1.3. Detection loop wire installation:
1.3.1. Suggested loop wire specification:
UL style 1015 AWM VW-1 18AWG TA
Wire size: 18AWG.
Conductor type: Multi-core Stranded tinned.
Insulation type: PVC (better to be LXPE)
Insulation withstanding voltage: 600V.
1.3.2. Loop position and wiring guide:
Maintain a 200cm minimum distance between 2 adjacent wire loops.
Maintain a 50cm minimum distance to any metal equipment from a wire loop.
Maintain a 100cm minimum distance to a sliding metal door if any.
Loop lead in: LOOP1 lead in should be at the car entering side, and LOOP2 lead in
should be at the car leaving side.
Loop lead to terminal of LOOP1 and LOOP2 should not over cross each other.
The loop wire pair (from loop lead-in to terminal) need to be twisted (about 20 times