avai...

Страница 4: ...tion of Humidify or Dehumidify must be made in Service Menu 12 to allow the adjustment of RH Set Point If Outside Air operation is selected from Service Menu 12 instead of Humidifi cation or Dehumidif...

Страница 5: ...elay is extended to 10 minutes The time delay can only be extended once If the thermostat is powered up in the Occupied State and the door is open after 10 minutes the thermostat will disable its outp...

Страница 6: ...of 58 90 F A user selection of OFF will disable the Cooling Setback Zone Temperature offset adjusts the sensed Zone Temperature reading Allows you to choose what the occupant can adjust on the TH170...

Страница 7: ...increases equal to or greater than the selected OA value Heat Pump operation is enabled and Aux Heat operation is disabled The Aux Heat output may still be enabled if a valid Aux Heat demand exists H...

Страница 8: ...COPYRIGHT 2008 PECO INC ALL RIGHTS RESERVED P N 69290 3220 2088 REV 0 PAGE 8...