OPERATING INSTRUCTIONS 

Universal Thermostat 

with modulating power control

 

 

© Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland 

Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55  • E-Mail: [email protected] • Internet: www.paul-lueftung.de

 

 

2.1.2.3 2-level control for backup duct heater 

 

The temperature sensor is installed 

downstream

 of the component backup duct heater. The control of the 

backup duct heater depends on the configured temperature threshold X1 (see appendix 1 and appendix 4):  
 

 

ON:   

 X1

 

OFF: T

 X1+H 

 
DIP-3 ON 

 

DIP-1, -2, -4 

OFF 

 
 
 
 
 
 
 
 

- Actual value of 

supply air temperature

 

H - 

Hysteresis 

X1  - setpoint  

upper switching value

 

 
2.1.2.4 Settings of operating mode ON/OFF control

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 

 
 
 

 

Button “Temp 1“ 

->  upper temperature threshold [X1] 

 

 

 

- keypress < 3 s = current switching threshold is displayed 

 

 

- keypress > 3 s = programming mode (display flashes) 

 

 

- setting range 15°C…65°C, increment: 0,5 K 

 
 

Button “Temp 2“ 

->  lower temperature threshold [X2] 

 

 

 

- keypress < 3 s = current switching threshold is displayed 

 

 

- keypress > 3 s = programming mode (display flashes) 

  

 

- setting range -15°C…15°C, increment: 0,5 K 

 
 

Button “Hyst.“ 

->  Hysteresis [H] 

 

 

 

- keypress < 3 s = current hysteresis is displayed 

 

 

- keypress > 3 s = programming mode (display flashes) 

 

 

- setting range 0,5…5 K, increment: 0,1 K 

 

 

Button 

+

  to 

increase value 

Button 

-

 

 to 

decrease value 

Button
Temp 1 

Button 
Temp 2 

Button 
Hysteresis 

Display “ACTUAL VALUE“ 
 

Indicator „locked“ 

Indicator 
“Consumer ON“ 

Indicator  
“Unit ready“ 

Содержание Universal Thermostat

Страница 1: ...er heater Back up duct heater fffff Paul W rmer ckgewinnung GmbH August Horch Stra e 7 08141 Reinsdorf Tel 49 0 375 303505 0 Fax 49 0 375 303505 55 Deutschland Operating Instructions Operating Instruc...

Страница 2: ......

Страница 3: ...ature switching threshold and switching times ON OFF Control Brine defroster GHX flap control 2 level control for defroster heater 2 level control for backup duct heater Settings of operating mode ON...

Страница 4: ...d by an electronic relay for electric duct heaters with modulating power control Pparallel to this a potential free changeover is available Enabling and locking of the control can be performed by an e...

Страница 5: ...nd switching times After setting the operation mode using the DIP switches the temperature thresholds have to be set via the control buttons The relevant thresholds can be changed according to the mod...

Страница 6: ...GHX regulating flap The control of the brine defroster GHX regulating flap depends on the configured temperature thresholds X1 X2 see appendix 1 and appendix 2 ON T X2 or T X1 OFF T X2 H and T X1 H D...

Страница 7: ...value of supply air temperature H Hysteresis X1 setpoint upper switching value 2 1 2 4 Settings of operating mode ON OFF control Button Temp 1 upper temperature threshold X1 keypress 3 s current switc...

Страница 8: ...contact is closed This input in combination with a backup duct heater can be used for a room thermostat and or a flow sensor 2 2 2 Status message Consumer load ON Terminal X7 Potential free output for...

Страница 9: ...rent lid of the existing plastic humidor suitable housing Operating data Housing dimensions W x D x H 160 x 120 x 90 mm Electrical connection 230 Vac 10 50 Hz Fuse T 160 mA Degree of protection IP 44...

Страница 10: ...n Terminal diagram Potential free output for notification consumer ON 230VAC and distribution Grounding External enabling contact contact open inhibiting contact closed releasing Consumer load Heating...

Страница 11: ...With intended use of brine defroster only connect at N und L pump 230VAC and distribution Grounding Potential free output for notification consumer load ON Balance leveling Middle position neutral pus...

Страница 12: ...lower threshold 3 C H Hysteresis 0 5 C Grounding 230VAC and distribution Filter time Balance leveling Middle position neutral push button days days days Keyboard Status relay e g release for defroster...

Страница 13: ...1 2 4 OFF X1 Setpoint upper threshold 50 C H Hysteresis 1 C 230VAC and distribution Potential free output for notification consumer load ON Room thermostat Status relay e g release for defroster Vent...

Отзывы: