INSTRUCTION REF: IN145
ISSUE No. 2
DATE 25.02.09
Page 2 of 13
www.parry.co.uk
IMPORTANT
PLEASE READ INSTRUCTIONS FULLY BEFORE USE
MODEL PDGF FRYER & PDGFP LPG FRYER
INSTALLATION INSTRUCTIONS
IMPORTANT- YOUR ATTENTION IS DRAWN TO THE GAS SAFETY REGULATIONS. THIS
APPLIANCE MUST ONLY BE USED IN A WELL VENTILATED AREA. IT IS RECOMMENDED THAT A
MINIMUM AREA OF 450mm² PER 1 Kw (3400 Btu/HR) OF TOTAL INPUT MUST BE ALLOWED.
PARTICULAR ATTENTION SHOULD BE PAID TO THE SUPPLY OF CLEAN FRESH AIR AT LOW
LEVEL TO THE APPLIANCE.
Attention is drawn to the requirement of the fryer to be fixed to the floor by means of fixing holes in the
flanged feet.
The data plate on the rear of the appliance must be checked to ensure the appliance is suitable for the
gas supply available. This appliance must be installed in accordance with the rules in force.
BS5440 Part 2
– (Air supply)
BS6891 (Installation of low pressure gas pipe work)
BS5482 (Codes of practise for Butane and Propane gas burning installations)
Read the user instructions, read the installation instructions and ensure the correct ventilation
requirements are met. Attention should also be drawn to the need for regular servicing.
In normal use parts of the catering equipment may become hot, suitable precautions must be taken to
avoid accidental burns, therefore the appliance should be positioned to minimise the risk of accidental
touching. It is the responsibility of supervisors to warn users of this and ensure the operators of this
equipment are trained in safe operation of this appliance. It is recommended the appliance be fitted below
a ventilating hood, preferably of the extractor type, incorporating a grease filter.
POSITIONING
The appliance must not be installed on or against combustible surfaces
– minimum clearances must be:
Rear
150mm (6”)
Sides
150mm (6”) FROM ANY ADJACENT WALL
The minimum distance between the top of the appliance and any over shelf or ceiling constructed of
combustible material must be 1525mm (60”). All local fire regulations must be observed before the
appliance is commissioned the gas safety regulations require that all gas connections on the gas line are
tested for gas soundness between the gas meter and the
appliance. All packing and protective film must
be removed from the panels etc. prior to commissioning the appliance.