MOST 20-2B
11
PACIFIC CONSOLIDATED INDUSTRIES
350003 Rev D
SECTION VI
6-1
TRANSFILLING THE MOST
6-2
PURPOSE
The MOST can be filled from the following devices: EDOCS-
120, GOX Carts and ‘H’ Cylinders or other sources of USP
grade gaseous oxygen. Table 6-1 shows the capacity
achievable by transfilling under various scenarios. The
‘H’ Cylinders are assumed to be at 2,250 psig and the values
in the table are approximate.
‘H’ Cyl
Qty
MOST Initial
Pressure- psig
Final Pressure-
psig
MOST
Oxygen
Capacity-
Liters
Empty 940 4230
250 1080 4850
500 1230 5490
750 1370 6130
1000 1520 6780
1
1500 1810 8070
Empty 1330 5930
250 1430 6370
500 1530 6820
750 1630 7270
1000 1730 7730
2
1500 1940 8640
Empty 1670 7440
250 1730 7710
500 1800 8000
750 1850 8280
1000 1920 8570
4
1500 2050 9140
Empty 1820 8130
250 1870 8330
500 1920 8540
750 1970 8750
1000 2010 8960
6
1500 2110 9370
Empty 1915 8530
250 1950 8680
500 1990 8850
750 2025 9010
1000 2060 9180
8
1500 2140 9500
Table 6-1 Capacity of MOST20-2B After Transfilling.
MOST Operating Panel
Figure 6-1
6-3
TRANSFILLING PROCEDURE
Unless otherwise specified, refer to Figure 6-1
MOST Operating Panel.
a. Position the high pressure quick connect vent valve
(V-3) to the vent position.
b. Remove the protective plug from the high pressure
input quick connecting port (C-4). Install the
transfilling adapter fitting (ADP-1), part number
790510-012, into the quick connect fitting. Ensure
that the adapter fitting is firmly engaged by the quick
connect fitting by pulling on the fitting.
c. Place the MOST on an elevated surface such as a
work bench or table. Position the ‘H’ cylinder as
close to the control panel as possible.
d. Connect one end of a clean conductive hose
assembly to the ‘H’ cylinder shutoff valve and the
other end of the pigtail to the transfilling adapter.
Tighten the fitting securely.
V-3
C-4
PROTECTIVE
PLUG
ADP-1
ADP-1
Содержание 793080-002
Страница 6: ...MOST 20 2B 2 PACIFIC CONSOLIDATED INDUSTRIES 350003 Rev D MOST P ID Schematic Figure 1 2...
Страница 20: ...MOST 20 2B 16 PACIFIC CONSOLIDATED INDUSTRIES 350003 Rev D Medical Oxygen Storage Tank MOST Figure 7 1...
Страница 25: ...MOST 20 2B 21 PACIFIC CONSOLIDATED INDUSTRIES 350003 Rev D Panel Assembly Figure 7 4...