© PCE Instruments
21
2
Specifications
2.1
Technical specifications
Manometer specifications
1 psi = 27.68 inH
2
O
1 psi = 68.947 mbar
1 psi = 703.072 mmH
2
O
1 psi = 6894.6 Pa
FSO: Full Scale Output
Air velocity
Unit
Range
Resolution
Accuracy
m/s (meters per second)
1.00 … 80.00
0.01
±2.5 % of reading at
10.00 m/s
Ft/min (feet per minute)
200 … 15733
1
Accuracy is
depending on duct
size and air velocity
Km/h (kilometers per hour)
3.6 … 288.0
0.1
MPH (miles per hour)
2.24 … 178.66
0.01
Knots (nautical miles per hour)
2.0 … 154.6
0.1
Air flow
Unit
Range
Resolution
CFM
0 … 99.999 ft³/min
0.0001 … 100
CMM
0 … 99.999 m³/min
0.001 … 100
CFM: cubic feet per minute
CFM (ft³/min) = Air velocity (ft/min) * Area (ft²)
CMM: cubic meters per minute
CMM (m³/min) = Air velocity (m/s) * Area (m²) * 60
Tem perature
Unit
Range
Resolution
Accuracy
°C
0 … +50.00
0.1
±1.0 °C
°F
32.0 … 122.0 °F
0.1
±2.0 °F
En
g
lis
h
Measuring range
5000 Pa
Accuracy
±0.3 % FSO (25 °C)
Repeatability
±0.2 % (Max. ±0.5 % FSO)
Linearity/hysteresis
±0.29 % FSO
Maximum pressure
10 psi
Response time
0.5 seconds typical
Error message
Pressure > measuring range
Err. 1
Error message
Pressure < measuring range
Err. 2
Unit
Range
Resolution
PSI
0.7252
0.0001
mbar
50.00
0.01
inH
2
O
20.07
0.01
mmH
2
O
509.8
0.1
Pa
5000
1
Содержание PCE-HVAC 2