background image

Page 2 

/ Bulletin 100-50-1

LEGEND

TEST POINTS and PIN JUMPERS 

TP1

Test Point 1

positive connection point to millivolt voltmeter to 

read set point temperature

TP2

Test Point 2

negative connection point as above

P1

Pin Jumper 1

voltage or current input selector

P2

Pin Jumper 2

TTL logic or 24-120 VAC Pulse Width Modulated 

signal input selector

P4

Pin Jumper 4

internal power selector - DO NOT CHANGE

P5

Pin Jumper 5

force valve open switch - valve will open and will 

remain open as long as jumper is installed

P6

Pin Jumper 6

force valve closes switch - valve will close and 

remain closed while jumper is installed

P7

Pin Jumper 7

 temperature sensor enable selector

P8

Pin Jumper 8

“open on rise” logic selector

P9

Pin Jumper 9

“close on rise” logic selector

P10

Pin Jumper 10

SEI .5 to SEI-11 valve selector (1596 step stroke)

P11

Pin Jumper 11

CDS-8 valve selector (3193 step stroke)

P12

Pin Jumper 12

all other valves selector (6386 step stroke)

WIRING CONNECTIONS

PID+

connect positive side of 4-20 ma or 0-10 VDC signal

INPUT

connect negative side of 4-20 ma or 0-10 VDC signal

BLACK

connect black valve lead

WHITE

connect white valve lead

GREEN

connect green valve lead

RED

connect red valve lead

Square Wave

connect TTL logic (5 VDC) step signal

DIRECTION

connect TTL logic direction signal.  5 VDC = OPEN, 0 VDC 

= CLOSE

24 VAC

2 connections for 24 VAC or 24 VDC @ 40 VA isolated 

power input

PUMPDOWN

2 connections for pumpdown contacts. When “shorted” 

the valve will close and remain closed. When “open” the 

valve will control normally. For alternate operation see 

5. 

under “Wire the Board” pg 3.

TEMP SENSOR

2 connections for supplied 2 k type B thermistor. Not 

polarized.

Blank

no connection - for high voltage input isolation.

AC PULSE

for one leg of 24-120 VAC, 3-30 second Pulse Width 

Modulated signal. 

Blank

no connection - for high voltage input isolation.

AC PULSE

for the other leg of 24-120 VAC, 3-30 second Pulse Width 

Modulated signal.

NOTE:

  

Not all inputs or pin jumpers will be used.  See Configuration 

instructions.

Valves  of  any  capacity  except  2500  step 
valves such as CDST-4 & CDST-7 (see note 
on  page  2).  Pin  jumpers  on  the  face  of  the 
board  will  permit  changes  in  board  control 

parameters  to  suit  particular  applications. 
Figure 1 shows the layout of the board with 
connection points labeled.

Figure 

1

P6

P5

P1

P2

P12

P11

P10

P9

P8

TP2

Set Point 

Potentiometer

TP1

P7

24-120 VAC

PWM Pulse

No Conn.

Temp. Sensor

Pumpdown

24VAC

TTL 

Direct.

TTL

Wave

Red

Green

PID+

PID-

Black

White

P4

The  Sporlan  TCB  has  been  developed  to 
allow  the  control  of  most  Sporlan  electric 
valves  with  the  use  of  a  generic  PID  or 
similar controller, or with the addition of the 
Sporlan sensor, to perform as a stand alone 
temperature controller. In addition to the 0 
to  10  volt  DC  or  4  to  20  milliamps  signal 
usual from PID controllers, the TCB can be 
configured to modulate a valve in response 
to  a  TTL  (5  volt)  signal,  or  a  24-120  volt 
AC pulse of three to thirty seconds duration. 

The 

TCB

 may be ordered less potentiometer 

if  an  external  signal  (e.g.  4-20ma)  is  to  be 
used.  See  ordering  instructions.  The  board 
was  designed  for  easy  standoff  mounting 
in electrical panels supplied by others, and 
with  screw  terminal  wiring  connections. 
The  unit  is  small  (3.5”  x  4.0”)  and  eco-
nomical  and  requires  only  24  volts  AC  or 
24 VDC at 40 VA for both board and valve 
power. Operating ambient and storage tem-
perature is -10°F to 160°F.

The 

TCB

  has  been  designed  to  work  with 

Sporlan  SEI/SEH  Electric  Expansion 
Valves,  CDS  Electric  Suction  Control 
Valves,  and  SDR  Electric  Hot  Gas  Bypass 

FOR USE ON REFRIGERATION and/or AIR CONDITIONING SYSTEMS ONLY

Bulletin 100-50-1, December 2010 supersedes Bulletin 100-50-1, January 2006 and all prior publications.