MACH® Series
Gas-Fired Boiler
Maintenance
Page 34
5.5.2 Auto-reset Service Codes
Code
Lockout
Description
b 08
Air pressure switch open.
The air pressure switch failed to close to indicate sufficient air flow to start the boiler.
b 18
Outlet high limit temp.
The outlet water temperature has exceeded the internal high limit temperature setting.
b 19
Return high limit temp.
The return water temperature has exceeded the internal high limit temperature setting.
b 24
Switched inlet / outlet.
The inlet water temperature has been more than 18° F above the outlet for more than
75 seconds.
b 25
Outlet temp rapid change.
The outlet water temperature is increasing too fast. Indicating low flow condition.
b 26
High exhaust back pressure. The high exhaust back pressure switch is tripped indicating a blocked stack, inlet, or
condensate system.
b 30
Max delta T.
The temperature rise across the heat exchanger is greater than maximum allowed,
indicating insufficient flow.
b 40
Flue sensor open.
The flue gas temperature sensor is indicating an open circuit.
b 52
High flue temp.
The flue temperature has exceeded the maximum allowable setting.
b 61
Air pressure switch closed.
The air pressure switch failed to open prior to starting the blower.
b 65
Fan speed incorrect.
The fan is being directed to a higher speed than it is achieving.
WARNING
If any “Manual Reset” limit device trips,
DO NOT
reset without determining and correcting the cause.
Содержание MACH Series
Страница 2: ...MACH Series Gas Fired Boiler...
Страница 42: ...MACH Series Gas Fired Boiler Parts and Technical Support Page 38 6 1 2 Wiring Series C 300...
Страница 43: ...MACH Series Gas Fired Boiler Parts and Technical Support Page 39 6 1 2 Wiring Series C 450...
Страница 53: ...MACH Series Gas Fired Boiler Appendix Page 49 8 0 APPENDIX Date Hi Low Fire O2 CO CO2 Stack Temp Action By...