in
Parking and access control equipment manufactured in the UK
PF9700 Automated Hinge Gate
1.
2.
4.
3.
1. 1. On the front of the panel locate the function buttons (figure.1)
2. 2. Press and hold the up arrow and stop button together for 3 seconds (figure.2).
3. The LCD display and change to P.XXX (xxx will be a parameter number last used) you are now in
programming mode and can follow the next line of instructions. When finished and to exit programming mode
press and hold the stop button for 5 seconds.
4. To enter a parameter scroll using the arrow keys until the LCD display show the number you require
(figure.3) using the command buttons (figure.2). when the display shows the parameter number required in
the first column of the table below, press the STOP button for one second. You are now in that selected
parameter, should you wish to leave this parameter or discard any changes simply press the STOP button
again for 1 second ONLY!!. To make any adjustments in the selected parameter simply use the arrow keys
(figure.2) up or down, when the appropriate value is selected you should press and hold the STOP button
until the flashing dots between the value cease to flash (see figure.4). The value you selected has now been
saved to memory. To exit the menu press and hold the “stop” key for seven seconds until the LCD display
shows “STOP” or “AU” (figure.5) Below is a short list of commonly used parameters:
60 5
10
15
20
25
30
35
40
45
50
55
10 mins
STOP
UP ARROW
STOP BUTTON
DOWN ARROW
STOP
figure.2
P.999
figure.3
figure.1
.0.99
LED Dot
Normal State = Static
Changed State = Flashing
LED Letters
or numbers
figure.4
P a ra m e te r
N u m b e r:
D e fa u lt
Sta te :
Se t to
V a lu e :
P a ra m e te r D e sc rip tio n
E ffe c t o f th is c h a n g e :
P.999
1
3
Passw ord level to see
ALL
param eters
Allow s all param eters to be seen
P.205
8
0
Tells panel Lim its or encoder
connected
8=encoder 0=m echanical lim its
P.980
0
1~4
This param eter defines the m ethod of
operation of the barrier.
1=dead m an m ode
2= input to open
3= input to close
4= auto open/close (engin eers test m ode)
P.991
0101
4 options :-
This param eter tells the panel w hat it
is connected to. This is n eeded as the
panel is used on all of our products
0101= Barrier m aster
0100=barrier slave
0300= Bi-Folding G ate
0200= Sliding G ate
P.460
0
1
You can connect safety edges to the
panel, here you can turn it on or off.
0= no safety edges connected
1= safety edge connected
P.010
0
U p to 1000
This param eter is w here you set the
“no passage” tim er so if the barrier is
opened and no one drives through it
w ill clo se autom atically after this tim e
0=Tim er is de-activated
0-100 0=tim e in seconds
P.50A
0
1613
This says that you have connected a
secondary safety edge.
1=Secondary safety edge connected
P.660
22
22 or 23
D efin es the operation of loop 1
22= Free Exit/Entry 23= Safety
P.670
22
22 or 23
D efin es the operation of loop 2
22= Free Exit/Entry 23= Safety
P.990
0
1
Resets the panel to its factory default
1 = erases all stored param eters
P.310
50
10~50
Increase or decrease the open speed
Speed up or slow dow n opening
P.350
50
10~50
Increase or decrease the clo se speed
Speed up or slow dow n clo se
‘STOP’
figure.5
‘AU’
9
Panel Usage Guide