FIT-1003-M Operation & Maintenance Manual 

 

 

  Paragon Controls Incorporated 

Revision Level 002 

 

2. CALIBRATION 

It is recommended that the DPT ZERO Calibration be performed upon installation. Span Calibration is 
not affected by the Zero Calibration. The Span of the unit has been factory calibrated and should only be 
adjusted using high accuracy test equipment. 

Refer to sections 1.1.1 and 1.1.2. 

Zero Calibration Equipment Required: 

DMM (Digital Multi Meter) 

Span Calibration Equipment Required: 

Low pressure air source (Paragon PS-100 or equivalent)  

Manometer for measuring low pressure 

DMM (Digital Multi Meter) 

2.1. 

DPT ZERO CALIBRATION 

The following zero calibration procedure can be performed without the need to perform a span 
calibration.  

Step 1.

 

Remove the cover by removing the 4 mounts screws. 

Step 2.

 

Apply power to the transducer and verify Power Status LED is illuminated. 

Step 3.

 

Using a DMM set to voltage mode, monitor between TP1 (GND) and TP2 (DPT). 

Step 4.

 

With zero pressure applied, adjust 

DPT ZERO

 potentiometer for a reading of 

0.0±.001vdc. 

2.2. 

OUTPUT SPAN CALIBRATION 

Note: It is recommended that a zero calibration be completed before performing a span calibration. 

 

2.2.1. 0-5VDC 

Output 

Procedure 

Step 1.

 

Using a DMM set to voltage mode, monitor between (

SIG)

 and (

-) 

terminal. 

Step 2.

 

Apply full scale pressure (Value shown on the transducer label) to the Total (High) 
Pressure port and adjust the 

SPAN

 potentiometer for an output reading of 

5±.01vdc. 

Step 3.

 

Reinstall the cover and 4 mounting screws. 

2.2.2. 0-10vdc 

Output 

Procedure 

Step 1.

 

Using a DMM set to voltage mode, monitor between (

SIG)

 and (

-) 

terminal. 

Step 2.

 

Apply full scale pressure (Value shown on the transducer label) to the High 
Pressure port and adjust the 

SPAN

 potentiometer for an output reading of 

10±.01vdc. 

Step 3.

 

Reinstall the cover and 4 mounting screws.   

2.3. 

MAGNEHELIC GAUGE ZERO CALIBRATION 

2.3.1. Zero 

Calibration 

Step 1.

 

With no pressure applied, verify magnehelic gauge reads zero on the meter face. If 
not, use a small slotted screw driver and adjust the slotted screw located at the end 
of the indicating needle until a zero reading is achieved.  

 