Parker Sporlan 952567 Скачать руководство пользователя страница 9

SD-324M / Page 9

LABEL COLOR

Prng

PSI

Green

150

(v-.5) x 37.5

None / Silver

300

(v-.5) x 75

Yellow

500

(v-.5) x 125

Figure 7 - Pressure Sensor Cable

Table 3 - Pressure Transducer Specifications

Troubleshooting Recommendations

As with any refrigeration component troubleshooting, actual 

system conditions should be verified with a gauge set and a cali-

brated temperature sensor (i.e verify actual superheat and refriger-

ant condition). This system information is valuable in determining 

whether it is component related or system related. 

For systems or applications that experience light loads on the Kel-

vin II circuit, it is important that the heat exchanger and refrigerant 

lines are sized correctly. This will ensure proper oil return and will 

minimize the effects of oil logging in the heat exchanger. Many 

heat exchanger manufacturers recommend a hot gas bypass for 

loads below 50%.

Sensors 

Failed sensors will trigger an alarm. An alarm code will show 

which sensor is mis-wired, disconnected, or faulty. The alarm will 

persist until the problem is corrected.

Failed temperature sensors

 may read extremely low or infinite 

resistance when tested with an ohmmeter. Readings should be 

taken with the sensor disconnected from the Kelvin II. A missing 

or disconnected temperature sensor will read 

-60

 on the controller.

Temperature sensor output can be checked by measuring the DC 

voltage across the sensor wires and consulting the tables in  

Appendix K and Appendix L.

2K and 3K sensors have approximately 1.9KΩ and 2.8KΩ, 

respectively, at 80̊F measured across sensor wires.

Pressure transducers

 must be installed tight enough to depress 

the valve stem in the fitting. Failure to do so will result in errone-

ous pressure readings and possibly leaks.

Pressure transducers should be tested while connected to the 

controller and powered. Test at the controller terminals. Voltage 

between terminals 34

 

and 35

 

should be 4.8 - 5.2 volts DC. Voltage 

between 33 and 34 should be between 0.5 and 4.5 volts DC.  

See Table 1 - Pressure Transducer Wire Colors.

To test the accuracy of the transducer, use a gauge set to obtain the 

actual system pressure. For volts-to-pressure conversion, measure 

the voltage between terminals 33 and 34. Identify the pressure 

transducer used and find the correct range 

Prng

 in Table 3. 

Substitute the measured voltage (v) into the formula in the PSI 

column. The result should be within 3 psi of the actual system 

pressure shown on the gauge set. If not, check the transducer for 

proper installation, correct Schrader valve, and verify the pressure 

range identified on the transducer.

To test the transducer cable, disconnect the cable from the trans-

ducer and check for 4.8 - 5.2 volts between terminals 

+

 and 

 .  

See Figure 7 - Pressure Sensor Cable.

ALARMS

If the superheat is 2 degrees below setpoint for 30 seconds, the 

controller will display the alarm 

LSHA

Alarms will persist until the problem is corrected.

ALARM DESCRIPTION

ACTION

PSAL

Pressure Sensor 

Failure

Pumpdown (open terminals 

19 & 20) and close EEV 

tSAL

Suction Temp  

Sensor Failure

Pumpdown (open terminals 

19 & 20) and close EEV 

LSHA

Low Superheat

If superheat is 2 degrees or less,

EEV will close more aggressively

HSHA

High Superheat

No system response

Table 4 - Alarm Actions

Содержание Sporlan 952567

Страница 1: ...controller in a rain tight protected location using the supplied DIN Rail To leave enough working space the suggested mounting area is 10 inches high and 5 inches wide The minimum depth is 3 inches Se...

Страница 2: ...emperature Sensor Type Select 2K or 3K see pictures below Default is 2K 4 Set Pt4P Pressure Sensor Type Select Absolute or Gauge sealed following the steps above Default is Gauge 5 Set Un_t Temperatur...

Страница 3: ...rigerant flow during power loss Refrigeration Superheat control on cases with EEPR preferred method The Kelvin II will regulate the refrigerant flow entering the evap orator to achieve the superheat s...

Страница 4: ...etting a Bleed Step Position B_ST allows a small amount of liquid refrigerant to pass through the EEV Normal industry practice is to set a bleed to equalize the system in 3 5 minutes The Kelvin II als...

Страница 5: ...gized red jacks punch down brown and brown white wires between 2 jacks See Figure 4 Kelvin IId Kelvin IIsd or Kelvin IIs Kelvin IIsd or Kelvin IIs Kelvin IIsd or Kelvin IIs Kelvin IIsd or Kelvin IIs c...

Страница 6: ...ress Default address for each controller is 1 NOTE AddR is the Modbus address CAdR is the controller display address Modbus Connection Requirements See Figure 5 Modbus Wiring Wire Type 18 AWG Universa...

Страница 7: ...ssary however to fine tune the PID settings in applications where systems experience rapid transient conditions such as frequent impulse changes in loading or mass flow rates In most instances adjustm...

Страница 8: ...ucer set up in controller 0 300 etc Pressure Transducer Type correct transducer set up in controller gauge sealed vs absolute Temperature Sensor Type correct sensor set up in controller 2K or 3K see A...

Страница 9: ...tively at 80 F measured across sensor wires Pressure transducers must be installed tight enough to depress the valve stem in the fitting Failure to do so will result in errone ous pressure readings an...

Страница 10: ...R 410A 417A R 417A R 422A R 422D R 507A R 744 R 245FA R E5 R 438A 401B R 401B 408A R 408A 508A R 508A 508b R 508B t4p Temperature Sensor Type Readout Description typ3 3K Thermistor typ2 2K Thermistor...

Страница 11: ...Pumpdown Mode Low Resistance or short on T3 S 4 Auxiliary Temperature 2 60 to 150 F 51 1 to 65 6 C rELA Relay Status Display Description dEng Relay is de energized open Eng Relay is energized open St...

Страница 12: ...on pressure sensor range type 14 7 to 485 psi 1 03 to 9 30 Bar max range H_op Maximum Operating Pressure Values depend on pressure sensor range type 5 to 485 psi 1 37 to 34 47 Bar max range C_in Cut i...

Страница 13: ...Sensor Type Readout Description t4p3 3k thermistor t4p2 2k thermistor 4 Chosen at Setup Pressure Sensor Type Absolute Pressure Type U Gauge Sealed Pressure Type Pressure Sensor Range Avto Based on Ref...

Страница 14: ...with well Can be used without well 3K Sensor Brass 952551 Not used with well Parker Sporlan Pressure Transducers Select one per controller based on refrigerant PSPT0500SVSP S 952576 0 500 psis transd...

Страница 15: ...Interface to dry contact or open collector Analog Inputs 4 Temperature Sensors 2Kohm 3Kohm optional 1 Pressure Transducer 5 4 5VR Relay Outputs 100 240VAC 3A ind 250V 22 28VDC 250mA digital output w...

Страница 16: ...ay L1 L2 EEV Load Line Liquid Line Solenoid Valve 10 14 minimize 1 2 ideal Evaporator Aux Temp T4 Internal Relay Rated 240v 3A T3 can be used as an Auxillary Temperature Input or a Pumpdown Input sign...

Страница 17: ...nce from the pressure transducer 2 Use Scotch BriteTM to clean the copper line at the installation location Remove oxides and dirt to increase sensor accuracy 3 Fasten the suction temperature sensor a...

Страница 18: ...Low Operating Pressure 0 to 150 psi 0 to 13 34 Bar 6 Maximum Operating Pressure 0 to 150 psi 0 to 13 34 Bar 7 Temperature Cut in 60 to 125 F 51 to 51 7 C 8 Temperature Cut out 60 to 125 F 51 to 51 7 C...

Страница 19: ...0 to 91 6 C 1 Suction Pressure Depends on Pressure Sensor Range and Type 15 to 500 PSI 1 01 to 34 47 Bar Maximum Range 2 Saturation Temperature 60 to 150 F 51 1 to 65 6 C 3 Suction Temperature 60 to 1...

Страница 20: ...90 3 322 21 1 6 3 161 3 293 20 6 5 3 133 3 263 20 0 4 3 104 3 233 19 4 3 3 075 3 203 18 9 2 3 046 3 173 18 3 1 3 017 3 142 17 8 0 2 988 3 112 17 2 1 2 958 3 082 16 7 2 2 929 3 051 16 1 3 2 900 3 021 1...

Страница 21: ...9 38 9 102 0 746 0 777 39 4 103 0 734 0 766 C F Range VDC 40 0 104 0 723 0 754 40 6 105 0 712 0 743 41 1 106 0 702 0 731 41 7 107 0 691 0 720 42 2 108 0 681 0 710 42 8 109 0 670 0 699 43 3 110 0 660 0...

Страница 22: ...23 4 189 21 1 6 3 999 4 164 20 6 5 3 975 4 139 20 0 4 3 951 4 114 19 4 3 3 926 4 088 18 9 2 3 901 4 062 18 3 1 3 875 4 035 17 8 0 3 849 4 008 17 2 1 3 823 3 981 16 7 2 3 796 3 953 16 1 3 3 769 3 924 1...

Страница 23: ...0 58 3 137 0 499 0 520 58 9 138 0 490 0 511 59 4 139 0 481 0 502 60 0 140 0 473 0 493 60 6 141 0 464 0 484 61 1 142 0 456 0 475 61 7 143 0 448 0 467 62 2 144 0 440 0 459 62 8 145 0 432 0 450 63 3 146...

Страница 24: ...Parker Hannifin Corporation Sporlan Division 206 Lange Drive Washington MO 63090 USA phone 636 239 1111 fax 636 239 9130 www sporlan com 122011 SD 324M 2011 Parker Hannifin Corporation...

Отзывы: