Purge Point Initiation/ Termination Instructions
Steps
Setup Instructions
Display
Notes
1
To initiate a purge when 'No Active
Points' are present, press (Init)
LIQUID SOL
VENT / WATER SOL
THU MAY/21/15 04:10PM WAIT
NO ACTIVE POINTS
ACTUAL
TARGET
16°F
99.3 PSIG VENT
56.4 PSIG
79.3 PSIG RESET
CYCLE HISTORY PT - -
VENTS - - - TOTAL TIME - - : - - : - -
MODE: MANUAL
Purge type must be set to 'Manual'
2
Use the
(
∧
) or (
∨
) buttons to choose
the 'Manual Purge Point' to initiate, then
press (Enter) to select.
ADJUST PURGE POINT WITH
∨ ∧
PRESS (ENTER) TO SELECT
PRESS (MENU) TO CANCEL
CHOOSE MANUAL PURGE POINT:
01
3
To terminate the purge point, press
(Term)
LIQUID SOL
VENT / WATER SOL
THU MAY/21/15 04:10PM PURGING
ACTIVE POINT: 01 03:51
ACTUAL
TARGET
16°F
99.3 PSIG VENT
56.4 PSIG
79.3 PSIG RESET
CYCLE HISTORY PT 01
VENTS 071 TOTAL TIME 01:45:56
MODE: MANUAL
To terminate a purge point in Auto mode, proceed to
Step 6
4
Use the
(
∧
) or (
∨
) buttons to move the
selection bar to 'Terminate Active Point
01' and press (Enter)
TERMINATE ACTIVE POINT 01
SELECT WITH
∨ ∧
PRESS (ENTER)
PRESS (MENU) TO RETURN
TERMINATE PURGE CYCLE
TERMINATE PURGE MENU
Selecting 'Terminate Purge Cycle' while in auto mode will
produce the same results
5
The screen now indicates that 'No Active
Points' are present
LIQUID SOL
VENT / WATER SOL
THU MAY/21/15 04:10PM WAIT
NO ACTIVE POINTS
ACTUAL
TARGET
16°F
99.3 PSIG VENT
56.4 PSIG
79.3 PSIG RESET
CYCLE HISTORY PT - -
VENTS - - - TOTAL TIME - - : - - : - -
MODE: MANUAL
6
To terminate a purge point in Auto mode,
press (term)
LIQUID SOL
VENT / WATER SOL
THU MAY/21/15 04:10PM PURGING
ACTIVE POINT: 01 03:51
ACTUAL
TARGET
16°F
99.3 PSIG VENT
56.4 PSIG
79.3 PSIG RESET
CYCLE HISTORY PT 01
VENTS 071 TOTAL TIME 01:45:56
MODE: AUTO
To terminate the purge cycle, proceed to Step 9
7
Use the
(
∧
) or (
∨
) buttons to move the
selection bar to 'Terminate Active Point
01' and press (Enter)
TERMINATE ACTIVE POINT 01
SELECT WITH
∨ ∧
PRESS (ENTER)
PRESS (MENU) TO RETURN
TERMINATE PURGE CYCLE
TERMINATE PURGE MENU
8
The screen now indicates that 'Active
Point 02' has begun purging
LIQUID SOL
VENT / WATER SOL
THU MAY/21/15 04:10PM PURGING
ACTIVE POINT: 02 04:54
ACTUAL
TARGET
15°F
78.3 PSIG VENT
39.0 PSIG
58.3 PSIG RESET
CYCLE HISTORY PT 02
VENTS 000 TOTAL TIME 00:00:00
MODE: AUTO
To cycle to the next purge point, repeat Steps 6-7
If there is only one purge point, the system will restart
'Purge Point 01'
8.5
To begin terminating the purge cycle,
press the (Term) button.
LIQUID SOL
VENT / WATER SOL
THU MAY/21/15 04:10PM PURGING
ACTIVE POINT: 01 03:51
ACTUAL
TARGET
16°F
99.3 PSIG VENT
56.4 PSIG
79.3 PSIG RESET
CYCLE HISTORY PT 01
VENTS 071 TOTAL TIME 01:45:56
MODE: AUTO