Installation Instructions for 4041-5300 Electrical Connection Kit
for Self-Regulating Bundles
2
Parker Hannifin Corporation
Parflex Division
Ravenna, OH USA
www.parker.com/pfd
NOTE
An HSB (heat shrinkable boot) or
ESB (end seal boot) or RTV sealant
is recommended for sealing the
bundle end.
NOTE
If an HSB (heat shrinkable boot)
or ESB (end seal boot) is used to
seal the end of the bundle, the
boot must be installed prior to
installing the base of the heating
cable.
Bundle End Preparation: Used in all connection types.
NOTE
The IEEE standards (515-2004)
for heating cables require the
use of GFEPDs with a nominal 30
milliampere trip level for “piping
systems in classified areas, those
areas requiring a high degree of
maintenance, or which may be
exposed to physical abuse or
corrosive atmospheres.”
1
Measure 24 inches from end of
bundle and carefully cut around
and lengthwise through jacket and
insulation. Do not cut into heating
cable or tubing.
2
Remove jacket, insulation and heat
transfer foil.