Description and use

The pressure transducer DS1/420 converts the physical quantity pressure into an electric signal  

(4...20 mA) and is designed for use in gas explosive areas of zone 2. The pressure transducer with 

the ignition protection type nA is a non-sparking electrical resource with low power input subject to 

DIN EN 60 079-15.
Please take the properties of the pressure transducer from the paragraph „Technical specifications“ 

of this manual and from the agreed specifications. 

Mounting notes

Please check whether the ambient conditions correspond to the safety level of the data logger (am-

bient temperature, gas group, temperature class etc.) before installing the transducer in the hazard 

area. The valid erection and operating specifications must be followed. 
When mounting, please mind clean and undamaged sealing surfaces at device and measurement 

point. Screw/unscrew the device with an appropriate tool only. 
Relative pressure transducers are equipped with a pressure equalization element (DAE) and should 

preferably be horizontaly positioned. This DAE is on the transducer‘s cover lid as little round label. 

Note that this DAE is not removed or damaged. 

Electrical connection

When connecting the transducer eletrically, please note that this one won‘t ever be connected to 

intrinsically safe circuits. Following connecting conditions subject to DIN EN 60 079-15 paragraph 

23 must be met:
•  Any live parts of the transducer must be surrounded with enclosure protection degree of at least 

IP54. That means, if there are open cable heads with electrical connection within the ex-zone, 

these ones must be protected by an appropriate terminal enclosure.

•  The rated voltage of the transducer‘s voltage supply must not exceed 60VAC and 75VAC res-

pectively. 

•  Even temporary exceeding the rated voltage by 40% must be prevented by appropriate measu-

res. 

The device should be grounded via pressure port. If not possible, keep sufficient electrical ground-

ing via connector or shield. 
The pin and cable assignment are printed on the type label of the device. 

 

 

 

 

 

 

Operating  manual  of  data  acquisition  system  PWBlogg        

Содержание DS1/420

Страница 1: ...Operating manual Data acquisition system PWBlogg Pressure transducer DS1 420 ...

Страница 2: ...Paul Wegener GmbH 2 ...

Страница 3: ...s are equipped with a pressure equalization element DAE and should preferably be horizontaly positioned This DAE is on the transducer s cover lid as little round label Note that this DAE is not removed or damaged 3 Electrical connection When connecting the transducer eletrically please note that this one won t ever be connected to intrinsically safe circuits Following connecting conditions subject...

Страница 4: ... specifications Pressure measuring range Supply 12 30 VDC Output signal 4 20 mA Measurement accuracy 0 2 FS Storage operating temperature 20 C 80 C Compensated temperature range 20 C 80 C Enclosure material Rustproof steel 1 4301 Degree of protection of enclosure IP67 subject to DIN EN 60529 Process port G1 2A Media touching materials Al2O3 viton X5CrNi18 10 X10CRNiS18 9 Explosion protection optio...

Страница 5: ...tor EN 60079 0 2014 06 electrical equipment for explosion hazard areas section 0 general requirements EN 60079 15 2011 02 electrical equipment for explosion hazard areas section 15 construction test and marking of electrical equipment of ignition protection type n Marking as category 3 equipment for use in explosion hazard areas of the zone 2 II3G Ex nA IIB T4 X 20 C Ta 60 C Manufacturer Paul Wege...

Страница 6: ...Paul Wegener GmbH 6 ...

Страница 7: ...7 Operating manual of data acquisition system PWBlogg ...

Страница 8: ...ße 24 D 06493 Ballenstedt Tel Fax Internet e mail 49 0 39483 96 300 49 0 39483 96 400 www paul wegener de info paul wegener de Most recent amendment 20 04 2016 Paul Wegener GmbH Paul Wegener GmbH PWB FORM 6033 EN16 ...

Отзывы: