FIT-1003-M Operation & Maintenance Manual 

 

 

  Paragon Controls Incorporated 

Revision Level 002 

 

1. INTRODUCTION 

This user manual provides information on product features and guides you through all basic functions. 

1.1. DESCRIPTION 

The 

FIT-1003M

 Air Volume transducer sensor operates on the capacitance principal and is capable of 

sensing ultra low differential pressures.  In the capacitance cell, a very lightweight, responsive 
diaphragm deflects a small amount when pressure is applied.  This deflection results in a change in 
capacitance, which is then detected and processed electronically into an output signal linear to the 
velocity pressure. The electronic signal is then sent to the square root extractor/multiplier, which 
converts the velocity pressure signal into an analog output signal linear to velocity (fpm) or volume 
(cfm). The measured process air velocity/volume is independently indicated on a front panel mounted 
magnehelic pressure gauge scaled in both cfm and fpm.  This independent readout allows for quick and 
immediate indication of Flow and Velocity and verification that the electronic transducer is operating 
effectively. An integral red LED indicator verifies proper power supply wiring orientation. 

1.1.1. Installation 

Setup 

Refer to figures below for pressure and electrical connections. 

ELECTRICAL CONNECTIONS

12 TO 36VDC

POWER SUPPLY

+

+

-

-

e:

PRESSURE CONNECTIONS

STATIC PRESS

UR

E

CONN

ECTIO

N

TOTAL PRESS

UR

E

CONN

ECTIO

N

1003-M

ING TRANSDUCER

POWER
STATUS

FIT-1003-M

1654

12-36vdc

0-10VDC

23,000
AHU-1

erved:

+

-

PCI

PARAGON

CONTROLS

INCORPORATED

COVER MTG.

SCREWS

SIG

RECEIVER

(0-5/10VDC)

 

1.1.2. Adjustment 

Locations 

 

POWER
STATUS

TP2
DPT

TP1
GND

DPT
ZERO

ZERO

SPAN

+

-

SIG

 