background image

 

DPT-4001 Operation & Maintenance Manual 

 

 

  Paragon Controls Incorporated 

Revision Level 002 

 

1. INTRODUCTION 

This user manual provides information on product features and guides you through all the basic 
functions of the DPT-4001. 

1.1. DESCRIPTION 

The 

DPT-4001

 differential pressure transducer sensor operates on the capacitance principal and is 

capable of sensing ultra low differential pressures.  In the capacitance cell, a very lightweight, 
responsive diaphragm deflects a small amount when pressure is applied.  This deflection results in a 
change in capacitance, which is then detected and processed electronically into an output signal linear to 
the differential pressure.

 The DPT-4001 can be configured as a Unipolar device (positive differential 

pressure only) or a Bipolar device (positive and negative differential pressures). A power indicator 
illuminates when power is attached correctly. 

1.1.1.  Field Connections & Output Load Limitations 

Refer to figure below for pressure and electrical connections. Use the chart shown below to determine 
load limitations verses loop power supply values. 

 

 

 

RECEIVER

SUPPLY

POWER

-

+

SPAN

ZERO

LO

HI

PCI

INCORPORATED

CONTROLS

PARAGON

TAG NO.:
W.O.#: 1300 / 1234

POWER: 12-36VDC
OUTPUT: 4-20mA

  

+

  

-

RANGE: 0-0.25"W.C.

MODEL: DPT-4001

V    = 12 + (0.022 x R      )

POWER SUPPLY VOLTAGE (VDC)

LOAD RES

IST

ANCE

 (OHMS)

0

0

250

10

20

30

36

MIN

12

LOAD

REGION

OPERATING

500

750

1045

40

POWER

-

+

(4-20mA)

 

 

Содержание DPT-4001

Страница 1: ...DPT 4001 Differential Pressure Transducer Operation Maintenance Manual Engineered for accuracy applicability durability and simplicity...

Страница 2: ......

Страница 3: ...LE OF CONTENTS TABLE OF CONTENTS i 1 INTRODUCTION 1 1 1 DESCRIPTION 1 1 1 1 Field Connections Output Load Limitations 1 1 1 2 Dimensions 2 2 CALIBRATION 3 2 1 UNIPOLAR ZERO CALIBRATION 3 2 2 BIPOLAR Z...

Страница 4: ...essed electronically into an output signal linear to the differential pressure The DPT 4001 can be configured as a Unipolar device positive differential pressure only or a Bipolar device positive and...

Страница 5: ...2 Revision Level 002 1 1 2 Dimensions Mount with 8 screws or 35mm Din Rail SPAN ZERO LO HI PCI INCORPORATED CONTROLS PARAGON TAG NO W O 1300 1234 POWER 12 36VDC OUTPUT 4 20mA RANGE 0 0 25 W C MODEL D...

Страница 6: ...eiver Step 2 Apply power to the DPT Step 3 Identify ZERO potentiometer Step 4 With no pressure applied adjust the ZERO potentiometer for a reading of 4 01mA 2 2 BIPOLAR ZERO CALIBRATION The following...

Страница 7: ...g 1 Verify Power Supply voltage is correct 2 Verify correct wire connections 3 Verify correct pressure connections 4 Verify input pressure differential with a manometer 5 Contact Factory Service Depar...

Страница 8: ...Paragon Controls Incorporated P O Box 99 Forestville CA 95436 http www paragoncontrols com Phone 707 579 1424 Revision Level 002...