background image

3

i

nStalling

 

and

 p

owering

 

the

 tS8010

MOUNTING INSTRUCTIONS

This operator interface is designed for through-panel mounting. A panel cut-

out diagram and a template are provided. Care should be taken to remove any 

loose material from the mounting cut-out to prevent that material from falling 

into  the  operator  interface  during  installation. A  gasket  is  provided  to  enable 

sealing to NEMA 4X/IP66 specification. Install the 14 kep nuts provided and 

tighten evenly for uniform gasket compression. 

Note: Tightening the kep nuts beyond a maximum of 17 inch-pounds (1.92 

N-m) may cause damage to the front panel.

CONNECTING TO EARTH GROUND

Each TS8010 has a chassis ground terminal on the back of the unit. Your unit 

should be connected to earth ground (protective earth).

The  chassis  ground  is  not  connected  to  signal  common  of  the  unit. 

Maintaining isolation between earth ground and signal common is not required 

to operate your unit. But, other equipment connected to this unit may require 

isolation  between  signal  common  and  earth  ground. 

To  maintain  isolation 

between signal common and earth ground care must be taken when connections 

are made to the unit.

 For example, a power supply with isolation between its 

signal common and earth ground must be used. Also, plugging in a USB cable 

may connect signal common and earth ground.

1

1. USB’s shield may be connected to earth ground at the host. USB’s shield 

in turn may also be connected to signal common.

POWER SUPPLY REQUIREMENTS

The units require a 24 VDC power supply rated at 30 W. Your unit may draw 

considerably less than the rated power depending upon the options being used. 

As additional features are used your unit will draw increasing amounts of power. 

Items  that  could  cause  increases  in  current  are  additional  communications, 

optional  communications  card,  CompactFlash  card,  and  other  features 

programmed through DSI8000.

In any case, it is very important that the power supply is mounted correctly if 

the unit is to operate reliably. Please take care to observe the following points:

–  The power supply must be mounted close to the unit, with usually not 

more than 6 feet (1.8 m) of cable between the supply and the operator 

interface. Ideally, the shortest length possible should be used.

–  The wire used to connect the operator interface’s power supply should 

be at least 22-gage wire. If a longer cable run is used, a heavier gage 

wire should be used. The routing of the cable should be kept away from 

large  contactors,  inverters,  and  other  devices  which  may  generate 

significant electrical noise.

–  A power supply with an NEC Class 2 or Limited Power Source (LPS) 

and  SELV  rating  is  to  be  used.  This  type  of  power  supply  provides 

isolation to accessible circuits from hazardous voltage levels generated 

by a mains power supply due to single faults. SELV is an acronym for 

“safety  extra-low  voltage.”  Safety  extra-low  voltage  circuits  shall 

exhibit voltages safe to touch both under normal operating conditions 

and  after  a  single  fault,  such  as  a  breakdown  of  a  layer  of  basic 

insulation or after the failure of a single component has occurred.

8.925

(226.7)

2.975

(75.6)

12.25 (311.2)

6.125 (155.6)

11.725 (297.8)

8.40

(213.4)

14X 

.188 (

4.8)

All tolerances ±0.010" (±0.25 mm).

ALL NONINCENDIVE CIRCUITS MUST BE WIRED USING 

DIVISION 2 WIRING METHODS AS SPECIFIED IN THE NATIONAL 

ELECTRICAL CODE, NFPA 70 FOR INSTALLATION WITHIN THE 

UNITED STATES, OR AS SPECIFIED IN THE CANADIAN 

ELECTRICAL CODE FOR INSTALLATION IN CANADA.

The protective conductor terminal is bonded to conductive 

parts  of  the  equipment  for  safety  purposes  and  must  be 

connected to an external protective earthing system.

WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT 

EQUIPMENT WHILE THE CIRCUIT IS LIVE OR UNLESS THE AREA 

IS KNOWN TO BE FREE OF IGNITABLE CONCENTRATIONS.

i

nStalling

 a

n

 o

ption

 c

ard

Each  option  card  comes  with  a  cable  for  communications  and  three 

screws for attaching the option card to the TS’s main board.

To install the option card, remove all power and I/O communications 

cables from the unit and remove the rear cover.  Connect the cable from the 

option card to the connector on the main board. Be sure both ends of the 

cable are firmly seated into their appropriate connector housings. Use the 

three screws provided to mount the option card to the main board as shown 

in Figure 1.

Carefully  replace  the  rear  cover  by  reversing  the  instructions  for 

removing the rear cover.

TYPICAL EXPANSION CARD INSTALLATION

Figure 1

WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT

EQUIPMENT UNLESS POWER HAS BEEN DISCONNECTED

AND THE AREA IS KNOWN TO BE NON-HAZARDOUS.

Содержание TS8010

Страница 1: ...OF PACKAGE TS8010 Operator Interface Panel Gasket This hardware bulletin Template for panel cutout Hardware packet for mounting unit into panel Terminal block for connecting power ORDERING INFORMATION DESCRIPTION PART NUMBER 10 4 TFT VGA Display Operator Interface indoor USB Host Isolated Comms TS8010 00 02 CANopen Option Card 8000 CB 00 00 Profibus DP Option Card 8000 PB 00 00 DeviceNet Option Ca...

Страница 2: ...Storage Humidity 80 maximum relative humidity non condensing from 0 to 50 C Vibration according to IEC 68 2 6 Operational 5 to 150 Hz in X Y Z direction for 1 5 hours 2 g Shock according to IEC 68 2 27 Operational 35 g 11 msec in 3 directions Altitude Up to 2000 meters 9 CERTIFICATIONS AND COMPLIANCES SAFETY IEC 61010 1 EN 61010 1 Safety requirements for electrical equipment for measurement contro...

Страница 3: ...terface Ideally the shortest length possible should be used The wire used to connect the operator interface s power supply should be at least 22 gage wire If a longer cable run is used a heavier gage wire should be used The routing of the cable should be kept away from large contactors inverters and other devices which may generate significant electrical noise A power supply with an NEC Class 2 or...

Страница 4: ...In order to access data from the CompactFlash card via the USB device port a driver must be installed on your computer This driver is installed with DSI8000 and is located in the folder C Program Files Parker DSI8000 Device after DSI8000 is installed This may have already been accomplished if your TS8010 was configured using the USB port Once the driver is installed connect the TS8010 to your PC w...

Страница 5: ...N 6 COMM 3 COMM 1 TxB 5 B 2 TxA 4 A 5 DH485 COMMUNICATIONS The TS8010 s RS422 485 COMMS port can also be used for Allen Bradley DH485 communications WARNING DO NOT use a standard DH485 cable to connect this port to Allen Bradley equipment A cable and wiring diagram are available from Parker SSD Drives TS to AB SLC 500 Connections RJ45 SSD Name RJ45 A B Name 1 TxB 1 A 2 TxA 2 B 3 8 RxA 24V 4 7 RxB ...

Страница 6: ...uchscreen is fully functional as soon as the operator interface is initialized and can be operated with gloved hands TROUBLESHOOTING YOUR TS8010 If for any reason you have trouble operating connecting or simply have questions concerning your new TS8010 contact Parker SSD Drives technical support For contact information refer to the back page of this bulletin for phone and fax numbers EMAIL info us...

Страница 7: ...isposed of in fire or in a manner whereby it may be damaged and its contents come into contact with human skin The battery used by the TS8010 is a lithium type CR2025 BATTERY INVERTER TOP BOTTOM WARNING EXPLOSION HAZARD THE AREA MUST BE KNOWN TO BE NON HAZARDOUS BEFORE SERVICING REPLACING THE UNIT AND BEFORE INSTALLING OR REMOVING I O WIRING AND BATTERY WARNING EXPLOSION HAZARD DO NOT DISCONNECT E...

Страница 8: ... CompactFlash socket Cards are available at most computer and office supply retailers CompactFlash can be used for configuration transfers larger configurations data logging and trending Information stored on a CompactFlash card by a TS8010 can be read by a card reader attached to a PC This information is stored in IBM Windows PC compatible FAT16 file format Note Do not remove or insert the Compac...

Отзывы: