FIT-1003-M Operation & Maintenance Manual
Paragon Controls Incorporated
1
Revision Level 002
1. INTRODUCTION
This user manual provides information on product features and guides you through all basic functions.
1.1. DESCRIPTION
The
FIT-1003M
Air Volume transducer sensor operates on the capacitance principal and is capable of
sensing ultra low differential pressures. In the capacitance cell, a very lightweight, responsive
diaphragm deflects a small amount when pressure is applied. This deflection results in a change in
capacitance, which is then detected and processed electronically into an output signal linear to the
velocity pressure. The electronic signal is then sent to the square root extractor/multiplier, which
converts the velocity pressure signal into an analog output signal linear to velocity (fpm) or volume
(cfm). The measured process air velocity/volume is independently indicated on a front panel mounted
magnehelic pressure gauge scaled in both cfm and fpm. This independent readout allows for quick and
immediate indication of Flow and Velocity and verification that the electronic transducer is operating
effectively. An integral red LED indicator verifies proper power supply wiring orientation.
1.1.1. Installation
Setup
Refer to figures below for pressure and electrical connections.
ELECTRICAL CONNECTIONS
12 TO 36VDC
POWER SUPPLY
+
+
-
-
e:
PRESSURE CONNECTIONS
STATIC PRESS
UR
E
CONN
ECTIO
N
TOTAL PRESS
UR
E
CONN
ECTIO
N
1003-M
ING TRANSDUCER
POWER
STATUS
FIT-1003-M
1654
12-36vdc
0-10VDC
23,000
AHU-1
erved:
+
-
PCI
PARAGON
CONTROLS
INCORPORATED
COVER MTG.
SCREWS
SIG
RECEIVER
(0-5/10VDC)
1.1.2. Adjustment
Locations
POWER
STATUS
TP2
DPT
TP1
GND
DPT
ZERO
ZERO
SPAN
+
-
SIG