P
AGE
28
TABLE 3-2 PROGRAM MODE CONFIGURATION PROCEDURE
Press and release the SCROLL key until Prog is displayed. Use the DOWN key to enter the
Program mode. Depress and release the SCROLL key to advance the display through the
parameters and their values. Use the UP and DOWN keys to adjust the parameter values.
After adjusting a parameter, depress the SCROLL key to proceed to the next parameter.
After all selections have been made, depress the UP key with a parameter code in the display
(not a setting) to exit the mode.
Note that parameter values are referred to in Degrees (
°
) and Engineering Units in the
following tables. The input selection determines what the parameter values will be.
STEP
DESCRIPTION
DISPLAY
AVAILABLE
FACTORY YOUR
CODE
SETTINGS
SETTING SETTING
1
Input Select
inPS
0 = J
°
C
Thermocouples
1
1 = J
°
F
2 = K
°
C
3 = K
°
F
4 = T
°
C
5 = T
°
F
6 = R
°
C
7 = R
°
F
8 = S
°
C
9 = S
°
F
10 = E
°
C
11 = E
°
F
12 = B
°
C
13 = B
°
F
14 = N
°
C
15 = N
°
F
16 = C
°
C
17 = C
°
F
20 = RTD
°
C
21 = RTD
°
F
30 = 0 to 5VDC / 0 to 20mA
31 = 1 to 5VDC / 4 to 20mA
32 = 0 to 50mVDC
33 = 10 to 50mVDC
34 = 0 to 25mVDC
2
Input Correction
iCor
-300
°
to 300
°
/Units
0
3
Output 1
out1
1 = On-Off Direct (Cooling)
2
2 = On-Off Reverse (Heating)
3 = Time Proportioning -
Direct (Cooling)
4 = Time Proportioning -
Reverse (Heating)
5 = Current Proportioning -
Direct (Cooling)
6 = Current proportioning -
Reverse (Heating)
7 = Position Proportioning
Reverse (Open)
8 = On-Off Latched * Direct
9 = On-Off Latched * Reverse
* Relays latch in the open position
4
Output 1
o1PL
0 to 100%
100
Percent Limit
NOTE: Fault detection is not
functional for 0-20mA inputs.